Correspondence OFFICE COPY
October 14, 2004 = . '�'
CITY OF TIGARD
•
OREGON
Arjae Sheet Metal
5510 SE Mclaughlin Boulevard
Portland, OR 97202
RE: GAS PIPING FOR COOKING EQUIPMENT
Project Information -
Building Permit: MEC2004 -00683 Construction Type: VN
Tenant Name: Halal Meat & Med Food Occupancy Type: M
Address: 11535 SW Pacific Highway
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 --
01) 1999 edition. The submitted plans are approved subject to the following.
1. The piping system shall be tested at 10 pounds per square inch for not less than 15
minutes with no perceptible drop in pressure. C406.4.1 OMSC
2. Each appliance shall be provided with a shutoff valve separate from the appliance.
The shutoff valve shall be located in the same room and within six feet of the
appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Respect
rian Bla ► ,
Senior ' ans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772