Loading...
Correspondence OFFICE COPY October 14, 2004 = . '�' CITY OF TIGARD • OREGON Arjae Sheet Metal 5510 SE Mclaughlin Boulevard Portland, OR 97202 RE: GAS PIPING FOR COOKING EQUIPMENT Project Information - Building Permit: MEC2004 -00683 Construction Type: VN Tenant Name: Halal Meat & Med Food Occupancy Type: M Address: 11535 SW Pacific Highway The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -- 01) 1999 edition. The submitted plans are approved subject to the following. 1. The piping system shall be tested at 10 pounds per square inch for not less than 15 minutes with no perceptible drop in pressure. C406.4.1 OMSC 2. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Respect rian Bla ► , Senior ' ans Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772