Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
4 June 10, 2008
RE: MECHANICAL
Proiect Information T I GARD
Building Permit: MEC2008 -00108 Construction Type: 5B
Tenant Name: America's Tire Occupancy Type: M /S -1
Address: 11462 SW Pacific Hwy. Occupant Load: 73
Area: 8817 Sq. Ft. Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty
Code (OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition.
The submitted plans are approved subject to the following.
Gas line is not in the scope of this permit.
1. Ductwork shall be supported in accordance with Sheet Metal & Air
Conditioning Contractors National Association, Inc. (SMACNA)
2. Each appliance shall be provided with a shutoff valve separate from the
appliance. The shutoff valve shall be located in the same room and within
six feet of the appliance served. Access shall be provided to the shutoff
valve. C409.5 OMSC
3. Equipment and appliances regulated by this code requiring electrical
connections shall have a positive means of disconnect in accordance with
the Electrical Code. 301.7 OMSC
4. Permanent equipment supported by the structure, 400 lbs and over, shall
have their attachments designed in accordance with the Building Code.
301.16 OMSC
5. Appliances shall be accessible for inspection, service, repair or
replacement without removal of permanent construction. 306.1 OMSC
6. Manufacturer's installation instructions shall be available on the jobsite at
the time of inspection. 304.1 OMSC
7. Condensate from cooling coils or evaporators shall be collected and
discharged to an approved plumbing fixture or disposal area. 307.1 OMSC
8. Smoke detectors shall be installed in return air systems with a design
capacity greater than 2000 cfm. Upon activation, the smoke detector shall
shut down the air distribution system. Smoke detectors shall be connected
Phone: 503.639.4171 • Fax: 503.684.7297 . • www.tigard - or.gov • TTY Relay: 503.684.2772
Fi to a fire alarm system or shall activate an audible and visible alarm at a
constantly attended location. 606.2, 606.4 & 606.4.1 OMSC
• 9. Suspended -type unit heaters shall be supported by non - combustible
elements that are designed and constructed to accommodate the weight
and dynamic loads and shall be sway braced. 920.2 OMSC
10. Inspector may require additional sway bracing at the final installation
inspection.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval
stamp, shall be maintained on the jobsite. The plans shall be available to the
Building Division inspectors throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all
new buildings in such a position as to be plainly visible and legible from the
street or road fronting the property.
When .submitting revised drawings or additional information, please attach a copy
of the enclosed City . of Tigard, Letter of Transmittal. The letter of transmittal
assists the City of Tigard in tracking and processing the documents.
Respectfull ,
an elson,
Senior Plans Examiner
(503)718 -2436
dann@tigard- or.com
City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
March 14, 2008 q
,
RE: MECHANICAL TI
Project Information T I GARD
Building Permit: MEC2008 -00108 Construction Type: 5 -B
Tenant Name: America's Tire Occupancy Type: M /S -1
Address: 11462 SW Pacific Hwy. Occupant Load: 73
Area: 8,817 Sq. Ft. Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The
following corrections need to be submitted for review prior to issuing of the permit
1) Provide structural drawings and calculations for connection of RTU's to curb. '-
2) Provide gas line drawing showing equipment BTU's. O.brON This . 4:51?..0A f - r -
3) Drawings on plans that say install "if required" will be required to be installed.
This would mean that all your duct work will have to be seismically braced as
per drawing 02 on M2.0 Provide drawing that shows the installation of all
equipment and ductwork.
4) Provide cut sheet for radiant heaters.
When responding, provide an itemized letter stating -in what way each numbered
issue has been addressedin the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
. Respectful , P.'
• • an Nelson,
Senior Plans Examiner
(503) 718 -2436
dann a @ tigard- or.gov
Phone: 503.639.4171 • Fax: 503.684.7297 .. www.tigard- or.gov • TTY Relay: 503.684.2772