Bulletin 136 Rev.O W
® Model Fl FR
Model F1 FR Recessed
Quick Response
Ej
CD
Sprinklers CD
0
Model F1 FR Sprinkler Types
Standard Upright F - 4. �° :� _- •
Standard Pendent
Conventional r
Vertical Sidewall r-
Horizontal Sidewall 1,0,(' ,.,,/ .
- HSW 1 Deflector --
Model F1 FR Recessed Sprinkler Types •
Recessed Pendent Upright Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector
Listings & Approvals 1
1. Listed by Underwriters Laboratories, Inc. (UL) 'F
2. Listed by Underwriters' Laboratories of Canada (ULC)
3. Certified by FM Approvals
4. Loss Prevention Council (LPC, UK) - � , ' L. F
5. NYC BS&A No. 587 -75 -SA `' -;.-
6. Meets MIL- S -901C and MIL -STD 167 -1
7. Verband der Schadenversicherer (VdS, Germany)
8. NYC MEA 258 -93 -E
UL Listing Category Vertical Sidewall Conventional
Sprinklers, Automatic & Open
• Quick Response Sprinkler
UL Guide Number
VNIV .0" -
cr
V.
I r „.,,
Patents: US Patent No 6,374,920 Applies to i
Model Fl FR Vertical Sidewall Sprinklers.
Product Description Horizontal Sidewall Recessed Pendent
Reliable Models F1 FR and F1 FR Recessed Sprinklers are HSW 1 Deflector (Model FP Shown)
quick response sprinklers which combine the durability of a pands, forcing the bubble smaller and smaller as the liquid
standard sprinkler with the attractive low profile of a decorative pressure increases. Continued heating forces the liquid to
sprinkler. push out against the bulb, causing the glass to shatter,
The Models F1 FR and F1 FR Recessed automatic sprinklers opening the waterway and allowing the deflector to distrib-
utilize a 3.0 mm frangible glass bulb. These sprinklers have ute the discharging water.
demonstrated response times in laboratory tests which are
five to ten times faster than standard response sprinklers. This Application
quick response enables the Model Fl FR and Fl FR Recessed Quick response sprinklers are used in fixed fire protec-
sprinklers to apply water to a fire much faster than standard tion systems: Wet, Dry, Deluge or Preaction. Care must be
sprinklers of the same temperature rating. exercised that the orifice size, temperature rating, deflector
The glass bulb consists of an accurately controlled amount style and sprinkler type are in accordance with the latest
of special fluid hermetically sealed inside a precisely manu- published standards of the National Fire Protection Asso-
factured glass capsule. This glass bulb is specially con- ciation or the approving Authority Having Jurisdiction.
structed to provide fast thermal response. The balance of Quick response sprinklers are intended for installation as
parts are made of brass, copper and beryllium nickel. specified in NFPA 13, FM Global Loss Prevention Data
At normal temperatures, the glass bulb contains the fluid Sheet 2 -8N or other applicable standards. Quick response
in both the liquid and vapor phases. The vapor phase can sprinklers and standard response sprinklers should not be
be seen as a small bubble. As heat is applied, the liquid ex- intermixed.
The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523
•
Model Fl FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
- I tallitio _DaIa:
K Factor Sprinkler Identification
Sprinkler Type Sprinkler Approval Number (SIN)
US Metric Height Organization SSU I SSP
Standard - Upright (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position
X" (15mm) Standard Orifice with y," NPT (R),) Thread 5.6 80 2.2" (56mm) 1,2,3,4,5,6,7 R3625 R3615
'%;' (20mm) Large Orifice with y" NPT (R /4)Thread 8.0 115 2.3" (58mm) 1,2,3,4,7,8 R3622 R3612
%R' (17mm) Small Orifice with y," NPT (R)2) Thread 4.2 60 2.2" (56mm) 1,2,8 R3623 R3613
%" ( 10mm) Small Orifice with )Z " NPT (R)Z)Thread 2.8 40 2.2 " (56mm) 1,2,8 R3621 R3611
10mm Orifice XLH with Rye" Thread 4.2 60 56mm 4,6,7 R3624 R3614
Conventional-Install in Upright or Pendent Position
10mm Orifice XLH with Rye Thread 4.2 60 56mm — R3674
15mm Standard Orifice with y" NPT (RX) Thread 5.6 80 56mm 4,6,7 R3675
20mm Large Orifice with 3 /4" NPT (R %)Thread 8.0 115 58mm 4,7 R3672
(1) Polyester coated upright UL and ULC listed corrosion resistant.
. + �, ;1 ..
/ r s'
U;:1;1 .5
s
*!,*°.2.- f 7F I t , �77I,�--e--�
�nU
' .
Upright Pendent Conventional
Model F1 FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
- Installation Data:
Nominal Thread K Factor Sprinkler Approval Sprinkler Identification
Orifice Size US Metric Height Organizations Number (SIN)
y," (15mm) X" NPT (R' //) 5.6 80 2.2" (56mm) 1,2,3,4,5,7,8 R3615
"42" (20mm) x" NPT (R 8.0 _ 115 _2.3" (58mm) 1,2,3,8 _ R3612
%R' (11mm) y" NPT (R1/2) 4.2 60 2.2" (56mm) 1,2,8 R3613
Y (10mm) )2" NPT (R1/2) 2.8 40 2.2" (56mm) 1,2,8 R3611
10mm Rae 4.2 60 _ 56mm 4,7 R3614
(1) Refer to escutcheon data table for approvals and dimensions.
t- 2 5/8" 041. (66.7mm)
2 1/e HOLE DIA. _` HOLE IN CEILING
(s7.Tmm)
I 15/I6' DM � 2 5/I6" DIA. [58.7m/n]
F 149.2mm) CUP
=_ 4= r= —� _q_ ,
— _ 1' X f /T REDUCER I I I 1" X r /2' REDUCER —
TURN COLLAR y l t —
UNTIL TIGHT
AGAINST SPRINKLER
WRENCH BOSS I
I _ _
J I
g _____- -I,
/— , m- d am FACE OF FITTING TO I'T CEILING W' -
4LUU5 THEN' ('I CEILING D/MCN5/0N
+ C / / �� + + - - - 03 W
FACE OF FITTING
I _ _Ii , I (�\ .` I DIMENSION
vs
m A 4'(I)
2 27/32 014. ADJUSTMENT
(72.2mm) 136FG01_C t
T ITerGOS_A
(I) REFER TO FI & F2 ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS. (I) REFER TO FP ESCUTCHEON RATA TABLE FOR .APPROVALS AND DIMENSIONS.
2.
Model F1 FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Thread K Factor Sprinkler Approval Sprinkler
Orifice Size US Metric Height Organizations Num beer r (SIN)
Number
'/z" ' /z" NPT(R') 5.6 80 2.2" (56mm) 1,2,3,6,8
R3685
15mm '/2" NPT (R'h) 5.6 80 2.2" (56mm) 4 (1)
(1) LPC Approval is for Pendent position only.
Orientation Deflector to Ceiling
� Dimension (Min. - Max.)
- Upright 4" - 12" (102mm - 305mm)
r ; . / III Ill Pendent 6" - 12" (152mm - 305mm)
- e.'
Vertical Sidewall
US Patent No. 6,374,920
Model F1 FR Quick Response Horizontal Sidewall Sprinkler
_ Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Approval Organizations
K Factor and Type of Approval Sprinkler
Identification
Nominal Thread Sprinkler Light Ordinary Number (SIN)
Orifice Size US Metric Length Hazard Hazard
y" (15mm) }Z" NPT(R'/z) 5.6 80 2.63" (67mm) 1,2,3,5,8 1,2,5,8 R3635
NOTE: UL, ULC and MEA Listing permits use with F1 or F2 recessed escutcheon.
136E04 r A
d (1) FACE W WALL TO
DIMENSION
:f ; -1. _ < ,e� 7 1/4 MIN.
.. (31.8mm)
} `� " \ , 2 7/4" HOLE DIA _ ( 8 57.2mm ? ? m [ J r-1/8"
3.2m (101.6mm- 152.4mrnJ
f i \
' i- a °. 4, .fir' 1" X 7/2" REDUCER - CEILING TO
DEFLECTOR
1 -w !- --r, AP_ -
�
/16" DIA. I _ _ _ I� „ ll -
7 15
Horizontal Sidewall [49.2 mm) �� i� 11111'.1 1 I 2 27/32" DIA.
.. . -+ �1� r ( 72.2mmj
l�
TURN COLLAR UNTIL
7
TIGHT AGAINST SPRINKLER \ \
WRENCH BOSS.
ADJUSTMENT (I
(1) REFER TO ESCUTHCEON DATA TABLE FOR APPROVALS AND DIMENSIONS
3.
•
' , Installation
Quick response sprinklers are intended for installation as tie vacuuming. Remove any sprinkler which has been
specified in NFPA 13, FM Global Loss Prevention Data Sheet painted (other than factory applied) or damaged in any
. 2-8N or other applicable standards. Quick response sprin- way. A stock of spare sprinklers should be maintained to
kiers and standard response sprinklers should not be inter- allow quick replacement of damaged or operated sprin-
mixed. klers. Prior to installation, sprinklers should be maintained
The Model F1FR Recessed Quick Response Sprinklers are to in the original cartons and packaging until used to mini -
be installed as shown. The Model Fl or F2 Escutcheons illus- mize the potential for damage to sprinklers that would
trated are the only recessed escutcheons to be used with the cause improper operation or non - operation.
Model Fl FR Sprinklers. The use of any other recessed escutch- Sprinkler Types
eon will void all approvals and negate all warranties. Standard Upright
When installing Model Fl FR Sprinklers, use the Model D Sprin-
kler Wrench. When installing Model F1FR Recessed Pendent or Standard Pendent
Sidewall Sprinklers, use the Model GFR1 Sprinkler Wrench. Any Conventional
other type of wrench may damage these sprinklers. Sidewall (Vertical, Horizontal HSW1)
Glass bulb sprinklers have orange bulb protectors to minimize Recessed Pendent
bulb damage during shipping, handling and installation. RE- Recessed Horizontal Sidewall HSW1
MOVE THIS PROTECTION AT THE TIME THE SPRINKLER
SYSTEM IS PLACED IN SERVICE FOR ARE PROTECTION. Re- Finishes (1) (2) _
moval of the protectors before this time may leave the bulb Standard Finishes
nerable to damage. RASCO wrenches are designed to install Sprinkler Escutcheon .
sprinklers when covers are in place. REMOVE PROTECTORS Bronze Brass
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS Chrome Plated Chrome Plated (3)
TO REMOVE THE PROTECTORS. White Polyester Coated White Painted (3)
Temperature Ratings Special Application Finishes
Sprinkler Sprinkler Escutcheon
Classification Temperature Max. Ambient Bulb Bright Brass Bright Brass
°C °F Temp. Color Black Plated Black Plated
Ordinary 57 135 100°F(38°C) Orange Black Paint Black Paint
Ordinary 68 155 100°F(38°C) Red Off White Off White
Intermediate 79 175 15OF(66°C) Yellow Satin Chrome Satin Chrome
Intermediate 93 200 150°F (66°C) Green
High (1) 141 286 225°F(107°C) Blue ( Other finishes and colors are available on special order.
Consult the factory for details.
(1) Not available for recessed sprinklers. (2) FM Approvals is limited to bronze and brass, chrome or black
Escutcheon Data plated finishes only.
FaoeofFlfti ( FP Push - on/Thread -off escutcheon.
Escutcheon ,vv, Fitting ( UL and ULC listed corrosion resistance.
IS Adjustment Dimension t SIN numbers: R3621, R3622, R3623, R3625.
- Wall Dimension
1/2 „ Note: For / orifice pendent FM approved white
F1 1 , 2 , 4 , 8 Max Recess (38.1mm) Yle -1 /t6 " polyester coated and UL approved white polyester
Min Recess X'r (5mm -24mm) corrosion resistant sprinklers refer to Bulletin 014.
(19.1mm)
1 /2' Ordering Information
Max Recess (38.1mm) X6 " " "
F2 1,2,3,4,5,7,8
Min Recess /16 " (5mm -17mm) Specify:
_(24mm) _, 1. Sprinkler Model
FP 1,2 Max Recessed X 1y2" (38.1mm) 2. Sprinkler Type
Push-on/ (11mm) 3. Orifice Size
Thread-off 1,2 Min Recessed 1,116" 1 "(25.4mm) 4. Deflector Type
(24mm)
No Dimensional Figure for FP 5. Temperature Rating
6. Sprinkler Finish
Maintenance
7. Escutcheon Type
The Models F1FR and F1FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system 8. Escutcheon Finish (where applicable)
maintained in accordance with NFPA 25. Do not clean Note: When Model F1FR Recessed sprinklers are
sprinklers with soap and water, ammonia or any other ordered, the sprinklers and escutcheons are packaged
cleaning fluids. Remove dust by using a soft brush or gen- separately.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
HeI The Reliable Automatic Sprinkler Co., Inc. R paper (800)431 - 1588 Sales Offices
(800)848 -6051 Sales Fax
Corporate Offices Revision lines indicate updated or new data
(914)829 -2042