Loading...
Specifications 6V1 / ©5Cr .5=-.)440-4 / ly e tqcci ' Fire & Building RECEIVED Products sE.P2 Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 CITY OF TIC/ RD BUILDING DIVISION Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage tained when exposed to corrosive at- General mospheres. Although corrosion resis- tant coated sprinklers have passed the Description standard corrosion tests of the appli- - i' z cable approval agencies, the testing is r The S TY -FRB, 2.8, 4.2, 5.6, and not representative of all possible cor- , . , 8.0 K- factor, Upright and Pendent rosive atmospheres. Consequently, it Sprinklers described in this data sheet is recommended that the end user be are quick response - standard cover- consulted with respect to the suitability age, decorative 3 mm glass bulb type of these coatings for any given corro- ; spray sprinklers designed for use in sive environment. The effects of ambi- x. ` --rx` light or ordinary hazard, commercial ent temperature, concentration of . — - - occupancies such as banks, hotels, chemicals, and gas /chemical velocity, `- .:,,...,, -:',. . shopping malls, etc. should be considered, as a minimum, The recessed version of the Series along with the corrosive nature of the TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be ��� plicable, is intended for use in areas exposed. with a finished ceiling. It uses either a An intermediate level versions of the = =" ""-‘,.,,- two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers , ", Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet f� � cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de- recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780 (19,1 mm) of total adjustment from the ` r- �. / flush pendent position, or a two -piece WARNINGS •,, rip': Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de- N, • inch NPT) Recessed Escutcheon with scribed herein must be installed and -.A' j 1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica- total adjustment from the flush pen- ble standards of the National Fire Pro - dent position. The adjustment pro- tection Association, in addition to the vided by the Recessed Escutcheon re- standards of any other authorities hay- Model/Sprinkler the accuracy to which the fixed ing jurisdiction. Failure to do so may pipe drops to the sprinklers must be impair the performance of these de- Identification cut. vices. Corrosion resistant coatings, where The owner is responsible for maintain- Numbers applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT manufacturer should be contacted TY2131 - Upright 4.2K, 1/2 "NPT with any questions. T 223 - Pe 1 • . • 2K 1 /2 ". • IMPORTANT Y 31 - pright 5.6K, 1 2 "NPT Always refer to Technical Data - • : • • . a • . 1 /2 "NP'r Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.0K, 3 4 "N - WARNING" that provides cautions TY4231 - Pendent 8.0K, 3/4 "NPT • with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 APRIL, 2006 TFP171 Page 2 of 10 TFP171 • ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING 1/2" * * NOMINAL RECESSED SSU* SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR ME_ •=( 5 rr 7/16 2-1/4" = ��1 (11,1 mm) I i 4 (57,2 mm) 5�� � NOMINAL ■2 `111 I MAKE -IN A �I' i 2 -3/16" 3 1-9/16" (39,7 mm) 111110 WRENCH (55,6 mm) tit' 1 FLATS P II , 1 - '` 7 SSP DEFLECTOR* - 2 -7/8" (73,0 mm) DIA. 1/2" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING ** NOMINAL RECESSED SSU* SURFACE 1/2" T MAKE -IN ESCUTCHEON 1 DEFLECTOR 6 . — cOrt _ �_ ■ , 5 3 f 7/16" 2- 3/16" m ��� ( 11,1 mm) I 4 (55,6 mm) I I I ��� r I NOMINAL I � MAKE - IN NMI I ' 0 2 1 -1/2" kill 2 -3/16" (38,1 mm) WRENCH (55,6 mm) -- FLATS "'���� f 7 1 SSP DEFLECTOR - -- 2 -7/8" (73,0 mm) DIA. 1/2" NPT ** 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT ( T Y 2 INCH NPT PENDENT (TY2231) SPRINKLERS 4.2 K • TFP171 Page 3 of 10 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING 1/2 ** NOMINAL RECESSED SSU* SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR A_ f ____ _____________=_____ _ ��1' =� 7116" 2-3/16" t �� (11,1 mm) 5 (55,6 mm) A I �MI�� NOMINAL I 4 7 11 MAKINE -IN 1 -1/2" I till I r 2 -3116' �P 2 (38,1 mm) WRENCH (55,6 mm) �.�- —:7-11L--- FLATS 's= 1 —JILT:— �¢S 3 1 SSP DEFLECTOR* 2 -7/8" (73,0 mm) DIA. -- "1 1/2" NPT ** f PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 3 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40 PLATE SEATING , ** NOMINAL RECESSED SSU* SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR 1 /2 (' 5 ' -� (12 12,7/ m"m) NOMINAL I 4 i r I MAKE -IN (2-1/4. ) 2 1 -9/16" I WRENCH � 57.2 mm � (39,7 mm) III F LATS 1 3 SSP DEFLECTOR* 2 -7/8" (73,0 mm) DIA. 3/4 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION '1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT • Page 4 of 10 . TFP171 SPRINKLER FINISH (See Note 7) Technical K TYPE TEMP. BULB NATURAL CHROME WHITE••• LIQUID BRASS PLATED POLYESTER Data 135"F/57°C Orange Approvals PENDENT UL and C -UL Listed. 155 °Fl68 °C Red (TY1231) 1, 2, 3, 5 FM, LPCB, and NYC Approved. and 175 °F /79 °C Yellow (Refer to Table A and B for complete UPRIGHT 200 °F /93 °C Green approval information including corro- 2.8 (TY1131) sion resistant status.) • 286 °F /141 °C Blue Maximum Working Pressure 1/2" NPT 135 °F /57 °C Orange Refer to Table C. RECESSED 155 °F /68 °C • Red Discharge Coefficient PENDENT K = 2.8 GPM /psi (40,3 LPM /bar (TY1231)* 175 °F /79 °C Yellow K = 4.2 GPM /psi / (60,5 LPM /bars / Figure 5 200"F/93°C Green 1, 2, 5 K = 5.6 GPM /psi / (80,6 LPM /bar / 135 °F /57 °C Orange K = 8.0 GPM /psis / (115,2 LPM /bar RECESSED 155 °F /68 °C Red _ Temperature Ratings PENDENT Refer to Table A and B (TY1231)" 175 °F /79 °C Yellow Finishes Figure 6 200 °F /93 °C Green Sprinkler: Refer to Table A and B. Recessed Escutcheon: White Coated, 135"F157°C Orange Chrome Plated, or Brass Plated. PENDENT 155"F/68°C Red (TY2231) and 175 °F /79 °C Yellow Physical Characteristics UPRIGHT Frame Bronze 200 °F /93 °C Green - Brass /Copper 4.2 (TY2131) Sealing Assembly 286 °F /141 °C Blue 1 2 g y 1/2" Beryllium Nickel w /Teflont NPT 135"F/57°C Orange Bulb Glass RECESSED 155 °F /68 °C Red Compression Screw Bronze PENDENT Deflector Copper /Bronze (TY2231)• 175 °F /79 °C Yellow Bushing (K =2.8) Bronze Figure 7 200 °F /93 °C Green 135 °F /57 °C Orange Operation RECESSED 155 °F /68 °C Red PENDENT The glass Bulb contains a fluid which (TY2231)•• 175 °F /79 °C Yellow expands when exposed to heat. When Figure 8 200"F/93°C Green the rated temperature is reached, the fluid expands sufficiently to shatter the ' glass Bulb, allowing the sprinkler to NOTES: activate and water to flow. 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Re- sponse Sprinklers. Design 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- /� klers. Criteria 5. Approved by the City of New York under MEA 354 -01 -E. 7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- The Series TY -FRB Pendent and Up- klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. right Sprinklers are intended for fire • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment protection systems designed in ac- Recessed Escutcheon, as applicable. cordance with the standard installation •• Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment rules recognized by the applicable Recessed Escutcheon, as applicable. ••• Frame and Deflector only. Listings and approvals apply to color (Special Order). Listing or Approval agency (e.g., UL • N /A: Not Available Listing is based on the requirements of Y TABLE A NFPA 13, and FM Approval is based on the requirements of FM's Loss Pre - LABORATORY LISTINGS AND APPROVALS vention Data Sheets ). Only the Style 2.8 AND 4.2 K - FACTOR SPRINKLERS 10, 20, 30, or 40 Recessed Escutch- 1- • d eon, as applicable, is to be used for recessed pendent installations. N im 12 • c 0 a 3 0 +- TFP171 Page S of 10 SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3231) 1, 2, 3, 4, 5, 6, 7 1,2,3,5 and 175 °F /79 °C Yellow UPRIGHT 200"F/93°C Green 5.6 (TY3131) 286 °F /141 °C Blue 1/2" NPT 135"F/57°C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 4, 5 N/A (TY3231)' 175 °F /79 °C Yellow Figure 9 200 °F /93 °C Green 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 - N/A (TY3231 )'° 175"F179°C Yellow Figure 10 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY4231) 1, 2, 5 and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 UPRIGHT 200"F193°C • Green 8.0 (TY4131) 286 °F /141 °C Blue 3/4" NPT 135 °F /57 °C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2. 4, 5 N/A (TY4231)' 175"F/79°C Red Figure 11 200 °F /93 °C Yellow 135"F/57°C Orange RECESSED 155"F168°C Red PENDENT 1, 2, 3, 4, 5 N/A (TY4231)" 175 °F /79 °C Yellow Figure 12 200 °F /93 °C Green NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31-53- 428 - 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. • Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. • "' Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS Page 6 of 10 TFP171 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED POLYESTER COATED - PENDENT (TY3231) - and 2 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A 1/2" RECESSED PENDENT NPT (TY323) • PENDENT (TY4231) and 4 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A 3/4" RECESSED PENDENT NPT (TY4231) PENDENT (TY3231) and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR) 5.6 UPRIGHT (TY3131) OR 1/2" 175 PSI (12,1 BAR) NPT RECESSED PENDENT (TY323) (SEE NOTE 1) N/A PENDENT (TY4231) and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR) 8 UPRIGHT (TY4131) 3/4" RECESSED PENDENT NPT (TY4231) N/A NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories. Inc. for use in Canada (C -UL); and , the Approval by the City of New York. TABLE C, MAXIMUM WORKING PRESSURE nections. Higher levels of torque may The Series TY -FRB Recessed Pen - Installation distort the sprinkler inlet and cause dent Sprinklers must be installed in leakage or impairment of the sprinkler. accordance with the following instruc- The Series TY -FRB Sprinklers must Do not attempt to make-up for insuffi tions. be installed in accordance with the fol- lowing instructions: cient adjustment in the escutcheon Step A. After installing the Style 10. plate by under- or over - tightening the 20, 30, or 40 Mounting Plate, as appli- NOTES sprinkler. Readjust the position of the cable, over the sprinkler threads and Do not install any bulb type sprinkler if sprinkler fitting to suit. with pipe thread sealant applied to the the bulb is cracked or there is a loss of The Series TY -FRB Pendent and Up- kler spr nkler fitting the sprin- liquid from the bulb. With the sprinkler right Sprinklers must be installed in held horizontally, a small air bubble accordance with the following instruc- Step B. Tighten the sprinkler into the should be present. The diameter of the tions. sprinkler fitting using only the W -Type air bubble is approximately 1/16 inch Step 1. Pendent sprinklers are to be 7 Recessed Sprinkler Wrench (Ref. ep (1,6 mm) for the 135 F /57 °C to 3/32 S ep in pos and Figure 14). With reference to Figure 1, ll 1. inch (2,4 mm) for the 286°F/141°C n the pendent t ab 2, 3, and 4, the W -Type 7 Recessed temperature ratings. upright sprinklers are to be install in Sprinkler Wrench is to be applied to the upright position. the sprinkler wrench flats. A leak tight 1/2 inch NPT sprinkler joint Step pipe thread sealant a t 2. With i thd lant should be obtained with a torque of 7 plied to the pipe threads hand tighten Step C. After the ceiling has been in- to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- t he sprinkler into the sprinkler fitting. stalled or the finish coat has been ap- mum of 21 ft. lbs. (28,5 Nm) of torque plied, slide on the Style 10, 20, 30, or may be used to install sprinklers with Step 3. Tighten the sprinkler into the 40 Closure over the Series TY - FRB 1/2 NPT connections. A leak tight 3/4 sprinkler fitting using only the W -Type Sprinkler and push the Closure over inch NPT sprinkler joint should be ob- 6 Sprinkler Wrench (Ref. Figure 13). the Mounting Plate until its flange tained with a torque of 10 to 20 ft.lbs. With reference to Figures 1, 2, 3, and comes in contact with the ceiling. (13,4 to 26,8 Nm). A maximum of 30 4, the W -Type 6 Sprinkler Wrench is to ft.lbs. (40,7Nm) of torque is to be used be applied to the sprinkler wrench to install sprinklers with 3/4 NPT con- flats. TFP171 Page 7 of 10 • 2 -7/8" DIA. 2 -7/8' DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8' (73,0 mm) 1/2" (12,7 mm) (15,9±6,4 mm) 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4' DIA. 2 -1/4' DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8' I 1/8' WC (3,2 mm) ■ -11 a ( 3,2 mm) ■ —� 1 i 1 !I f \ f N , . f SURFACE � MOUNTING SURFACE ,_,_ CLOSURE SERIES 1 -5116° (33,3 mm) CLOSURE SERIES 1 -5/16" (33,3 mm) TY-FRB 13/16" (20,6 mm) TY-FRB 1 -1/16" (27,0 mm) FIGURE 5 FIGURE 6 SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. 2 -7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8' (73,0 mm) 1/2" (12,7 mm) (15,9±6,4 mm) 1/4" (6,4 mm) (12,7±3,2 mm) 2.1/4' DIA. 2 -1/4' DIA. 1 1/4 "(6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" M co' i v •�' (3,2 mm) �� (3,2 mm) A IC /. _ ,_ 6' I I \ Y— f MOUNTING II, �' I ' te MOUNTING . SURFACE � . SURFACE . -. CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm) FIGURE 7 FIGURE 8 SERIES TY -FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT objects; otherwise, non - operation in by brushing it with a soft bristle brush. are and the event of a fire or inadvertent opera- Care must be exercised to avoid dam - IVlaintenance tion may result age to the sprinklers - before, during, Absence of an escutcheon, which is and after installation. Sprinklers dam - The Series TY -FRB Sprinklers must used to cover a clearance hole, may aged by dropping, striking, wrench be maintained and serviced in accord- delay the time to sprinkler operation in twist/slippage, or the like, must be re- • ance with the following instructions: a fire situation. placed. Also, replace any sprinkler Sprinklers that are found to be leaking that has a cracked bulb or that has lost • NOTES or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation Before closing a fire protection system must be replaced. Section). main control valve for maintenance Frequent visual inspections are rec- work on the fire protection system that Automatic sprinklers must nev be ommended to be initially performed for it controls, permission to shut down the Painted, plated, coat or otherwise corrosion resistant coated sprinklers, affected fire protection system must be altered after leaving the factory. Modi- after the installation has been corn- obtained from the proper authorities fied sprinklers must be replaced. pleted, to verify the integrity of the cor- and all personnel who may be affected Sprinklers that have been ex to rosion resistant coating. Thereafter, c orrosive products of combustion, but by this action must be notified. annual inspections per NFPA 25 have not operated, should be replaced should suffice; however, instead of in- The owner must assure that the sprin- if they cannot be completely cleaned specting from the floor level, a random klers are not used for hanging of any by wiping the sprinkler with a cloth or Page 8 of 10 TFP171 2 -7/8' DIA. 2 -7/8" DIA. • 5/8±1/4' (73,0 mm) 3/4' (19,1 mm) 1/2±1/8' (73,0 mm) 1/2" (12,7 mm) (15,9±6.4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7 ±3,2 mm) 2 -1/4' DIA. 1/4' (6,4 mm) FACE OF (57,2 mm) • FACE OF (57,2 mm) MOUNTING MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1 /8' I 1/8" (3,2 mm) ° (3,2 mm) 60, 1U iii -,VIII;' r 1 M 11•11 ' r i G ;lgll, ■3 0 111 lew } ' MOUNTING } MOUNTING SURFACE SURFACE == .I._ _. CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm) TY-FRB - (19,1 mm) TYFRB 1" (25,4 mm) FIGURE 9 FIGURE 10 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT • STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8' DIA. 2.7/8' DIA. 5/8±1/4' (73,0 mm) 3/4" (19,1 mm) 112±1/8' (73.0 mm) 1/2" (12,7 mm) (15,9±6,4 mm) 1/4" (6,4 mm) (12,713,2 mm) 2 -1/4' DIA. 1/4' (6,4 mm) ( ) 2 -1/4' DIA. ) (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING FACE OF SPRINKLER PLATE SPRINKLER PLATE FITTING B" FITTING 118' " (3,2 mm) " I (3,2 mm) r r NO ii r E O i A. i �, } MOUNTING IIP } MOUNTING SURFACE SURFACE • CLOSURE SERIES 1 -5/16' (33.3 mm) CLOSURE SERIES 1 -5/16' (33,3 mm) TY -FRB 13/16' (20,6 mm) TY -FRB 1 -1/16" (27,0 mm) FIGURE 11 FIGURE 12 SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT sampling of close -up visual inspec- L� RECESS tions should be made, so as to better determine the exact sprinkler condi- tion and the long term integrity of the WRENCH RECESS ��'r. corrosion resistant coating, as it may (END °A° USED FOR • ' be affected by the corrosive conditions ^ 1/2" NPT MODELS) present. The owner is responsible for the in- `, spection, testing, and maintenance of WRENCH RECESS their fire protection system and de- (END °B° USED FOR PUSH WRENCH • vices in compliance with this docu- 3/4° NPT MODELS) IN G TO A GEMUNT p ) ENGGEMENT ment, as well as with the applicable F IGURE 13 WITH SPRINKLER standards of the National Fire Protec- WRENCHING AREA tion Association (e.g., NFPA 25), in W - TYPE 6 SPRINKLER addition to the standards of any other WRENCH FIGURE 14 authorities having jurisdiction. The in- W - TYPE 7 RECESSED stalling contractor or sprinkler manu- SPRINKLER WRENCH facturer should be contacted relative tested, and maintained by a qualified to any questions. Inspection Service in accordance with It is recommended that automatic local requirements and /or national sprinkler systems be inspected, codes. • TFP171 Page 9 of 10 - P/N 57 - XXX - X - XXX I I TEMPERATURE MODEL /SIN RATING SPRINKLER 330 2.8K UPRIGHT (1/2 °NPT) TY1131 135 135 °F /57 °C 331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C 340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C 341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)• 200 200 °F /93 °C 370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C 371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED 390 8.0K UPRIGHT (3/4 "NPT) TY4131 391 8.0K PENDENT (3/4 "NPT) TY4231 • Eastern Hemisphere sales only. TABLE D PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS . charges, regardless of whether TFBP Limited was informed about the possibility of Ordering . such damages, and in no event shall Procedure Warranty TFBP's liability exceed an amount equal to the sales price. Products manufactured by Tyco Fire & When placing an order, indicate the Building Products (TFBP) are war- The foregoing_warranty is made in lieu full product name. Refer to the Price ranted solely to the original Buyer for of any and all other warranties. ex- List for complete listing of Part Num- ten (10) years against defects in mate- press or imolied including warranties bers. rial and workmanship when paid for of merchantability and fitness fora oar - and properly installed and maintained ticular purpose, Contact your local distributor for avail - • under normal use and service. This ability. This limited warranty sets forth the ex- warranty will expire ten (10) years clusive remedy for claims based on Sprinkler Assemblies with NPT from date of shipment by TFBP. No failure of or defect in products, materi- Thread Connections: warranty is given for products or corn- als or components, whether the claim Specify: (Specify Model /SIN), Quick ponents manufactured by companies is made in contract, tort, strict liability Response, (specify K- factor), (specify not affiliated by ownership with TFBP or any other legal theory. temperature rating), Series TY -FRB or for products and components which Upright) Sprinkler have been subject to misuse, improper This warranty will apply to the full ex- (s P eci fY Pendent or P 9 ht ) S n P installation, corrosion, or which have tent permitted by law. The invalidity, in with (specify type of finish or coating), not been installed, maintained, modi- whole or part, of any portion of this P/N (specify from Table D). fled or repaired in accordance with ap- warranty will not affect the remainder. Recessed Escutcheon: plicable Standards of the National Fire Specify: Style (10, 20, 30, or 40) Re- Protection Association, and /or the cessed Escutcheon with (specify') fin - standards of any other Authorities ish, P/N (specify'). Having Jurisdiction. Materials found by TFBP to be defective shall be either • Refer to Technical Data Sheet TFP770. repaired or replaced, at TFBP's sole option. TFBP neither assumes, nor Sprinkler Wrench: authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench, any other obligation in connection with P/N 56- 000 -6 -387. the sale of products or parts of prod- ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench, sprinkler system design errors or inac- P/N 56 -850 -4 -001. curate or incomplete information sup- plied by Buyer or Buyer's repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential darn - ages; including but not limited to labor 1 Page 10 of 10 TFP171 • • TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446