Correspondence •
/Ak
May 18, 2005
CITY OF TIGARD
OREGON
CIDA INC "tcril
Jennifer Beattie
4445 SW Barbur Blvd, Suite 200
Portland, OR 97239
RE: CROWN CARPET PHASE II REVIEW
Project Information
Building Permit: BUP2005 -00192 Occupancy Type: M
Tenant Name: Crown Carpet Construction Type: III -B
Address: 12230 SW Main St. Occupant Load: 38
Area: 2,285 Sq Ft Stones: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R. The submitted plans are
approved subject to the following conditions.
1. All exit doors shall be openable from the inside without the use of a key or any special
knowledge or effort. 1008.1.8 OSSC
2. Exit signs shall be illuminated at all times and shall be provided with a second source of
power that will provide 1 '/z hours of illumination in case of primary power loss. 1006.3
OSSC FYI Additional exit signs may be required by the city field inspector to clearly
indicate the path of egress.
3. The means of egress shall be provided with illumination of not less than 1 foot candle at the
floor level anytime the building is occupied. The means of egress illumination shall be
provided with a second source of power in case of primary power loss. 1006.2 OSSC
4. Safety glazing including but not limited to: the following locations: Each unit of glazing
shall be permanently identified by the manufacturer. 2406 OSSC. Some of these locations
are as follows:
a. Glazing in ingress and means of egress doors.
b. Glazing in an individual fixed or operable panel adjacent to a door where the nearest
vertical edge is within a 24" arc of the door in a closed position and whose bottom
edge is less than 60" above the floor or walking surface except when there is an
intervening wall or other permanent barrier between the door and the glazing.
c. Glazing that meets all the following conditions: In lieu of safety glazing, protective
bar (1 ' /s" height minimum) may be installed on the accessible side(s) of the glazing
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
36" ± 2" above the floor. The bar shall be capable of withstanding a horizontal load of
50 plf without contacting the glass. Sec. 308.4
5. Special Inspection: Special inspection is required for items listed on sheet S0.1. The
special inspection agency of record shall furnish inspection reports to the Engineer of
Record, David A Stivers, the General Contractor, Yorke & Curtis, Inc. and the City of
Tigard, Building Division, attention Hap Watkins. All discrepancies shall be brought to the
immediate attention of the general contractor for correction. The special inspector shall
submit a final signed report stating whether the work requiring special inspection was, to the
best of the inspector's knowledge, in conformance with the approved plans and
specifications and the applicable workmanship provisions of the code. 1704 OSSC
6. American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the
structure only for compliance with Chapter 11 of the OSSC, which may not include all of the
requirements of the ADA.
7. Live Loads Posted: The live loads for which each floor has been designed to exceed 50 psf
shall be conspicuously posted by the owner in that part of each story in which they apply,
using durable metal signs, and it shall be unlawful to remove or deface such notices. The
occupant of the building shall be responsible for keeping the actual load below the allowable
limits. 1603.3 OSSC
Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will be
charged a deferred submittal fee based on the valuation of the portion of the work being deferred.
The minimum fee shall be $200.00. Deferred items;
• None Listed
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.3.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings
in such a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Respect 1 ,
lH 3
al He el,
Senior Plans Examiner