Correspondence June 7, 2005
/ 741fil tl
Konell Construction CITY OF TIGARD
rr. Kent Jackson
36000 SE Industrial Way OREGON
Sandy, OR 97055
RE: CROWN CARPET — VAULT & FIRE LINES
Project Information
SIT
Building Permit: X2005 -00011 Occupancy Type: M,B,S -1
Tenant Name: Crown Carpet Construction Type: III -B
Address: 12230 SW Main St. Occupant Load: 307
Area: 23,750 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2004 edition; and the Tualatin Valley Fire & Rescue Fire & Life Safety
Requirements for Fire Department Access and Water Supplies (Based on the 2003
International Fire Code as amended by TVF &R). The submitted plans are approved
subject to the following.
EROSION
1. Erosion control measures shall be in place prior to excavation or grading.
FIRE
1. The private fire service main shall be at least 30 inches below grade.
2. The private fire service main shall be flushed thoroughly before connection to the
system riser in order to remove foreign materials that might have entered the main
during the course the installation. The flow rate shall not be less than the water
demand rate of the system.
3. All piping shall be inspected prior to backfill.
ACCESSIBILITY
4. Accessible walkways and routes shall not exceed a running slope of 1 unit vertical
in 20 units horizontal (5% slope). Cross slopes shall not exceed 1 unit vertical in
50 units horizontal (2% slope).
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
5. Accessible parking spaces and access aisles shall be located on a surface with a
slope not to exceed 1 unit vertical in 50 units horizontal in all directions. 1104.4.3
$, OSSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
inspectors throughout all phases of construction. 106.4.2 OSSC
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the
ADA requirements for the structure. The City of Tigard reviews the plans and inspects
the structure only for compliance with Chapter 11 of the OSSC which may not include all
of the requirements of the ADA.
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Resp full ,
al Henzel,
Senior Plans Examiner
r
rt.
FROM : YCA?KE&CUR71 FAX: NO. :5037779046 Jun. 0E• 200E 04: 07PM P1
6 1 T2.01:9 5- az» I (
¥ORKE&
CURTIS
Fax Cover Sheet
DATE: June 6, 2005 TIME 3:59 PM
TO: Konell
PAX: 503-668-
3518
ATTN: Bruce
FROM: Kent
RE: Crown Carpet / Vault
Number of pages including 2
cover sheet:
Bruce: During the process of meeting with the senior building
official today, I discovered that I still need to pull a site permit.
In order to do this I need you to answer 2 questions for the city.
Please see attached letter from Tigard. I saw the information that
she had but it didn't show which lid was used in order to
determine the weight that it would support. Can you please take
care of this as soon as possible? Once she has the info I still need
to pull the permit and call for an inspection. At best that is 3 days.
Thanks for your cooperation.
Sincerely, Kent
4480 S.W. 101 Ave., Beaverton, Oregon 97005 (503) 646 - 2123 Fax: (503)
643 -5531
E[N#: 93- 0966272 (an Oregon Corporation) OR CCB # 0055644 WA* 601 -076 -450
•
May 20. 2005
Konen Construction ( ri OF BFI GA {j
Kent Jackson /1't+ i� �`
36000 SE Industrial Way ORFOON
Sandy, OR 97055
ltl : CROWN CARPET -- VAULT & FIRE J.INES
Project Ltfolmati.)u
0
Building Permit: )3UP200S -00011 Occupancy Type: M,13,S••1
Tenant Name: Crown Carpet Construction Type: III -13
Address: 12230 SW Main St. Occ%lprnt Load: 307
Area: 23,750 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2004 edition; and the Tualatin Valley Fire & Rescue Fire & Life Safety
Requirements for Fire Department Access and Water Supplies (Based on the 2003
International Tire Code as amended by TVF &R). The submitted plans are approved
subject to the following.
1. Provide information on vault location at accessible parking area access aisle
showing lid will meet surface stability as required per chapter 11 of OSSC.
Or
2. Provide new location for accessible parking and route and show lid will meet
weight limit for vehicle weight or provide balusters for protection of location.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respect ly,
Val u 1,
Senior Plans Examiner
•
1312.5 SW Holt Blvd . Tigard. OR 97223 (503) 639 -4171 TDD (503) 684 - 2772 _
May 20, 2005 �.... /i� -- �+�i lWl��� i\
•
Konell Construction CITY OF TIGARD
Kent Jackson
36000 SE Industrial Way OREGON
Sandy, OR 97055
RE: CROWN CARPET — VAULT & FIRE LINES
Project Information
5 1T
Building Permit: AM :4)2005-00011 Occupancy Type: M,B,S -1
Tenant Name: Crown Carpet Construction Type: III -
Address: 12230 SW Main St. Occupant Load: 307
Area: 23,750 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2004 edition; and the Tualatin Valley Fire & Rescue Fire & Life Safety
Requirements for Fire Department Access and Water Supplies (Based on the 2003
International Fire Code as amended by TVF &R). The submitted plans are approved
subject to the following.
1. Provide information on vault location at accessible parking area access aisle
showing lid will meet surface stability as required per chapter 11 of OSSC.
Or
2. Provide new location for accessible parking and route and show lid will meet
weight limit for vehicle weight or provide balusters for protection of location.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respect ly,
Val He el, ' it"
Senior Plans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
{
May 11, 2005
CITY OF TIGARD
OREGON
Doug Lepper
Integrity Investments
6324 NE Halsey
Portland, OR 97213
RE: CROWN CARPET PROJECT
Dear Doug,
It has been brought to my attention that the installation of the underground fire
line vault is required to have a Public Facility Improvement (PFI) Permit. I have
enclosed a copy of the PFI application for your use. If you have questions regarding
the PFI permit please contact Mike White @ 503- 718 -2464.
When the PFI permit is approved, I will release the Site Permit applied for on 5 -6 -05,
pending any revisions required through the PFI permit process.
Respectfully,
rian B : • ck,
Senior ' lans Examiner