Correspondence •
P II O J E N T RECEIVED
win DEC 20 2011 " ED
oiaeoioo aoo aesioo ( _ dl
CITY OF TIGARD
763 Susquehanna Avenue BUILDING DIVISION CIT OF
Franklin Lakes, NJ 07417 ? IGARD
Tele: 201.848.9060
BUIL DING D
Fax: 201.848.9881
www.wjcainc.com
12/15/11
Attn: Dan Nelson
Senior Plans Examiner
dann(c�tigard- or.qov
RE: TENANT IMPROVEMENT
Project Information
Building Permit: BUP2011 -00247 Construction Type: 2 -B
Address: 9459 SW Washington Sq. Occupancy Type: M
Area: 5405 Sq. Ft. Stories: 1
Name: Footlocker Sprinklers: Yes
Mr. Nelson,
Below is an itemized letter stating the conditions noted in your letter, dated 12/2/2011,
regarding the tenant improvement project at Footlocker located at 9459 SW Washington
Square. Please see responses to each condition below, and refer to attached calculations and
construction drawings.
1) Construction requirements for suspended ceiling systems are found in the Oregon
Building Codes Division website under Statewide Code Interpretations date 4/20/2007.
(See interpretations {structural} at www.bcd.oregon.gov)
See sheet S1.1 detail G. As prepared by Joseph Lewis, P.E.
2) Provide calculations and construction details (including seismic bracing details for non -
full- height partitions) for all walls. Note: The roof structure may be approximately 30' -0"
above the finished floor. OSSC 106.1
Refer to structural calculations dated 12/12/11. As prepared by Joseph
Lewis, P.E.
3) Please provide calculations and construction details for the soffits and storefront
construction. Every structure, and portion thereof, including non - structural components
that are permanently attached to structure and their supports and attachments, shall be
designed and constructed to resist the effects of earthquake motions in accordance with
ASCE 7 as modified by Section 1613.7. The seismic design category for a structure is
permitted to be determined in accordance with Section 1613 or ASCE 7. OSSC 1613.1.
Refer to structural calculations dated 12/12/11, and revised details B/S1.1
and E /S1.2. As prepared by Joseph Lewis, P.E.
•
4) Please submit plans and calculations for steel storage racks that comply with the design
requirements of ASCE 7 (15.5.3).
Refer to shelving calculations dated 12/12/11, and sheet S1.0. As prepared
by Joseph Lewis, P.E.
5) Please provide a permit valuation based on the total work being performed. Permit
valuations shall include total value of work, including materials and labor, for which the
permit is being issued, such as electrical, gas, mechanical, plumbing equipment,
flooring, ceilings and any fixture attached to the building. If, in the opinion of the building
official, the valuation is underestimated on the application, the permit shall be denied,
unless the applicant can show detailed estimates to meet the approval of the building
official. Final building permit valuation shall be set by the building official.
Final permit valuation will be submitted upon selection of the General
Contractor.
•
Sincerely,
Lino Picinic
Project Manager
(201) 848 -9060 ex. 21
Ipicinic @wjcainc.com
•
January 11, 2012
RE: TENANT IMPROVEMENT
Project Information
Building Permit: BUP2011 -00247 Construction Type: 2 -B
Address: 9459 SW Washington Sq. Occupancy Type: M
Area: 5405 Sq. Ft. Stories: 1
Name: Footlocker Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2010 edition; 2010 Oregon Fire Code. Please respond to conditions below.
1) Please provide a permit valuation based on the total work being performed.
Permit valuations shall include total value of work, including materials and
labor, for which the permit is being issued, such as electrical, gas,
mechanical, plumbing equipment, flooring, ceilings and any fixture attached to
the building. If, in the opinion of the building official, the valuation is
underestimated on the application, the permit shall be denied, unless the
applicant can show detailed estimates to meet the approval of the building
official. Final building permit valuation shall be set by the building official. This
will be required prior to the plans being approved.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson
Senior Plans Examiner
(503) 718 -2436
Bann @tigard- or.gov
°a
December 2, 2011
TIGARD
RE: TENANT IMPROVEMENT City of Tigard
Project Information
Building Permit: BUP2011 -00247 Construction. Type: 2 -B
Address: 9459 SW Washington Sq. Occupancy Type: M
Area: 5405 Sq. Ft. Stories: 1 •
Name: Footlocker Sprinklers: Yes
•
The plan review was performed under the State of Oregon Structural Specialty Code •
(OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below.
1) Construction requirements for suspended ceiling systems are found in the
Oregon Building Codes Division website under Statewide Code
•
Interpretations dated 4/20/2007. (see interpretations {structural} at •
www.bcd.oregon.gov)
2) Provide calculations and construction details (including seismic bracing
details for non full height partitions) for all walls. Note: The roof structure
may be approximately 30' above the finished floor. OSSC 106.1.
3) Please provide calculations and construction details for the soffits and
storefront construction. Every structure, and portion thereof, including non
structural components that are permanently attached to structures and their
supports and attachments, shall be designed and constructed to resist the
effects of earthquake motions in accordance with ASCE 7 as modified by
Section 1613.7. The seismic design category for a structure is permitted to be
determined in accordance with Section 1613 or ASCE 7. OSSC 1613.1
4) Please submit plans and calculations for steel storage racks that comply
with the design requirements of ASCE7 (15.5.3).
5) Please provide a permit valuation based on the total work being performed.
Permit valuations shall include total value of work, including materials and
labor, for which the permit is being issued, such as electrical, gas,
mechanical, plumbing equipment, flooring, ceilings . and any fixture attached to
the building. If, in the opinion of the building official, the valuation is
underestimated on the application, the permit shall be denied, unless the
applicant can show detailed estimates to meet the approval of the building
official. Final building permit valuation shall be set by the building official.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.639.4171
TTY Relay: 503.684.2772 • www.tigard- or.gov
Respectfully,
40' A T. Y■)E7-- - rie 32 d
Dan Nelson
Senior Plans Examiner
(503) 718 -2436
dann @tigard - or.gov
December 29, 2011
RE: TENANT IMPROVEMENT
Project Information
Building Permit: BUP2011 -00247 Construction Type: 2 -B
Address: 9459 SW Washington Sq. Occupancy Type: M
Area: 5405 Sq. Ft. Stories: 1
Name: Footlocker Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below.
1) Provide calculations and construction details (including seismic bracing
details for non full height partitions) for all walls. Note: The roof structure
may be approximately 30' above the finished floor. OSSC 106.1 On the
revisions you're your engineer has prepared it does not include the length of
the 45deg kickers used to support none full height walls which could be as
long as 30ft. and bracing for them.
2) Please provide a permit valuation based on the total work being performed.
Permit valuations shall include total value of work, including materials and
labor, for which the permit is being issued, such as electrical, gas,
mechanical, plumbing equipment, flooring, ceilings and any fixture attached to
the building. If, in the opinion of the building official, the valuation is
underestimated on the application, the permit shall be denied, unless the
applicant can show detailed estimates to meet the approval of the building
official. Final building permit valuation shall be set by the building official. This
will be required prior to the plans being approved.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson
Senior Plans Examiner
(503) 718 -2436
dann @tigard- or.gov