Correspondence June 23, 2005 Jerry Griffith NorthWest Handling Systems, Inc. 18008 NE Airport Way Portland, OR 97230 RE: RACK STORAGE @ CROWN CARPETS Project Information Building Permit: BUP2005 -00238 Construction Type: III -N Tenant Name: Crown Carpets Occupancy Type: M Address: 12230 SW Main Street Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The submitted plans are approved subject to the following conditions. Loads Posted: The racks shall display in one or more conspicuous locations a permanent plaque not less than 50 square inches in area, showing the maximum permissible unit load in clear legible print. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and process' g the documents. Respectfully . B • aloc mor Pl. xaminer • FILE COPY June 23, 2005 Jerry Griffith NorthWest Handling Systems, Inc. 18008 NE Airport Way Portland, OR 97230 RE: RACK STORAGE @ CROWN CARPETS Project Information Building Permit: BUP2005 -00238 Construction Type: III -N Tenant Name: Crown Carpets Occupancy Type: M Address: 12230 SW Main Street Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The submitted plans are approved subject to the following conditions. Loads Posted: The racks shall display in one or more conspicuous locations a permanent plaque not less than 50 square inches in area, showing the maximum permissible unit load in clear legible print. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Brian Blalock, Senior Plans Examiner June 1Sk 2005 Jerry Griffith NorthWest Handling Systems, Inc. 18008 NE Airport Way Portland, OR 97230 RE: RACK STORAGE @ CROWN CARPETS -2 " Review Building Permit: BUP2005 -00238 Construction Type: III -N Address: 12230 SW Main Street Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The following items remain and are required prior to the issuance of the Rack Storage Permit. GENERAL • Clarify the classification of the commodities being stored in accordance with section 2303 OFC. • Type of fire suppression system. (See comment regarding Sprinkler System Analysis) • Location of valves controlling the water supply of ceiling and in -rack sprinklers. • Dimension and location of transverse and longitudinal flue spaces in accordance with Table 2308.3 OFC SPRINKLER SYSTEM ANALYSIS • A sprinkler system analysis shall be submitted to the City of Tigard, Building Division prior to approval of the Rack Storage Permit. The analysis shall provide hydraulic calculations verifying that the existing sprinkler system has the required flow for the commodity being stored. FYI In rack sprinklers are required for the project and were not indicated on the previous Fire Sprinkler Permit. Revisions to the existing sprinkler permit will be required or a new sprinkler permit will be required. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Brian Blalock, Plans Examination Supervisor • FILE COPT CHAPTER 23 HIGH -PILED COMBUSTIBLE STORAGE SECTION 2301 !LEQO /RC913.. Dimension and location of transverse and longitudinal GENERAL flue spaces. 2301.1 Scope. High -piled combustible storage shall be in ac- 14. Additional information regarding required design fea- cordance with this chapter. In addition to the requirements of tures, commodities, storage arrangement and fire pro - this chapter, the following material - specific requirements shall tection features within the high -piled storage area shall apply: be provided at the time of permit, when required by the 1. Aerosols shall be in accordance with Chapter 28. fire code official. 2. flammable and combustible liquids shall be in accor- 2301.4 Evacuation plan. When required by the fire code offs dance with Chapter 34. cial, an evacuation plan for public accessible areas and a sepa- rate set of plans indicating location and width of aisles, location 3. Hazardous materials shall be in accordance with Chapter of exits, exit access doors, exit signs, height of storage, and lo- 27. cations of hazardous materials shall be submitted at the time of 4. Storage of combustible paper records shall be in accor- permit application for review and approval. Following ap- dance with NFPA 231C. proval of the plans, a copy of the approved plans shall be main - 5. Storage of combustible fibers shall be in accordance with tained on the premises in an approved location. Chapter 29. 6. Storage of miscellaneous combustible material shall be SECTION 2302 in accordance with Chapter 3. DEFINITIONS 2301.2 Permits. A permit shall be required as set forth in Sec- 2302.1 Definitions. The following words and terms shall, for tion 105.6. the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. 2301.3 Construction documents. At the time of building per- ARRAY. The configuration of storage. Characteristics consid- mit application for new structures designed to accommodate high -piled storage or for requesting a change of occupancy /use, ered in defining an array include the type of packaging, flue and at the time of application for a storage permit, plans and spaces, height of storage and compactness of storage. specifications shall be submitted for review and approval. In ARRAY, CLOSED. A storage configuration having a 6 -inch addition to the information required by the International Build- (152 mm) or smaller width vertical flue space that restricts air ing Code, the storage permit submittal shall include the infor- movement through the stored commodity. mation specified in this section. Following approval of the BIN BOX. A five -sided container with the open side facing an plans, a copy of the approved plans shall be maintained on the aisle. Bin boxes are self- supporting or supported by a structure premises in an approved location. The plans shall include the designed so that little or no horizontal or vertical space exists following: around the boxes. PROVIDED 1. Floor plan of the building showing locations and di- COMMODITY. A combination of products, packing materi- mensions of high -piled storage areas. als and containers. i zcQO/Rt=D 2. Usable storage height for each storage area. DRAFT CURTAIN. A structure arranged to limit the spread ! PROVIDED , 3. Number of tiers within each rack, if applicable. of smoke and heat along the underside of the ceiling or roof. R EGUMZED 4. Commodity clearance between top of storage and the EARLY SUPPRESSION FAST - RESPONSE (ESFR) • sprinkler deflector for each storage arrangement. SPRINKLER. A sprinkler listed for early suppression fast -re- R EQU/R( 5. Aisle dimensions between each storage array. sponse performance. NA 6. Maximum pile volume for each storage array. EXPANDED PLASTIC. A foam or cellular plastic material f EOU /LP 7. Location and classification of commodities in accor- having a reduced density based on the presence of numerous dance with Section 2303. small cavities or cells dispersed throughout the materiaL REQUIREf7 8. Location of commodities which are banded or encapsu- EXTRA - HIGH -RACK COMBUSTIBLE STORAGE. lated. Storage on racks of Class I, II, III or IV commodities which ex- PRoV1DE9 9. Location of required fire department access doors. ceed 40 feet (12 192 mm) in height and storage on racks of high -hazard commodities which exceed 30 feet (9144 mm) in lZE4Ull9 10. Type of fire suppression and fire detection systems. height. RGavi4G'9 , 11. Location of valves controlling the water supply of ceil- HIGH -PILED COMBUSTIBLE STORAGE. Storage of ing and in -rack sprinklers. combustible materials in closely packed piles or combustible 12. Type, location and specifications of smoke removal and materials on pallets, in racks or on shelves where the top of curtain board systems. storage is greater than 12 feet (3658 mm) in height. When re- 2003 INTERNATIONAL FIRE CODE® 201 • TRANSMISSION VERIFICATION REPORT TIME : 06/10/2005 10:04 FILE CO?Y TEL NAME : 50362436: 81LDING DEPT FAX SER.# : BROD4J479592 DATE,TIME 06/10 10:03 FAX NO. /NAME 5032261670 DURATION 00:00:34 PAGE(S) 02 RESULT OK MODE STANDARD ECM /r 14 . 4 . - • ' j I ritO June 10, 2005 ., �Ir`1. . .. ... CITY OF rrGaRa :. . OREGON Jerry Griffith NorthWest Handling Systems, Inc. 18008 NE Airport Way Portland, OR 97230 RE: RACK STORAGE @ CROWN CARPETS Building Permit: BUP2005-00238 Construction Type: III -N Address: 12230 SW Main Street Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The following information is required prior to the approval of the submitted plans. GENERAL I have enclosed a copy of Section 2301.3 of the Oregon Fire Code. • Please submit all the information indicated as "Required ". • I have indicated the items that have been provided with the word "Provided ". • I have indicated items that are not required with "NA ". SPRINKLER SYSTEM ANALYSIS • A sprinkler system analysis shall be submitted to the City of Tigard, Building Division prior to approval of the Rack Storage Permit. The analysis shall provide 1... i�...1:.. ,.,.1....1.. +:..... ....�: j'..:�.. + L... + + 1.......:..a:.... ...x..5.1 .. .... .+...tiy 1 . a," wnr,irna TRANSMISSION VERIFICATION REPORT TIME : 06/10/2005 10:12 NAME : TIGARD BUILDING DEPT 4 FAX 5036243681 FILE COPY SER. # : BROD4J479592 DATE,TIME 06/10 10:11 FAX NO. /NAME 5034650677 DURATION 00:01:25 PAGE(S) 03 RESULT OK MODE STANDARD fr a I 2�h June 10 2005 p ' - `..: .,: �,, Y . , = OF TIGARD -Y==. CITY O r'. OREGON Jerry Griffith . >• .... . NorthWest Handling Systems, Inc. 18008 NE Airport Way Portland, OR 97230 RE: RACK STORAGE @ CROWN CARPETS Building Permit: BUP2005 -00238 Construction Type: III -N Address: 12230 SW Main Street Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The following information is required prior to the approval of the submitted plans. . GENERAL I have enclosed a copy of Section 2301.3 of the Oregon Fire Code. • Please submit all the information indicated as "Required ". • I have indicated the items that have been provided with the word "Provided ". • I have indicated items that are not required with "NA ". SPRINKLER SYSTEM ANALYSIS • A sprinkler system analysis shall be submitted to the City of Tigard, Building Division prior to approval of the Rack Storage Permit. The analysis shall provide hydraulic calculations verifying that the existing sprinkler system has the required 06/10/2005 10:11 5036243681 TIGARD BUILDING DEPT PAGE 01/03 Tune 10, 2005 • • 'A& Y CITY OF TIGARD REGEid&P Jerry Griffith NorthWest Handling Systems, Inc. ..l_ 4 t` 4 2005 18008 NE Airport Way CITY .F ' Portland, OR 97230 BUILDING DIVISION RE: RACK STORAGE @ CROWN CARPETS Building Permit: BUP2005 -00238 Construction Type: Ill -N Address: 12230 SW Main Street Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The following information is required prior to the approval of the submitted plans. GENERAL I have enclosed a copy of Section 2301.3 of the Oregon Fire Code. • Please submit all the information indicated as "Required ". • I have indicated the items that have been provided with the word "Provided ". • I have indicated items that are not required with "NA ". SPRINKLER SYSTEM ANALYSIS • A sprinkler system analysis shall be submitted to the City of Tigard, Building Division prior to approval of the Rack Storage Permit. The analysis shall provide hydraulic calculations verifying that the existing sprinkler system has the required flow for the commodity being stored. FYI In rack sprinklers are required for the project and were not indicated on the previous Fire Sprinkler Permit. Revisions to the existing sprinkler permit will be required or a new sprinkler permit will be required. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respec , • rian..B ock, Plans xainination Supervisor 13125 SW Hall Blvd,. Tigard, OR 97223 (503) 639 -4171 TDD (503) 684-2772 06/10/2005 10: 5036243681 TIGARD BUILDING DEPT PAGE 02/03 a CHAPTER 23 HIGH -PILED COMBUSTIBLE STORAGE SECTION 2301 REQUIRIP13, Dimension and location of transverse and longitudinal GENERAL flue spaces. . 2301.1 Scope. High -piled combustible storage shall be in ac- 14, Additi Witmation re rding tea 'r d kit t fea- cordance with this chapter. In addition to the requirements of rees, m o0 lities fi fe pro- this chapter, g P q the followin material -s ecific re uirements shall t' j tt'Ctio llres i t et e a rea shall S e codSded ' + rmtt quired by the 1 apply: ire official I. Aerosols shall be in accordance with Chapter 213. 2. Flammable and combustible liquids shall be in accor- 2301.4 Evacuation plan. When required by the fire code offi- dance with Chapter 34, vial. an evacuation plan for public accessible areas and a sepa- rate set of plans indicating location and width of aisles. location 3. Hazardous materials shall be in accordance with Chapter of exits. exit access doors, exit signs, height of storage. and lo- 27 . cations of hazardous materials shall be submitted at the time of 4. Storage of combustible paper records shall be in accor- permit application for review and approval. Following ap- dance with NFPA 231C. proval of the plans. a copy of the approved plans shall be main - 5. Storage of combustible fibers shall be in accordance with taincd on the premises in an approved location. Chapter 29. 6. Storage of miscellaneous combustible material shall be SECTION 2302 in accordance with Chapter 3. DEFINITIONS 2301.2 Permits. A permit shall be required as set forth in Sec- 2302.1 Definitions. The following words and terms shall. for tion 105.6. the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. 2301.3 Construction documents. At the time of building per- mit application for new structures designed to accommodate ARRAY. The configuration of storage. Characteristics conrid- high -piled storage or for requesting achangeofoccupancy /use, creel in defining an array include the type of packaging, flue and at the time of application for a storage permit. plans and spaces, height of storage and compactness of storage. specifications shall he submitted for review and approval. In ARRAY, CLOSED. A storage configuration having a 6 -inch addition to the information required by the International Build (152 mm) or smaller width vertical flue space that restricts air ing Code, the storage permit submittal shall include the infor- movement through the stored commodity. mation specified in this section. Following approval of the BIN BOX. A five -sided container with the open side facing an plans. a copy of the approved plans shall be maintained on the aisle. Bin boxes arc self - supporting or supported by a structure premises in an approved location. The plans shall include the designed so that little or no horizontal or vertical space exists following: around the boxes. PRO /DED 1. Floor plan of the building showing locations and di- COMMODITY. A combination of products. packing matcri- mensions of high -piled storage areas. als and containers. ( QUIR tP 2. Usable storage height for each storage area. DRAFT CURTAIN. A structure arranged to limit the spread I PROV'DEP 3. Number of tiers within each rack, if applicable. of smoke and heat along the underside of the ceiling or roof. REQU!R.fp 4. Commodity clearance between top of storage and the if EARLY SUPPRESSION FAST-RESPONSE (ESFR) sprinkler deflector for cach storage arrangement. SPRINKLER. A sprinkler listed for early suppression fast-re- - REOUIQCI) 5. Aisle dimensions between each storage array. sponse performance. IL ni 6. Maximum pile volume for each storage array. EXPANDED PLASTIC. A foam or cellular plastic material BEIPPIEZD 7. Location and classification of commodities in accor- having a reduced density based on the presence of numerous dance with Section 2303. small cavities or cells dispersed throughout the material. REQ /fl07 8. Location of commodities which are banded or encapsu J EXTRA -HIGH -RACK COMBUSTIBLE STORAGE. laced, Storage on racks of Class 1. i1. Ili or iV commodities which ex• PRa VIDCO teed 40 feet (12 192 mm) in height and storage on racks of 9. Location of requ fire department access doors, high - hazard commodities which exceed 30 feet (9144 mm) in AE6 V1RED 10. Type of fire suppression and fire detection systems. height. RaGEu/4 c 11. Location of valves controlling the water supply of ceil- HIGH -PILED COMBUSTIBLE STORAGE. Storage of ing and in -rack sprinklers. combustible materials in closely packed piles or combustible N 12. Type, location and specifications of smoke removal and materials on pallets. in racks or on shelves where the top of curtain board systems. storage is greater than 12 feet (3658 mm) in height. When re- 2003 INTERNATIONAL FIRE COOS/0 201 TRANSMISSION VERIFICATION REPORT TIME : 06/16/2005 08:58 NAME : TIGARD BUILDING DEPT FAX : 5036243681 TEL SER.# : BROD4J479592 DATE,TIME 06/16 08:57 FAX NO. /NAME 5034650677 DURATION 00:00:34 PAGE(S) 01 RESULT OK MODE STANDARD r June 16, 2005 `- 4 � 1 I ' . ' �J rr' CITY OF TIGARD Jerry Griffith OREGON NorthWest Handling Systems, Inc. 18008 NE Airport Way Portland, OR 97230 RE: RACK STORAGE @ CROWN CARPETS -2 " Review Building Permit: BUP2005 -00238 Construction Type: TIT N Address: 12230 SW Main Street Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The following items remain and are required prior to the issuance of the Rack Storage Permit. GENERAL • Clarify the classification of the commodities being stored in accordance with section 2303 OFC. • Type of fire suppression system. (See comment regarding Sprinkler System Analysis) • Location of valves controlling the water supply of ceiling and in -rack. sprinklers. • Dimension and location of transverse and longitudinal flue spaces in accordance with Table 2308.3 OFC SPRINKLER SYSTEM ANALYSIS • A sprinkler system analysis shall be submitted to the City of Tigard, Building Division prior to approval of the Rack Storage Permit. The analysis shall provide • TRANSMISSION VERIFICATION REPORT TIME : 06/16/2005 08:55 NAME : TIGARD BUILDING DEPT FAX : 5036243681 TEL . SER.# : BROD4J479592 DATE,TIME 06/16 08:55 FAX NO. /NAME 5032261670 DURATION 00:00:18 PAGE(S) 01 RESULT OK MODE STANDARD ECM June 16, 2005 . I�. • CITY OF TIGARD Jerry Griffith OREGON NorthWest Handling Systems, Inc. 18008 NE Airport Way Portland, OR 97230 • RE: RACK STORAGE @ CROWN CARPETS -2 Review Building Permit: BUP2005-00238 Construction Type: ITN Address: 12230 SW Main Street Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The following items remain and are required prior to the issuance of the Rack Storage Permit. GENERAL • Clarify the classification of the commodities being stored in accordance with section 2303 OFC. • Type of fire suppression system. (See comment regarding Sprinkler System Analysis) • Location of valves controlling the water supply of ceiling and in -rack sprinklers. • Dimension and location of transverse and longitudinal flue spaces in accordance with Table 2308.3 OFC SPRINKLER SYSTEM ANALYSIS • A sprinkler system analysis shall be submitted to the City of Tigard, Building nivicinn nrinr to annrnva1 of the. 12 a■L- « «,...: FILE COPY hhotiloi June 10, 2005 CITY OF TIGARD OREGON Jerry Griffith NorthWest Handling Systems, Inc. 18008 NE Airport Way Portland, OR 97230 RE: RACK STORAGE @ CROWN CARPETS Building Permit: BUP2005 -00238 Construction Type: IIi -N Address: 12230 SW Main Street Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The following information is required prior to the approval of the submitted plans. GENERAL I have enclosed a copy of Section 2301.3 of the Oregon Fire Code. • Please submit all the information indicated as "Required ". • I have indicated the items that have been provided with the word "Provided ". • I have indicated items that are not required with "NA ". SPRINKLER SYSTEM ANALYSIS • A sprinkler system analysis shall be submitted to the City of Tigard, Building Division prior to approval of the Rack Storage Permit. The analysis shall provide hydraulic calculations verifying that the existing sprinkler system has the required flow for the commodity being stored. FYI In rack sprinklers are required for the project and were not indicated on the previous Fire Sprinkler Permit. Revisions to the existing sprinkler permit will be required or a new sprinkler permit will be required. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respec , rian B ock, Plans xamination Supervisor 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 p f z cr — ay .3 7 NORTH WEST HANDLING SYSTEMS, INC. • 18008 NE AIRPORT WAY PORTLAND, OR 97230 (503) 465 -9200 FAX (503) 465 -0677 TOLL FREE 1- 800-442 -6431 Proposal: 060205CrownComm erdelPermit TO: City of Tigard DATE: June 2, 2005 SUBJECT: Crown Commercial Sales DELIV: TBD FOB: Portland, OR ATTN: Permit Dept TERMS: Net 15 Days From: Jerry Griffith North West Handling Systems, Inc R ECEIVED 18008 NE Airport Way Portland, OR 97230 JUN 0 3 2005 (503) 465 -9200 Ext: 614 Oregon Contractors License #65422 CITY OF TIGARD Federal ID Number: 91- 0869801 BUILDING DIVISION RE: Crown Commecial Sales 12230 SE Main Tigard, OR 97223 Notes: North West Handling Systems, Inc. is working for Crown Commercial Sales to erect Bulk rack in their new facility at 12230 SE Main, Tigard, OR 97223. The value of our rack related to installation and anchoring of this rack is $4,000.00 for which a City of Tigard permit is now sought. Crown Commercial Sales has received a City of Portland permit for Tenant Improvement. This permit relates to storage rack only. The commodity stored are carpet, linoleum, and related products on wood pallets and / or wood decking. Attached: Seizmic calculations for storage rack over 8' height by Rack Design RD- 9791 Corresponding rack floor plan Jerry Griffith, Sales & Design • 4445 SW BARBUR BLVD., SUITE 200 • PORTLAND, OREGON 97239 TEL: 503.226.1 285 FAX: 503.226.1 670 E -MAIL: info @cidainc.com www.cidainc.com June 16, 2005 - City of Tigard Attn: Brian Blalock Val Henze! 13125 SW Hall Blvd. Tigard, OR 97223 RE: Crown Carpets — Rack Permit Permit Number. BOP 2005 -00238 CIDA Project Number. 040103.01 Dear Brian: Doug Lepper of Crown Carpets has requested that CIDA provide you with further explanation and information on the racking at the remodeled Crown Carpets location per your request on June 10, 2005. Following is the response to the High -Pile Combustible Storage Chapter 23 requirements included within your plan checklist: I. Per your comment, NorthWest Handling Systems (NWHS) provided the locations and dimensions of the high -piled storage areas. We have also included a copy of their sheet for ease of reference. 2. The usable storage height for each storage area is 16' high. This has been depicted on a drawing called racking elevation (Sheet .1). We believe this was a supplemental drawing recently supplied by NWHS, but we have also included it within this package for ease of reference. 3. Per your comment, NWHS provided information to establish the number of tiers within each rack. 4. The distance from the top of the carpet being stored to the sprinkler deflector is 8' -0 ". We believe this was a supplemental drawing recently supplied by NWHS, but we have also included it within this package for ease of reference. 5. NWHS overlaid the CIDA floor plan with racking and dimensions. It is our understanding that this sheet was revised and resubmitted recently. The aisles as shown are 24' -5 ", 23' -2" and 8' -10 ". 6. Not applicable. • ARCHITECTURE 0 ENGINEERING • PLANNING • INTERIORS • LANDSCAPE 7. The . locations of the commodities are illustrated on the supplemental drawing supplied by NWHS sheet I. The commodities are classified within Class III commodities, rugs without foam backing and Class IV, linoleum products. 8. There are no commodities which are banded or encapsulated. 9. Per your comment the location of the fire access door has been provided. 10. The sprinkler design criteria at the roof is for High Pile storage with .6/2000 square foot for Group A plastics. The sprinkler designer designed the system to a "worst case scenario" to elevate future required modifications to the sprinkler system for future racking. Attached please find information provided by the sprinkler designer, Patriot Fire, on the design criteria. I 1. Attached please . find the location provided by the sprinkler designer, Patriot Fire, locating the riser control valve. 12. Not applicable. 13. Per Table 2308.3, in a m ggle -row rack application, the system is required to have a4" transverse flue space and not required to have a longitudinal flue space. The racks have 3" tube steel at each of the four corners to provide a separation of the commodities from rack to rack, creating a transverse flue space within the racking system. In addition, due to the nature of the rolls of carpet, the separation between commodities at the tube steels easily exceeds the minimum requirements. r1 argyle. kr ►-ac.l +> 110 u—) b" c.. e- beituc..r` ¥$.L) -s • I have included the hydraulic calculations provided by Patriot Fire that verify the existing design of the sprinkler system was designed for high -pile storage, and to provide coverage for the products stored within Crown Carpets. The racking is constructed without solid shelving in accordance with IFC 2308.2.2 Exception I. The shelving is constructed of 2x4 wood studs laid flat with 5 I A " spacing between face of stud to face of stud. In accordance with IFC Table 2308.3 and NFPA 13 Table 12.3.2.1.2, the rack storage is not required to have an in -rack sprinkler system. In addition, Doug Lepper has provided information in regards to the flammability of carpet and smoke density. Carpet is highly regulated for flammability to insure safety within residential and commercial applications. This information is included for your reference. Sincerely, Jennifer Beattie Project Manager Enclosure: Sheet I and Al . I , IFC Table 2308.3. NFPA 13 — 1 2.3.2.1.2, Hydraulic Calcs, Sprinkler design criteria letter, Carpet Flammability. c: Doug Lepper, Crown Carpets David Welsh, CIDA, file \ \fileserv\admin \GENADMIN \PROJECTS \04 \0I 03.00_crown carpet \06 - I 6-05_rackdoc