Correspondence CITY OF TIGARD OREGON November 14, 2005 Brian Elliot SLX Architects 213 SW Ash Street Portland, OR 97204 Re: Alternate Method of Construction — E -1 Occupancies Metzger Elementary School C.F. Tigard Elementary School 10350 SW Lincoln Street 12855 SW Grant Avenue Permit # BUP2003 -00585 Permit # BUP2003 -00570 We had previously approved your request for an alternate method of construction in conjunction with Eric McMullen, Deputy Fire Marshal with Tualatin Valley Fire & Rescue for the above referenced projects. We recently discovered that we had not formally documented this approval as required by the code. Therefore, please accept this as notification that the following alternate has been approved by the City of Tigard Building Division. Your proposal was to construct these two buildings of Type II One -Hour construction, fully sprinklered in order to achieve your desired floor area, with some relief from the one -hour fire - resistive construction. Your other alternative would be to subdivide the buildings with 2 -hour area separation walls without a fire sprinkler system. Our belief is that a sprinklered building provides a far greater level of safety to the occupants than a nonsprinklered building provided with fire walls. However, the code does not allow us to use a sprinkler system for both an area increase and substitution for one -hour construction. Therefore, the following additional requirements must be met in order for us to approve the request. 1. The buildings will be provided with an Ordinary Hazard Group 2 sprinkler system instead of the required Light Hazard; and 2. The exit corridors shall be constructed as one -hour corridors with opening protection as required by Section 1004.3.4; and 3. Full coverage smoke detection throughout. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 - Based on these additional items we feel that the buildings provide a level of protection to the occupants equal to or greater than the code prescribes. They are, in our opinion, inherently safer than a nonsprinklered building with fire wall compartmentization. These conditions were identified as being required items during the plan review process and were reviewed and inspected as such. All conditions have been met and have been approved in accordance with Section 104.2.8 of the State of Oregon Structural Specialty Code, 1998 edition. If you have any questions, please contact me at (503) 718 -2448. Respectfully, G Lampella Building Official c. Stephen Pogue, Tigard — Tualatin School District 23J File 05:5TPM FROM -SLX 503- 224 -4836 T -662 P.02/02 F -814 March 28, 2003 Gary Lampella Building Official, City of Tigard 13125 SW Hall Blvd. Tigard, OR 97223 RE: METZGER ELEMENTARY /C.F. TIGARD ELEMENTARY ALTERNATE METHODS OF CONSTRUCTION Gary: This letter is to follow up discussions held at the City of Tigard on March 24, 2003 regarding the building code analysis for the replacement schools at Metzger Elementary and C.F. Tigard Elementary. Occupancy groups in both schools include E -1 (classrooms and library) and A2.1 (commons and gymnasium). Based on the use of structural components (steel), number of stories (2) and limitations set by table 5 -B of the U.B.C., Type U one -hour construction will be utilized. It is our goal to eliminate the need for one -hour construction, except for corridors, or the requirement for an automatic sprinkler system (per 904.2.4) due primarily to budgetary reasons. The size of the proposed buildings does not allow the group E -1 occupancies to substitute an automatic sprinkler system for one -hour construction (section 904.2.4; crossreference section 508). Section 904.2.4 of the U.B.C. would allow this substitution to occur if the building were subdivided (by area separation walls) into 20,000 sq. ft. areas. This subdivision of the building would allow type II one -hour A2.1 and E -1 occupancies to be constructed without an automatic sprinkler system. In our discussion, SLX Architects proposed providing an automatic sprinkler system throughout the building in lieu of one -hour construction. We feel that combined with non combustible construction, that an automatic sprinkler system would provide improved safety for the building structure and its users. Instead of subdividing the building into 20,000 sq.ft. compartments, which would be of type II N and type II one -hour construction without an automatic sprinkler, we respectfully request that an automatic sprinkler system be installed throughout the building in lieu of one -hour construction as an alternate method of construction per U.B.C. 104.2.8. Please provide a response at your earliest convenience for the inclusion in our documents. Thank you Brian Elliott SLX Architects Cc: Eric McMullen Brian Raddabaugh January 12, 2004 CITY OF TIGARD OR EGON Delta Fire, Inc. 14795 SW 72 Portland, OR 97224 RE: FIRE SPRINKLER SYSTEM @ METZGER Project Information � /64-141 Building Permit: BUP2003 -00585 Construction Type: II -1HR Tenant Name: Metzger Elementary Occupancy Type: E -1 Address: 10255-SW-90--Avenue Occupant Load: NA Area: 67,400 Sq Ft Stories: 2 Sprinkled: In lieu of 1HR construction Alarms: Automatic The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. 1. A key box shall be installed within 20 feet of the riser room entrance. The bottom of the ke3f box shall be not less than 8 feet nor more than 10 feet above the walking surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 Contact TVF &R for keybox at 503- 612 -7010 2. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property. Standard 9 -1, section 2 -2.7.1 OSSC 3. A special sprinkler wrench shall be provided and kept in the cabinet along with the spare sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1, section 2 -2.7.2 OSSC 4. A minimum of 18 inches shall be maintained between top of storage and ceiling sprinkler deflectors. Standard 9 -1, section 4 -4.1.6 and 4 -4.3.2 OSSC 5. Sidewall sprinkler deflectors shall be located not more than 6 inches or less than 4 inches from walls and ceilings. Standard 9 -1, section 4- 4.2.3.3 OSSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 - 2772 6. Clearances shall be provided around all piping extending through walls, floors, platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 1/2 inches shall be not less than 1 inch. Minimum clearance for pipes 4 inches and larger shall be 2 inches. Standard 9 -1, section 4- 5.4.3.4 7. Monitoring, Section 904.3.1 OSSC All valves controlling the water supply for the automatic sprinkler system shall be electrically monitored. 8. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. An approved audible sprinkler flow alarm to alert the occupants shall be provided in the interior of the building in a normally occupied location. 904.3.2 OSSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respect +( : rian Bla Senior ',.. 1 Ex. er s ` " • penkro SIlL FILE COPY 4, 2003 .19 A CITY OF TIGARD Brian Radabaugh Cornerstone Construction OREGON 5410 SW Macadam Avenue, Suite 250 Portland, OR 97239 RE: PHASED PERMIT FOR METZGER ELEMENTARY, EXTERIOR & INTERIOR WALLS AND MECHANICAL Building Permit: BUP2003 -00585 Construction Type: II -1HR Tenant Name: Metzger Elementary Occupancy Type: E -1 Address: 10255 SW 90 Avenue Occupant Load: NA Area: 67,400 Sq Ft Stories: 2 Sprinkled: In lieu of 1HR construction Alarms: Manual The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition and the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition. The following information is required prior to the issuance of the second phase of the above referenced project. Provide a written item by item list to clarify the responses to the following; GENERAL 1. The plans submitted do not complete the construction documents required for construction. Please provide a written list to document any additional deferred submittals that will be submitted at a future date. 2. The "Power and Signal" plan indicate the location of smoke detectors, strobes, pull stations, etc.... Provide equipment cut sheets, battery calculations, voltage drop calculations and identify candela rating on the plans for fire alarm/smoke detector review. 3. Several Sheets are identified as "For Reference Only ". Provide replacement drawings for construction documents. 4. Provide the energy code information required by chapter 13 of the OSSC. The required forms should include Building Envelope, HVAC Systems & Lighting Budget. 5. Provide a complete door schedule indicating the ratings and hardware for all doors. The submitted project manual door schedule was incomplete. Review has not been done at this time and will be done when a complete schedule has been submitted. 6. Provide drawings for ceiling construction. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 1 I ' I 7. Provide a door for Rest room C126. FIRE- & LIFE - SAFETY 8. The travel distance reduction required for the area increase does not meet the requirements of section 1007.3.3.1 OSSC. Provide a solution. 9. Music room A112 requires 2 exits. 1 exit is required to a corridor or directly to the exterior, and 1 exit may travel through an intervening room. Revise drawings. 10. Rated wall listing 16.1 -1 is acceptable for wall types 50 and 51. Provide a listing for all other walls that are required to be rated. ie wall type 200 at room C128 & C228, C131 & C231 and wall type 53 at stair 125. 11. Glazing is indicated at the NE corner of rooms C121 & C221. The glazing is adjacent to a rated stairwell. Revise plans to indicate 3 hour glazing at these locations. 12. Corridor C101 ends at Stair B125. It appears to have a door, B125B, perhaps a rolldown fire door, to separate the corridor from the non -rated Lobby B101. The door is on the West side of the seismic joint. Clarify how the integrity of the corridor is maintained through the seismic joint. 13. The code requires an unobstructed floor space within the accessible restroom of sufficient size to inscribe a 60 inch diameter circle. Clarify the clear floor space RR- A105, B110, B127 and C114. Section 1109.10.2 STRUCTURAL 14. There were no calculations submitted with the plans. The previous structural submittal only addressed the structural frame. Provide calculations for the components submitted with this phase including their connections to the structural frame. 15. Special inspection will be required for Structural welding and High- Strength Bolting. Clarify special inspection agency. 16. Provide drawings for the window curtain walls including calculations for their structural support and anchorage to the structural frame. 17. Clarify compliance with the area limitations as determined in section 2403 OSSC. 18. Provide product information for load capacity of the "Verticlip" product. 19. The embedded plate called out on sheet S2.1Bw & S2.1Cw was not in the first phase of structural drawings. The concrete is poured. Provide information to clarify the installation of the embeds. • • 20. Provide calculations for the construction of all exterior canopies, welds, bolts, footings, cantilever, etc.. 21. Clarify the attachment to the structure of the Tube Steel framing, top & bottom, grid B around the opening between the kitchen and the commons. 22. Detail 7/S7.2 does not indicate the attachment of the top track to structure. Clarify support for the top track to structure. 23. Details 13 & 17/S7.3 do not indicate complete connection criteria. Clarify all welds. 24. Canopy plan A provide the following: • Cross - section at concrete columns indicating column reinforcement. • Cross - section at concrete columns indicating connection to W16 x 26. • Cross - section at concrete columns indicating connection to W8 x 18. MECHANICAL 25. Provide all mechanical equipment cut sheets. 26. Provide calculations and design for anchorage of mechanical equipment exceeding 400 lbs. 27. Dryer duct on sheet M2.1A exceeds 25 feet. Section 504.6.1 OMSC Provide an alternate design. 28. Return grill in corridor between grid S & T @ 17 & 18 requires Fire /Smoke damper. Revise drawings. 29. Clarify exhaust for room C227. 30. Exhaust fan 9 does not appear on the roof plan. Clarify location of EF9. 31. Provide equipment cut sheets for the devices and equipment used for fire suppression of the kitchen hood. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Brian Blalock, Senior Plans Examiner OFFICE COP'S S L}( 224 SW FIRST AVENUE PORTLAND, OREGON 97204 T1503.224.0173 F 1 503.224.4836 December 15, 2003 Brian Blaylock DEC 2 4 2003 Building Official, City of Tigard CITY OF TIGARD 13125 SW Hall Blvd. BUILDING DIVISION Tigard, OR 97223 RE: METZGER ELEMENTARY Brian: Please find the following responses to the plan review comments dated November 24,2003: GENERAL 1. The plans submitted do not complete the construction documents required for construction. Please provide a written list to document any additional deferred submittals that will be submitted at a future date. We will be submitting the following items as deferred submittals: 1. Cut sheets and installation instructions for mechanical joint connections for fire service lines (requirement from site work package comment 3. dated July 8, 2003). 2. Cut sheets for fire service line valves (requirement from site work package comment 4. dated July 8, 2003). 3. Water heater seismic strapping details (requirement from plumbing plan review comment 3. dated October 3, 2003). 4. Isometric drawings for roof drains and overflows (requirement from plumbing plan review comment 7. dated October 3, 2003). 5. Steel joist shop drawings and calculations. 6. Fire Sprinkler shop drawings. 7. Kitchen hood fire suppression. 8. Fire alarm shop drawings and cut sheets. 2. The "Power and Signal" plan indicate the location of smoke detectors, strobes, pull stations, etc.... Provide equipment cut sheets, battery calculations, voltage drop calculations and identify candela rating on the plans for fire alarm/smoke detector review. Information will be furnished as part of fire alarm shop drawing deferred submittal. S E L I G / L E E / R U E D A A R C H I T E C T S + P L A N N E R S , L L C • • 3. Several sheets are identified as "For Reference Only ". Provide replacement drawings for construction documents. Bid package 5 documents will be sent to you to complete all final submitted plans. See attached updated structural drawings which include all addendums and value engineering changes to this point. 4. Provide the energy code information required by Chapter 13 of the OSSC. The required forms should include Building Envelope, HVAC Systems and Lighting Budget. See attached completed energy code. 5. Provide a complete door schedule indicating the ratings and hardware for all doors. The submitted project manual door schedule was incomplete. Review has not been done at this time and will be done when a complete schedule has bee submitted. Completed door and hardware schedule is part of Bid package 5. See item no. 3. 6. Provide drawings for ceiling construction. Completed ceiling detailing is part of Bid package 5. See item no. 3. 7. Provide a door for Restroom C126. Restroom door is shown in both Bid package 4 and 5 on sheets 2.2C and 2.4 detail 58/2.4. FIRE -& LIFE SAFETY 8. The travel distance reduction required for the area increase does not meet the requirements of section 1007.3.3.1 OSSC. Provide a solution. As per the memorandum dated October 31, 2003 and the follow up memorandum dated November 03, 2003, the modifications shown to decrease the travel distance are adequate for the area increase shown in the building code study on sheet 0.1. 9. Music room A112 requires 2 exits. 1 exit is required to a corridor or directly to the exterior, and 1 exit may travel through an intervening room. Revise drawings. Per 1004.2.2, exception 1., access to exits may occur through lobbies. Lobby A113 exits to the exterior through doors at the termination of the Lobby ramp shown on sheet 2.1B. 10. Rated wall listing 16.1 -1 is acceptable for wall types 50 and 51. Provide a listing for all other walls that are required to be rated. i.e. wall type 200 at room C128 & C228, C131 & C231 and wall type 53 at stair B125. Wall type 53 — 5/8" type `x' gypsum board will be installed on both sides of wall and continue to adjacent roof deck where it will be sealed in an approved manner. Similar to wall type 51, the adjacent room will be completely separated to form a smoke tight barrier. Wall type 200 — the rated wall type is exactly the same as wall type 50 with the addition of a brick veneer skin. We will clarify the need for the stud wall with 5/8" type `x' gypsum board ea. side to meet UBC 16.1 -1. Wall type 400 — wall type meets UBC table 7 -B, item no. 6 -1.1. 11. Glazing is indicated at the NE corner of rooms C121 & C221. The glazing is adjacent to a rated stairwell. Revise plans to indicate % hour glazing at these locations. Window types 83 and 84 are shown in Bid package 5 on sheet 8.7 as having fire rated glazing. 12. Corridor C101 ends at Stair B125. It appears to have a door, B125B, perhaps a rolldown fire door, to separate the corridor from the non -rated Lobby B101. The door is on the west side of the seismic joint. Clam how the integrity of the corridor is maintained through the seismic joint. The corridor terminates at the rated rolldown door B125B as shown in the door schedule in Bid package 5. Wall and ceiling details of the seismic joints are shown on details 28/9.1, 22/9.2 and 33/8.8 of Bid package 5 and are shown to provide a fire barrier integral with the expansion joint. Assemblies are tested in accordance with ANSI/UL 2079 procedures for one and two hour classifications. 13. The code requires an unobstructed floor space within the accessible restroom of sufficient size to inscribe a 60 inch diameter circle. Clam the clear floor space RR- A105, B110, B127 and C114. Section 1109.10.2. See the attached restroom plan. STRUCTURAL 14. There were no calculations submitted with the plans. The previous structural submittal only addressed the structural frame. Provide calculations for the components submitted with this phase including their connections to the structural frame. Refer to the attached structural calculations. These calculations reflect the structural drawings dated 11 -21 -03 attached. 15. Special inspection will be required for structural welding and high- strength bolting. Clam special inspection agency. Carlson Testing Inc. (503) 684 -3460. 16. Provide drawings for the window curtain walls including calculations for their structural support and anchorage to the structural frame. There are no curtain wall systems on this project. All windows are standard storefront systems. 1 7. Clark compliance with the area limitations as determined in section 2403 OSSC. Largest area of glass is approximately 21 sq.ft. The design wind pressure of 80 has an adjustment factor of 1.70 for 2 panes of insulated glass (Table 24 -A) for an actual design wind pressure of 47. 21 sq. ft. of 1 /4" glass is within the allowable area at a design wind pressure of 47 according to Graph 24 -1. 18. Provide product information for load capacity of the "Verticlip " product. Refer to the attached calculation sheets S -15 through S -20. • • 19. The embedded plate called out on sheet S2.1Bw & S2.1 Cw was not in the first phase of structural drawings. The concrete is poured. Provide information to clarifi, the installation of the embeds. Refer to the attached detail RS.31. 20. Provide calculations for the construction of all exterior canopies, welds, bolts, footings, cantilever, etc. Refer to the attached calculation sheets S -36 through S -42. Note that only Canopy A shown on 1/S7.0 will be constructed. 21. Clar the attachment to the structure of the tube steel framing, top & bottom, grid B around the opening between the kitchen and the commons. Refer to the attached clarification memo dated 12 -11 -03 and detail RS.34. 22. Detail 7/S7.2 does not indicate the attachment of the top track to structure. Clark support for the top track to structure. See attached details. 23. Details 13 & 17/S7.3 do not indicate complete connection criteria. Clarify all welds. Refer to the attached revised details RS.32 and RS.33. 24. Canopy plan A provide the following: - Cross - section at concrete columns indicating column reinforcement. - Cross - section at concrete columns indicating connection to W16x26. - Cross - section at concrete columns indicating connection to W8x18. Refer to detail 4/S7.1 on drawings dated 11 -21 -03 and the attached details RS.29, RS.30 and RS.35. MECHANICAL 25. Provide all mechanical equipment cut sheets See attached cut sheets. 26. Provide calculations and design for anchorage of mechanical equipment exceeding 4001bs. rr •RQy s4 4 VAK4 Ac 27. Dryer duct on sheet M2. IA exceeds 25 feet. Section 504.6.1 OMSC. Provide an alternate design. The dryer vent will be changed to route up inside wall of Office A103 to a point approximately 12 ft. above floor and elbow to the outside with a dryer vent outlet with backdraft damper. n L " V JS E 5 11 6 Ti - / 4 28. Return grill in corridor between grid S & T @ 17 & 18 requires fire /smoke damper. Revise drawings. The duct connecting the second floor return grill in the corridor will be modified to have a fire /smoke damper at the corridor penetration. 29. Clam exhaust for room C227. 30. Exhaust fan 9 does not appear on the roof plan. Clarify location of EF -9. EF -9 is a transfer fan located in the ceiling space, taking air from IDF room C226 and discharges into the ceiling plenum. 31. Provide equipment cut sheets for the devices and equipment used for fire suppression of the kitchen hood. Fire suppression of the kitchen hood is provided by the kitchen hood supplier and installing contractor. We request a deferment of this submittal until information is made available. If there are any questions or required revisions to the statements above, please do not hesitate to call at 503- 224 -0173. Thank you Brian Elliott SLX Architects cc. Brian Radabaugh 6' -9" �_ _. I I 1 - - - -- -1 -__ 1 _ L _ -` - _ _ Ali* �; i RR R 18' 1l--_. �I _ 8' 1 1 I 1 _� i `— 1 _,__n■NNI._________ 3" mil CO 105 52 RR B110 2.4 1/4" =1' -0" 2.4 1/4" =1' -p» 1 II I \! i li ILM L- 1 \ 0 S CUSTODIAL o .4_ 1 ] jC113j i rn In M R I B 27 A __Nt rEl ____, „Lfr ,.. . 1 3' I — - , MEI 1 R =18 �o o 1 1 f r 1 0- L al..... i l 41 • 1 d \. '...4. I N I O I ^ I 94 RR B127 9 6 RR C114 2 .4 1/4" =1' -0" 2 . 4 1/4" =1' -p„ f ILE cop February 17, 2004 Bob Richards Power Plumbing 6611 SW Multnomah Boulevard Portland, OR 97223 RE: GAS PIPING & HYDRONIC PIPING Building Permit: MEC2004 -00064 Construction Type: II -1HR Tenant Name: Metzger Elementary School Occupancy Type: E -1 Address: 10350 SW Lincoln Street Occupant Load: NA Area: 67,749 Sq Ft Stories: 2 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99- 01) 1999 edition. 1. Gas piping shall be installed as noted on sheets P0.1, P2.1A, P2.1B, P2.1C, P2.2A, P2.2B, P2.2C, P2.3C & P5.1 of approved plans, issue date 12 SEPTEMBER 2003. 2. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC 3. Hydronic piping shall be installed as noted on sheets M2.1 A, M2.1 B, M2.1 C, M2.2C, M4.1, M6.1 and M6.3 of approved plans, issue date 12 SEPTEMBER 2003. 4. Hydronic piping shall be tested at relief valve setting as noted on sheet M6.1 FYI A Boiler Permit is required for the project. Contact the Building Codes @ 503 -378- 4133 for the permitting process. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Respectfully, Brian Blalock, Senior Plans Examiner 1 9 -G, ,12:32PM FROM-SLX 503 - 224-4836 T7!52 P.01/02 F -545 • Ilk 1 $ , : j FAXMITTAL ft , I ���, � S lJ1 ' 'ill Wz l }} ll: 4 0 � l 224 SW FIRST AVENUE PORTLAND, OREGON 97204 T1503.224.0173 F1503.224.4836 to: 13Rt /hN i31.A (LOCI - project: Z. from: 3i N W . fax number: date: 0 2. - (q - 0 4' _ no. of pages: _ re: V St G ( copies: date: description these e;re transmitted as checked below: ❑ for approval ❑ as requested ❑ for your use ❑ for review and comment remarks; " RC-v Cwo l G :-.,Y . - • 0 T e X-C Lt. b ti= ) CA SI"'W Ote K S t4 C- Fro t) TIN-6 es . l.. — l.A E KANNVJ ( Th S t S M' LE PO ti, GA/ 4 W V rA TD oacu MC-NT cc: &&(P4 le4 { , S E L I G / L E: C / R lJ E: O A A R C H I T E C T S + P L A N N E R S , L L C FEB- 19:04,.12'32PM FROM -SLX 503-224-4836 T.4f2 P.02/02 F -545 ik I, ' WALL, Moves EAT I = — — _ MI Cnutgreit4- (HALL MOvES S Coot. MOVES of Iltgi l itrl r1 _ IIII _ f COU�1 r -, T! t.,„„LL, i _ tiooR MOVES WEST L_J r - - C MUSIC M12 -► F�4Ce OF 151 I MwES EAST IF ill it. r ill _ it', - =i =i - - - ___ zr • pRt GINAd - czoOm SQ."(; <INGLvt.INC7 C,aseWOZ 1240 • ROOM sQ •FT. ceXCLUD(146 CACONoRK w /c+tFkt4GEs SA-kow tJ > _ 1 — 3OCCUr.h -+- to&a1 44 A9 ' FILL l . A February 19, 2003 . i' CITY OF TIGARD Brian Radabaugh Cornerstone Construction OREGON 5410 SW Macadam Avenue, Suite 250 Portland, OR 97239 RE: FINAL PHASE PERMIT FOR METZGER ELEMENTARY Building Permit: BUP2003 -00585 Construction Type: II -1HR Tenant Name: Metzger Elementary Occupancy Type: E- 1 /A2.1 Address: 10350 SW Lincoln Street Occupant Load: 2500 Area: 70,918 Sq Ft Stories: 2 Sprinkled: In lieu of 1 HR construction Alarms: Manual The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. FIRE- & LIFE - SAFETY 1. Sprinklers have been used in lieu of the 1 hour fire resistive construction as permitted by section 904.2.4.1 OSSC. The sprinkler system has been upgraded from Light Hazard to an Ordinary Hazard, Group II, to increase the density as an alternate to Section 508 OSSC as permitted by section 104.2.8 OSSC. 2. The travel distance required by section 1007.3.3 OSSC has been reduced by 50% to permit an allowable area increase for the entire structure of 50% as noted in section 305.2.1 OSSC. Eight classrooms exceed the reduced travel distance to the rated corridor as required by section 1007.3.3.1 OSSC by 10 feet. The applicant will be installing a smoke detection system throughout the entire corridor system as an alternate as permitted by section 104.2.8 OSSC 3. Smoke Detection shall be provided in accordance with section 1007.3.4 OSSC. 4. Automatic sprinkler systems and manual and automatic fire alarms, and shall be connected to the building fire alarm system. 1007.2.4.1 TVFR99 -01 Group A occupancy portions shall be alarmed as per E occupancies. 5. Exit doors shall be provided with panic hardware.1007.3.10 OSSC 6. Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 Y2 hours of illumination in case of primary power loss. 1003.2.8.5 OSSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 L_ • • S • 7. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied. The means of egress illumination shall be provided with a second source of power in case of primary power loss. 1003.2.9.2 OSSC 8. Provide one 2 -A rated fire extinguisher so that no usable space has a distance greater than 75 feet to the extinguisher. Standard 10 -1, Chapter 3 TVFR99 -01. STRUCTURAL 1. Special Inspection: Special inspection is required for Epoxy Anchors and Site Welding. The special inspection agency of record shall furnish inspection reports to the Engineer of Record, Nishkian Dean, the General Contractor, Baugh - Skanska and the City of Tigard, Building Division, attention Hap Watkins. All discrepancies shall be brought to the immediate attention of the general contractor for correction. The special inspector shall submit a final signed report stating whether the work requiring special inspection was, to the best of the inspector's knowledge, in conformance with the approved plans and specifications and the applicable workmanship provisions of the code. 1701.3 OSSC • Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will be charged a deferred submittal fee based on the valuation of the portion of the work being deferred. The minimum fee shall be $200.00. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respec , Bri. : la . ck, • tor Plans Examiner Ag c H / 7C C OFFICE C9PY qc AGSPoNS DCj'ti p jvDn 1 779L_f architects SLX 224 SW FIRST AVENUE PORTLAND, OREGON 97204 T 503.224.0173 F 503.224.4836 R 4 g December 15, 2003 ? - 3 TO Brian Blaylock �Q� �O Building Official, City of Tigard Q F ()I 13125 SW Hall Blvd. Tigard, OR 97223 eN1E -v` RE: METZGER ELEMENTARY Brian: Please find the following responses to the plan review comments dated November 24,2003: GENERAL 1. The plans submitted do not complete the construction documents required for construction. Please provide a written list to document any additional deferred submittals that will be submitted at a future date. We will be submitting the following items as deferred submittals: 1. Cut sheets and installation instructions for mechanical joint connections for fire service lines (requirement from site work package comment 3. dated July 8, 2003). 2. Cut sheets for fire service line valves (requirement from site work package comment 4. dated July 8, 2003). 3. Water heater seismic strapping details (requirement from plumbing plan review comment 3. dated October 3, 2003). 4. Isometric drawings for roof drains and overflows (requirement from plumbing plan review comment 7. dated October 3, 2003). 5. Steel joist shop drawings and calculations. 6. Fire Sprinkler shop drawings. 7. Kitchen hood fire suppression. 8. Fire alarm shop drawings and cut sheets. 2. The "Power and Signal" plan indicate the location of smoke detectors, strobes, pull stations, etc.... Provide equipment cut sheets, battery calculations, voltage drop calculations and identify candela rating on the plans for fire alarm /smoke detector review. Information will be furnished as part of fire alarm shop drawing deferred submittal. S E L I G / L E E / R U E D A A R C H I T E C T S + P L A N N E R S , L L C 3. Several sheets are identified as "For Reference Only ". Provide replacement drawings for construction documents. Bid package 5 documents will be sent to you to complete all final submitted plans. See attached updated structural drawings which include all addendums and value engineering changes to this point. 4. Provide the energy code information required by Chapter 13 of the OSSC. The required forms should include Building Envelope, HVAC Systems and Lighting Budget. See attached completed energy code. 5. Provide a complete door schedule indicating the ratings and hardware for all doors. The submitted project manual door schedule was incomplete. Review has not been done at this time and will be done when a complete schedule has bee submitted. Completed door and hardware schedule is part of Bid package 5. See item no. 3. 6. Provide drawings for ceiling construction. Completed ceiling detailing is part of Bid package 5. See item no. 3. 7. Provide a door for Restroom C126. Restroom door is shown in both Bid package 4 and 5 on sheets 2.2C and 2.4 detail 58/2.4. FIRE -& LIFE SAFETY 8. The travel distance reduction required for the area increase does not meet the requirements of section 1007.3.3.1 OSSC. Provide a solution. As per the memorandum dated October 31, 2003 and the follow up memorandum dated November 03, 2003, the modifications shown to decrease the travel distance are adequate for the area increase shown in the building code study on sheet 0.1. 9. Music room A112 requires 2 exits. 1 exit is required to a corridor or directly to the exterior, and 1 exit may travel through an intervening room. Revise drawings. Per 1004.2.2, exception 1., access to exits may occur through lobbies. Lobby A113 exits to the exterior through doors at the termination of the Lobby ramp shown on sheet 2.1B. 10. Rated wall listing 16.1 -1 is acceptable for wall types 50 and 51. Provide a listing for all other walls that are required to be rated. i.e. wall type 200 at room C128 & C228, C131 & C231 and wall type 53 at stair B125. Wall type 53 — 5/8" type `x' gypsum board will be installed on both sides of wall and continue to adjacent roof deck where it will be sealed in an approved manner. Similar to wall type 51, the adjacent room will be completely separated to form a smoke tight barrier. Wall type 200 — the rated wall type is exactly the same as wall type 50 with the addition of a brick veneer skin. We will clarify the need for the stud wall with 5/8" type `x' gypsum board ea. side to meet UBC 16.1 -1. Wall type 400 — wall type meets UBC table 7 -B, item no. 6 -1.1. 11. Glazing is indicated at the NE corner of rooms C121 & C221. The glazing is adjacent to a rated stairwell. Revise plans to indicate 3 /4 hour glazing at these locations. Window types 83 and 84 are shown in Bid package 5 on sheet 8.7 as having fire rated glazing. 12. Corridor C101 ends at Stair B125. It appears to have a door, B125B, perhaps a rolldown fire door, to separate the corridor from the non -rated Lobby B101. The door is on the west side of the seismic joint. Clam how the integrity of the corridor is maintained through the seismic joint. The corridor terminates at the rated rolldown door B125B as shown in the door schedule in Bid package 5. Wall and ceiling details of the seismic joints are shown on details 28/9.1, 22/9.2 and 33/8.8 of Bid package 5 and are shown to provide a fire barrier integral with the expansion joint. Assemblies are tested in accordance with ANSUUL 2079 procedures for one and two hour classifications. 13. The code requires an unobstructed floor space within the accessible restroom of sufficient size to inscribe a 60 inch diameter circle. Clarify the clear floor space RR- A105, B110, B127 and C114. Section 1109.10.2. See the attached restroom plan. STRUCTURAL 14. There were no calculations submitted with the plans. The previous structural submittal only addressed the structural frame. Provide calculations for the components submitted with this phase including their connections to the structural frame. Refer to the attached structural calculations. These calculations reflect the structural drawings dated 11 -21 -03 attached. 15. Special inspection will be required for structural welding and high - strength bolting. Clarify special inspection agency. Carlson Testing Inc. (503) 684 -3460. 16. Provide drawings for the window curtain walls including calculations for their structural support and anchorage to the structural frame. There are no curtain wall systems on this project. All windows are standard storefront systems. 17. Clarify compliance with the area limitations as determined in section 2403 OSSC. Largest area of glass is approximately 21 sq.ft. The design wind pressure of 80 has an adjustment factor of 1.70 for 2 panes of insulated glass (Table 24 -A) for an actual design wind pressure of 47. 21 sq. ft. of 1 /4'' glass is within the allowable area at a design wind pressure of 47 according to Graph 24 -1. 18. Provide product information for load capacity of the "Verticlip " product. Refer to the attached calculation sheets S -15 through S -20. 19. The embedded plate called out on sheet S2.1Bw & S2.1 Cw was not in the first phase of structural drawings. The concrete is poured. Provide information to clarify the installation of the embeds. Refer to the attached detail RS.31. 20. Provide calculations for the construction of all exterior canopies, welds, bolts, footings, cantilever, etc. Refer to the attached calculation sheets S -36 through S -42. Note that only Canopy A shown on 1 /S7.0 will be constructed. 21. Clary the attachment to the structure of the tube steel framing, top & bottom, grid B around the opening between the kitchen and the commons. Refer to the attached clarification memo dated 12 -11 -03 and detail RS.34. 22. Detail 7/S7.2 does not indicate the attachment of the top track to structure. Clarify support for the top track to structure. See attached details. 23. Details 13 & 17/S7.3 do not indicate complete connection criteria. Clarify all welds. Refer to the attached revised details RS.32 and RS.33. 24. Canopy plan A provide the following: - Cross - section at concrete columns indicating column reinforcement. - Cross - section at concrete columns indicating connection to W16x26. - Cross- section at concrete columns indicating connection to W8x18. Refer to detail 4/S7.1 on drawings dated 11 -21 -03 and the attached details RS.29, RS.30 and RS.35. MECHANICAL 25. Provide all mechanical equipment cut sheets See attached cut sheets. 26. Provide calculations and design for anchorage of mechanical equipment exceeding 400 lbs. 11 i- ,` &etuettacited-calettiatiefts, ?..12 dues 3-0Q Sw �+vi lip k 27. Dryer duct on sheet M2.1A exceeds 25 feet. Section 504.6.1 OMSC. Provide an alternate design. The dryer vent will be changed to route up inside wall of Office A103 to a point approximately 12 ft. above floor and elbow to the outside with a dryer vent outlet with backdraft damper. 28. Return grill in corridor between grid S & T @ 17 & 18 requires fire /smoke damper. Revise drawings. The duct connecting the second floor return grill in the corridor will be modified to have a fire /smoke damper at the corridor penetration. 29. Clarify exhaust for room C227. 30. Exhaust fan 9 does not appear on the roof plan. Clarify location of EF -9. EF -9 is a transfer fan located in the ceiling space, taking air from IDF room C226 and discharges into the ceiling plenum. 31. Provide equipment cut sheets for the devices and equipment used for fire suppression of the kitchen hood. Fire suppression of the kitchen hood is provided by the kitchen hood supplier and installing contractor. We request a deferment of this submittal until information is made available. If there are any questions or required revisions to the statements above, please do not hesitate to call at 503- 224 -0173. Thank you Brian Elliott SLX Architects cc. Brian Radabaugh /t 1 1 1 '_ L 1 11 Tem i RR 0:3 A I I I I 1 1 1 W_, 1 _ . R- 18' i ,,,, : 1 I CD jj :" i 4 ' 1 illifilal _ _ _____LIIIIIiilllil 3" _ _ _ _ _ _ _ _ 22 RR A105 5 2 RR B110 2.4 1/4" =1' -O" 2.4 1/4" =1' -o„ _ I '-I j f. 1 1 r 1 \ S ( CUSTODIAL o M 1 � - -- - _, \ 1' 3' \ C R .J 1 I l n // /1 '- t I M IX O I i M O \ U 94 RR B127 96 RR C114 2.4 1/4" =1' -o" 2.4 1/4" =1' -o„ ,W piT /ANAL. J T OCTVrr -t P em, if' Nishkian Dean Consulting and Structural Engineers December 11, 2003 Mr. Brian Elliott Selig /Lee/ Rueda/ Architects 224 First Avenue Portland, OR 97204 Reference: Metzger Elementary NDI Project No: 431.00 Dear Brian: Subject: Clarifications and Revisions for Plan Review Comments 1. Drawing S2.1Aw Add detail reference RS.34 at (2) TS6x4x1/4 columns on gridline B east of gridline 4. 2. Drawing S2.3Aw Add detail reference RS.34 at (2) TS6x4x1 /4 columns on gridline B east of gridline 4. Add detail reference RS.28 at gridline intersections B /4A and B/11A at the TS6x4x1 /4 framing into the CMU wall. 3. Drawing S7.11 Delete details 9, 13, and 14. If you have any questions please call. Sincerely, NISHKIAN DEAN 00(340.,t 0. Robert A. Aman, P.E. Project Engineer • H:WD431 Metzger ES\Admin\Correspondence1431 Clarifications 12- 11- 03.doc 319 SW Washington Street, Suite 720, Portland, OR 97204 Si (503) 274 -1843 FAX (503) 273- 5696 s ? AUCTU ' DP�OF IG IN 4 F ` f ` f 4? 9 0 7 59/f t ; OREGON 4 41) L GO1G EXPIRATION DATE: 6 -30 -05 3 " 3" T . O . W . .. TS6x4x1/4 SEE 13/S7.2 AA" 8" CMU WALL toll/ 1/4 r 2 SIDES 111111% . 1/2x6x1' -4" cV 2) 5/8"o EPDXY ANCHORS EMBED 5 ") OT EPDXY ANCHORS — USE COVERT CIA— GEL7000 INSTALL IN ACCORDANCE WITH ICBO REPORT No. ER -4846. DETAIL AT GRID 11A B 1 1/2-.1 * RESPONSE TO RFI # I5 /LEE /RUEDA SELIG / LEE / RUEDA METZGER ELEMENTARY SCHOOL A R C H I T E C T S & P L A N N E R S TIGARD- TUALATIN SCHOOL DISTRICT No. 23J R S. 2 8 ND431.00 04 DEC 2003 egg ESIDwgs \Strvaural\RS Drawings \RS- 28.DWG, 12 /04/2003 02:37:31 PM N S- cRUCTU/? � _a 4 .4 4,, 9� j I x OREGO CO 4th air o � ( fG E tig"~ v `x 9 9< O L GG VD ~ EXPIRATION DATE: 6- 30 -051 J O Q 3m (.10 lst _ x Sri / < I ( ' 'Mir \ �� I � gin-ii I /- 0 ,•Z/ L Z i „z/ l I. 0-- V x X � 0 < NI F' / I— < U --c\4 0 L W WOQ /� /■ X `tcj f c�m cn 1 'N. 'N. �� in < I I � I , n o I o \ I I z �, z w III r) w w 1 U) U- t ~ i> z H 00 O x 0 CO co co co) M M ,) _ /., d SELIG /LEE /RUEDA S LIXI SELIG / LEE / RUEDA METZGER ELEMENTARY SCHOOL (� A RW C ,0 11 ,, 1 i ,. a, , ,,S,.,&o, . P ;, N N ERs TIGARD- TUALATIN SCHOOL DISTRICT No. 23J R S 9 ND431.00 9 DEC 2003 (t) o r 1A m 3/8" STIFFENER R c R3/4x3x6 1 /2 01 + D ROOFING, SEE ARCH BEVEL R. TO (2) C8x 1 1.5 MATCH ROOF TS 4x2x 1 /4 > � SLOPE Cr1 • 5' -4" R 3/4x4x6 W/ - r" nP \ 111M111111r (2) 3/4" 0 1 BOLTS _ -- 3/16 3/1s C2 2 m I .1 N : ..,,,,, 1 , 7 Z 5 ,, `Z N N 1/4 \ TS16x8x5/16 1/4 1' -6" 1' -5 1/8" 1/4 , r- Li It 1 / V 1 / 4 1I D m W1 6x26 o N SPACER R 3/4x3x6 Li c m W/ (2) 3/4 "95 BOLTS D 4 LOCATE 1' -0" FROM EA m ® END OF W8 BEAM z m C) rn = m o � 2 \ DETAIL — CANOPY A il - 7.y 3/4 " =1' -0" VE C HA\ G ES n 0 i z 0 Z ° 0 o N r w L m °o x lb U U z O ti o m 0 ✓ ° c D c 0Q w Sy r , o q < k ` � \Q \ o \` u, 9 1FtUCTUR4 4 c \ O PROF 7 w 7159 % • OREGON Co `'e, , � cb e`~ P v OPfRA11ON DATE: 6- 30 -05+ ► i TS$x6 OR TS6x4 COLUMN i 1 I� I I /// 1 1 I I 1 1 I 6 " I 1/ Y I I 1/4 V I I w/ I I 3/4x8(2) x0' -8 3/4 "x8" 1 /2" REBAR BEARING EPD PLATE 1 I I I (6" GAGE) 4" CONC. SOG I I RECESS BRG PL INTO TOP OF SLAB A NCHORS I 1 + . 4 ', 1/4 V • It - 9 ETA! L 3/4 " =1' -0" REF: S2.1BW + S2.1CW 6; g17, J F — / 1 J- l 4 z-+ • /0 -- J 5 i W p- (-1 f Y X RESPONSE TO PLAN CHECK ITEM 19 ;ELM / LEE / RUEDA S LX SELIG / LEE / RUEDA METZGER ELEMENTARY SCHOOL A RC n r E C r 5 P N N E R S TIGARD- TUALATIN SCHOOL DISTRICT No. 23J R S. 31 n � S x s.1 St, l- Amon ]nl • h.nl.nd. O:q r ,o. 15I1!2 II I ND431.00 II DEC 2003 9 - c RUCTUF \ 0(0 PROFF ` jirlik i t. po OREGON 0914, 1 4�yQv EXPIRATION DATE: 6 - 30 -051 GRID d- I I M I I II I I I 1 I I 1 I _PLAN 1 1/4 N6 1 /2" CAP PLATE 1/4 TS6x4x1/4 FLAT —N 125' -0" l T.O.W. 7 ( V . . 1 L6x6x3/8 x 0' - 1/4 V CTYP. EACH SIDE —J W8 COLUMN 13 DETAIL— REVISED s7.y 3/4 ". 1'_O" X RESPONSE TO PLAN CHECK ITEM 23 SELIG / LEE / RUEDA S LX SELIG / LEE / RUEDA METZGER ELEMENTARY SCHOOL RS . 3 R C I T E C T S & P L A N N E R S TIGARD - TUALATIN SCHOOL DISTRICT No. 23J II DEC 2003 ND431.00 SS AUCTUR44 .. f %G1f • 9 407 `/p OREGON Q � 9 —(1 4/ 6 %cb' P v 4A 11A (EXPIRATION DATE: 6 -30 -051 I I Ir I I I ^ � II I II I II I I I I I PLAN 1/4 \6 1/4 \6 s 125' -0" TOW 7 4 1 CV TS6x4x 1 /4 FLAT I L6x6x3/8 x 1' - 1/4 17 (TYP. EACH SIDE W10 FRAME COLUMN 7 DETAIL- REVISED (I 7. 3 /4 " =i' -o" • X RESPONSE TO PLAN CHECK ITEM 23 SELIG / LEE / RUEDA SIJ X SELIG / LEE / RUEDA METZGER ELEMENTARY SCHOOL n R C I 1 1 T E C T 5 & P L A N N E R S TIGARD- TUALATIN SCHOOL DISTRICT No. 23J R S. 3 3 !13 SW.. \lv St,.e1. toes !S - f.il■.e4 Or.�a9 v'!a! .1` •_1.91) ND431.00 II DEC 2003 S'RUCTURAt PROP Zt N 45 / 71 F� OREGON �iQ lI' 26, 19 P / : 9( L GOtj BOD (EXPIRATION DATE: 6- 30 -05( W24x55 3 /4 "0 A307 BOLT WITH A ASHER IN 13/16 x3 1/2 SLOTTED HOLE 1/4 4 c 1/4 4 n e M M L6x4x3/8 (LLV) I EACH SIDE OF TS COL. I I , I `TS6x4x1 /4 COLUMN TS12x6x1/4 SEE 10/S7.3 I I I I . j l R.O. SEE ARCH. DWGS � I I SEE 1/S7.3 FOR BASEPLATE DETAIL RECESSED SLAB I SEE ARCH. DWGS I I ee 104' -0" h 1 I 2 LA DETAIL- JAMBS AT ROLL UP DOOR A101 A 3/4" =1' -O" * RESPONSE TO PLAN CHECK ITEM #21 SELIG /LEE /RUEDA SL X SELIG / LEE / RUEDA METZGER ELEMENTARY SCHOOL A R c H i r �. c r s r i. N F. R s TIGARD - TUALATIN SCHOOL DISTRICT No. 23J R S. 3 4 I, N II DEC 2003 \ND431 Metzger ES \Dwgs \ Structural \RS Drawings \RS- 34.DWG, 12/12/2003 02:32:04 PM r ® STRUCTURk 0 IP'OF(j 151 8xBx5 18 "/' ( T58x4x1/4 FLIT ABOVE l o — 7159 , - © w8x18 t H - -- 11 `• III \ OREGON 7, O X x O N N N \ D � 1�� P 0 m 0 W8x18 0 . 4 ^ ® � - ! !6 ' G .j .` N '° n ' O L G, 0 ' ( Ro a^ 3 - - - _ _ n _ (EXPIRATION DATE: 6 -30 -051 (2) C8x11.5 O � El ' u 18x8x5/ 8 L 1 2 f I 7 Alk • S7.1 I 1 RS.30 MOB d .. x k ev m N ox N fp 0 3 n I V111(18 O 3 I 8 TYP. S7.1 RS.29 W8x1B DECK 1 0 0.H. (2) C8x11.5 ' "- 1 0 I F+- H L --E Ts18x8x5�18 1 - r 2 / a 57.1 -I- n � RS.30 ® d . TYP. _ o x m W�1x18 � � Alk X N X X X 3 w 04 Cs1 O — W8x18 J H TS16x6x5 ,8 l 0 TS6x4x1 /4 FIAT cR IZIF SIM. (1.i 4LIN N " 1 PLAN — REVISED CD 7,0 N.T.S. VE CHANGES SELIG /LEE /RUEDA S LX SELIG / LEE / RUEDA METZGER ELEMENTARY SCHOOL �7 S .35 ^ R H I T T s & P s TIGARD - TUALATIN SCHOOL DISTRICT No. 23J x �i1 11 e:.i. Rean :xl - Iefll.[R. �)iroe.. OUOI -i.n ., of ND431 00 11 DEC 2003