Correspondence March 26, 1998 CITY Constructo Inc. CITY O TIGARD
PO Box 54
West Linn, OR 97068
RE: Lundmark Homes Site Plan Review
9275 SW Locust
PC #: 3 -67r SIT #: 98 -0009
Submittal documents for the above referenced project have been reviewed for conformance with
the applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The
following comments are noted:
OK" 6 kM r ' 4441 ` ja 1Y w v °F s
.,;«.2.,n,..,._,,,,_R
� ; ����ya����� '"s����w�c^°,�'a,.•Z„ ` ?�'�.;.��s'�:' -�2,` � i`'.r`�.�`RS��:�a�''� �I
1. DEAD END ROADS: Dead end fire apparatus access roads in excess of 150 feet in
length shall be provided with an approved turnaround. Diagrams of approved
turnarounds area available from the fire district. (UFC Sec. 902.2.2.4)
2. NO PARKINGS SIGNS: Where fire apparatus roadways are not sufficient width to
accommodate parked vehicles and 20 feet of unobstructed driving surface, "No parking"
signs shall be installed on one or both sides of the roadway and in turnarounds as needed
(UFFC Section 902.2.4). Signs shall read "NO PARKING - FIRE LANE - TOW AWAY
ZONE, ORS 98.810 - 98.812" and shall be instralled with a clear space above ground
level of feet. Signs shall be 12 inches wide by 18 inches high and shall have black and
red letters and border on a white background. (UFC Section 901.4.5.(1) (2) & (3).
3. PAINTED CURBS: Fire apparatus roadway curbs shall be painted yellow and marked
"NO PARKING FIRE LANE" at each 25 feet. Lettering shall have a stroke of not less than
one inch wide by six inches high. (UFC Section 901.4.5.2)
4. The minimum fire flow requirement for your proposal is 1000 GPM @ 20 psi residual is
required. Provide a flow test using the enclosed form.
Please submit two copies of revised submittal documents and a letter indicating your response to
the above comments for review. Please call me at (503) 639 -4171 if you have any questions.
Sincerely,
Robert Poskin, CBO
SENIOR PLANS EXAMINER
Enclosure
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
LUNDMARK HOMES LLC
3381 COEUR D' ALENE DR.
WEST LINN, OR 97068
APRIL 9, 1998
CITY OF TI GRRD
ROBERT POSKIN
SENIOR PLANS EHAMINER
REFERENCE: LETTER DATED MARCH 26,1998. SITE PLAN
REVIEW 9275 SW LOCUST STREET.
SITE WORK
(1) DEAD END ROADS: SEE ATTACHED LETTER FROM FIRE
MARSHAL ADDRESSING THIS ISSUE.
f2) NO PARKING SIGNS: WE WILL INSTALL SUCH SIGNAGE
ON ONE SIDE AND IN THE TURN AROUND.
(3) PAINTED CURBS: NO CURBS BEING DONE.
(4) MINIMUM FIRE FLOW, HYDRANT. SEE ATTACHED LETTER
REGARDING TEST.
o
BERT LUNDMARK
LUNDMARK HOMES
(503) 655 -8004
. �
• 4p N V - JUN 14 199?
i � p I T UALA-TIN VALLEY FIRE -& RESCVE
FIRE PREVENTION •
4755 S.W. Griffith Drive . F.O. Box 4755 . Beaverton, OR 97076. (503) 526 -2469 . FAX 526 -2538
R � •
June 6, 1997
Sisul Engineering
375 Portland Avenue
Gladstone, Oregon 97027 -2450
• Re: Lundmark Partition
9275 S.W. Locust Street
File Number; 1158 -96
Gentlemen:
This is a Fire and Life Safety Plan Review and is based on the 1994 editions of the
Uniform Fire Code (UFC) and those sections of the Uniform Building Code (UBC) and
Uniform Mechanical Code (UMC) specifically referencing the fire department, and other
local ordinances and regulations.
Plans for the above noted project are conditionally approved subject to the following:
Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (15
feet for not more than two dwelling units), and an unobstructed vertical clearance of not
less than 13 feet 6 inches. (UFC Sec. 902.2.2.1)
Fire apparatus access roads shall be of an all- weather surface that is easily distinguishable
from the surrounding area and is capable of supporting not less than 12,500 pounds point
load (w heel .load).and.50,000 -paund,s..Iivc load -(p,,was,w.ehicie.weight). (UFC Sec:
902.2.2.2)
Where fire apparatus access roadways are not of sufficient width to accommodate parked
vehicles and maintain the minimum 20 foot wide unobstructed driving surface, "No
parking" signs shall be installed on one or both sides of the roadway and in turnarounds
as needed. (UFC Sec. 902.2.4). Signs shall read "NO PARKING - FIRE LANE - TOW
AWAY ZONE, ORS 98.810" and shall be installed with a clear space above ground level
of 7 feet. Signs shall be 12 inches wide by 18 inches high and shall have black or red
letters and border on a white background. (UFC Sec. 90I.4.5(1)(2) &(3)) Both sides of
private drive,
"Working" Smoke Detectors Save Lives
- u; Y.' ,;-.; =;s:�.. ,tT•1• •ror':- .aa-r
•
- $isu1- Engineering
Jiine 6, 1997
- - -- -Page 2-
The minimum available fire flow for single family dwellings and duplexes shall be 1,000
gallons per minute. If the structure(s) are 3,600 square feet or larger, the required fire
flow shall be determined according to UFC Appendix Table A- III -A -1. (UFC Appendix
III -A, Sec. 5)
Approved fire apparatus access roadways and fire fighting water supplies shall be
installed and operational prior to any other construction on the site or subdivision. (UFC
Sec. 8704)
If you have questions or need additional information, please contact me at 526 -2469
referring to the above noted file number.
Sincerely,
C /
✓71 -7' r 1 C]
• erry LI Renfro, DIPM
Plans Examiner
JLR:kw
cc: Mark Roberts
City of Tigard Planning
r. ..... ... .. ,. ... .. ..... ..... ... .....r r...... 1. ..... ... ....._ .._._. r( ....... .t „i, ...0 .... ..t•.. ...,•..• ...r .. .....n.. l[.AUY; \Y >•�yY,.
D/ a ii///tlll����lulll���� I,
May 24, 1997 i �
Y
CITY OF TIGARD
OREGON
Bert Lundmark
3381 Coeur D'Alene Drive
West Linn, Oregon 97068
RE: Plans Check Number: 05 -127R site work/plumbing
This letter is to confirm receipt of your building plans which have been routed to the plans
examiner.
As a reminder, the associated land use case(s) is /are: MLP96 -0014
Please be aware you are responsible for satisfying the conditions of the land use case(s)
and must submit plans directly to the appropriate staff person(s) indicated on your final
order.
Your building plans are not routed to the planning or engineering departments; you must
satisfy the land use permit conditions independent of the building permit plans review
process.
After the building plans review process has been completed, your building permit will •
not be issued without approval from the engineering and planning departments.
If you have any questions regarding this notice, please feel free to telephone me and I will
be happy to explain further.