Correspondence t 411 46 III„ 'I ITY OF TIGARD j OREGON October 23, 2003 SLX Architects Xavier Rueda 224 SW First Avenue Phone: (503) 224.0173 Portland, OR 97204 Fax: (503) 224.4836 RE: ELECTRICAL PLANS REVIEW Dear Mr. Rueda: Project Information Permit: ELC 2003 -00597 Tenant: Charles F Tigard Elementary School Address: 12850 S.W. Grant Ave. This plans review is based on the 2002 edition of the National Electrical Code (NEC). The plans and revisions received on October 16, 2003 for this project have been reviewed and are approved for construction subject to the following: 1. The approved plans including all schedules, calculations, specifications, and reports must be available at the job site for the field inspector at the time of inspection. 2. Changes to the approved plans shall be submitted and must be approved by the City before the installation covering the changes can be inspected If I can be of any additional assistance, please feel free to contact me at (503) 718 -2446. Sincerely Herb tabenow Plans Reviewer HS c: file 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 / CITY OF TIGARD t October 9, 2003 OREGON SLX Architects Xavier Rueda 224 SW First Avenue Phone: (503) 224.0173 Portland, OR 97204 Fax: (503) 224.4836 RE: ELECTRICAL PLANS REVIEW Dear Mr. Rueda: Project Information Permit: ELC 2003 -00597 Tenant: Metzger Elementary School 3 Sa S L / N6.0 A/ Address: ' 3 5—OEW 9 _. This plans review is based on the 2002 edition of the National Electrical Code (NEC). The plans received on September 19, 2003 for this project have been reviewed and are not approved as submitted . he following items shall be revised (revisions clouded) on the plans and addressed in a response letter. Two complete sets of the revised plans and the response letter shall be submitted to this office for review and approval prior to issuance of the electrical permit. Please note: Loose pages are not acceptable. The grounding diagram on Sheet E 4.0 does not indicate the footing rebar as a grounding electrode. It also is not shown in the Specifications 16060 Section 3.03 Installation. Article 250. 50 require it to be used "if available on the premises ". Rod electrodes are only permissible if these others are not available Please revise the documents accordingly If I can be of any additional assistance, please feel free to contact me at (503) 718 -2446. Sincerely, Herb Stabenow Plans Reviewer HS e 13125 §V 1 Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772