Correspondence t
411 46
III„
'I ITY OF TIGARD
j OREGON
October 23, 2003
SLX Architects
Xavier Rueda
224 SW First Avenue Phone: (503) 224.0173
Portland, OR 97204 Fax: (503) 224.4836
RE: ELECTRICAL PLANS REVIEW
Dear Mr. Rueda:
Project Information
Permit: ELC 2003 -00597
Tenant: Charles F Tigard Elementary School
Address: 12850 S.W. Grant Ave.
This plans review is based on the 2002 edition of the National Electrical Code (NEC).
The plans and revisions received on October 16, 2003 for this project have been reviewed and are
approved for construction subject to the following:
1. The approved plans including all schedules, calculations, specifications, and reports must be
available at the job site for the field inspector at the time of inspection.
2. Changes to the approved plans shall be submitted and must be approved by the City before the
installation covering the changes can be inspected
If I can be of any additional assistance, please feel free to contact me at (503) 718 -2446.
Sincerely
Herb tabenow
Plans Reviewer
HS
c: file
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
/ CITY OF TIGARD
t October 9, 2003 OREGON
SLX Architects
Xavier Rueda
224 SW First Avenue Phone: (503) 224.0173
Portland, OR 97204 Fax: (503) 224.4836
RE: ELECTRICAL PLANS REVIEW
Dear Mr. Rueda:
Project Information
Permit: ELC 2003 -00597
Tenant: Metzger Elementary School 3 Sa S L / N6.0 A/
Address: ' 3 5—OEW 9 _.
This plans review is based on the 2002 edition of the National Electrical Code (NEC).
The plans received on September 19, 2003 for this project have been reviewed and are not approved as
submitted . he following items shall be revised (revisions clouded) on the plans and addressed in a
response letter. Two complete sets of the revised plans and the response letter shall be submitted to
this office for review and approval prior to issuance of the electrical permit. Please note: Loose pages
are not acceptable.
The grounding diagram on Sheet E 4.0 does not indicate the footing rebar as a grounding electrode. It also is
not shown in the Specifications 16060 Section 3.03 Installation. Article 250. 50 require it to be used "if
available on the premises ". Rod electrodes are only permissible if these others are not available Please revise
the documents accordingly
If I can be of any additional assistance, please feel free to contact me at (503) 718 -2446.
Sincerely,
Herb Stabenow
Plans Reviewer