Correspondence May 18, 2004
CITY OF TIGARD
Jerry McCormick OREGON
Commercial Refrigeration
5920 NE Glisan
Portland, OR 97213
RE: REFRIGERATION FOR WALK -IN COOLER & FREEZER
Building Permit: MEC2004 -00249 Construction Type: II -1HR
Tenant Name: Metzger Occupancy Type: E -1
Address: 10350 SW Lincoln Street Occupant Load: NA
Area: Kitchen Stories: 2
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99-
01) 1999 edition. The submitted plans are approved subject to the following.
• Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
• Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
• Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
• Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
• Guards shall be provided where appliances are located within 10 feet of the roof edge
or open side of a walking surface and such edge or open side is located more than 30
inches above the floor, roof or grade below. The guard shall be 42 inches above the
elevated surface with an intermediate rail so as not to allow the passage of a sphere,
A 21 inches in diameter. 304.9
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC