Correspondence • 1n st ry CoM June 25, 1998 City Of Tigard 13125 SW Hall Blvd Tigard Oregon 97223 Attn: Robert Poskin Re: Thayer Co. Mechanical Plan Review 73 y2, SW Kable Lane PC #: 04 -107c MEC #: 98 -0141 Dear Robert, The following information is provide in response to your Mechanical Plan Review letter dated May 20, 1998: 1. Attached plans are the structural plans for this installation as provided by TM Rippey (Brent 244 -0266) 2. Exhaust system for the restrooms is connected to the lighting system. No make -up air units to be installed on this project. 3. New units are split system heat pumps. Outside air is provided to these units to meet fresh air requirements for occupancy. 4. Each unit shall be properly marked with the unit number and complete address for the space the units are serving. Power disconnects to be provided at indoor and outdoor units, with service receptacles within 25'. 5. Smoke detectors with automatic shut -off to be provided with both new units. Detectors to be tied into existing fire detection/alarm system. If you have any questions or require any additional information, please do not hesitate to call. Sincerely, McKinstry Co. C y : ] 01;&3 ,-t■ Dan Osborne Project Manager 5400 N.E. Columbia Blvd. • Portland, OR 97218 • (503) 331 -0234 MCKIN* *372ND • CCB #40981 CITY OF TIGARD May 20, 1998 OREGON McKinstry Co. 5400 NE Columbia Blvd. Portland, OR 97218 RE: Thayer Co. Mechanical Plan Review 73y2_--7344W Kahle Lane PC #: 04 -107c MEC#: 98 -0141 Submittal documents for the above referenced project have been reviewed for conformance with the applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The following comments are noted: IIA ^.,i. _ +a.-.s 'tr s�'m.Y"� -a' .s ...ri�s���� .. _ ....... ' �.M+��.il' a4 L. i.�Yl • .�. . 1. The attachment of permanent equipment (HVAC) supported by the building's structural components shall be designed to resist the total design seismic forces prescribed in Section 1603.2 of the Structural Specialty Code. Provide an engineer's design specifying attachment requirements [OSSC, Section 106.3.2 and OMSC, Section 304.4). 2. The exhaust and makeup air systems shall be interconnected by an electrical interlocking switch [OMSC, Section 402.4]. 3. Where required by OSSC, Section 1202.2 natural ventilation or a mechanically operated ventilation system capable of supplying occupancy air in accordance with OSSC, Table 12 -A shall be provided. When proposing to use the economizer of the HVAC system with the outside air damper set to stay partially opened to provide occupancy ventilation, the designer shall: A. Document within the construction plans the anticipated occupancy load for the design of the occupancy ventilation system and, B. Provide detail of the modification to the HVAC economizer that will prevent the Building operator from adjusting the air damper to a fully closed position at any time and, 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 4 • Thayer Co. Mechanical Plan Review PC #: 04 -107c BUP#: 98 -0141 Page #2 C. Provide design specifications for the additional energy requirements resulting from the air damper being partially open during the heating cycle and, D. Specify on the plans that the system shall operate during such times the building or space is occupied. 1. Provide outside air specifications on revised plans. 4. Each individual roof - mounted HVAC shall be permanently labeled as to the areas it serves [OMSC, Section 305.5]. In addition, each unit shall be equipped with a power disconnect. A 120 -volt receptacle shall be located within 25' of each unit [OMSC, Section 309.1]. 5. Air moving systems (combination of units),. supplying air in access of 2000 CFM to enclosed spaces, shall be equipped with an automatic shut -off. The smoke detectors shall be supervised when a fire detection or alarm system is provided [OMSC, Section 608]. Please submit two copies of revised submittal documents and a letter indicating your response to the above comments for review. Please call me at (503) 639 -4171 if you have any questions. Sincerely, Ro rt Poskin, CBO SEN. R PLANS EXAMINER tWwwdo o.s.w�_a.neewnmer. •