Loading...
Correspondence City of Tigard, Oregon 0 13125 SW Hall Blvd. 0 Tigard, OR 97223£° April 25, 2008 ` { RE: TENANT IMPROVEMENT i Project Information waftgirft Building Permit: BUP2008 -00047 Construction Type: 2 -B Address: 9009 SW Hall BIvd.3ti Occupancy Type: M /S2 Area: 74,600 Sq. Ft. Stories: 3 Name: Macy's Furniture Sprinklers: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below. 1) Suspended ceiling to be installed as per ASCE 7 or Oregon State Interpretation. • 2) All improvements made to the building shall be inspected prior to covering. 3) Make approved set of plans available for all inspections. 4) A total of 25% of the cost of the project shall go towards removing architectural barriers (accessibility). 5) All framing shall conform to accepted engineering standards. FIRE LIFE AND SAFETY / GENERAL The main exterior door or doors are permitted to be equipped with key- operated locking devices from the egress side provided: 1. The locking device is readily distinguishable as locked, 2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. Sec. 1008.1.8.3 All exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. Sec. 1008.1.8 Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Sec. 1011.1 Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 1 /2 hours of illumination in case of primary power loss. Sec. 1006.3 FYI Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied. The means of egress illumination shall be provided with a second source of power in case of primary power loss. Amended Construction Documents: Work shall be installed in accordance with the approved construction documents, and any changes made during construction that are Phone: 503.639.4171 0 Fax: 503.684.7297 0 www.tigard- or.gov 0 TTY Relay: 503.684.2772 not in compliance with the approved construction documents shall be resubmitted for approval as an amended set of construction documents. OSSC 106.4 Work Commencing Before Permit Issuance: Any person who commences any work on a building or structure before obtaining the necessary permits shall be subject to an investigation fee equal to the permit fee that shall be in addition to the required permit fees. OSSC 108.4 Inspections: Construction or work for which a permit is required shall be subject to inspection by the building official and such construction or work shall remain accessible and exposed for inspection purposes until approved. Approval as a result of an inspection shall not be construed to be an approval of a violation of the provisions of this code or of other laws or ordinances of the jurisdiction. Inspections presuming to give authority to violate or cancel the provisions of this code or of other laws or ordinances of the jurisdiction shall not be valid. OSSC 109.1 Approval Required: Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the building official. The building official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or his or her agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the building official. OSSC 109.6 Use and Occupancy: No building or structure shall be used or occupied, and no change in the existing character, use or occupancy classification of a building or structure or portion thereof shall be made until the building official has issued a certificate of occupancy for such change in character, use or occupancy, therefore, as provided herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. OSSC 110.1 American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property Submitting revised drawings or additional information, please attach a copy of the City of Tigard, Letter of Transmittal found on the city web site under forms. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Res ectfully, L&9 Dan Nelson Senior Plans Examiner (503) 718 -2436 dann @tigard - or.gov • City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 • April 21, 2008 II 1111 IN • i g " -N', RE: TENANT IMPROVEMENT ='C ?' Z -ARD Project Information Building Permit: BUP2008 -00047 Construction Type: 2 -B Address: 9009 SW Hall Blvd. Occupancy Type: M /S2 Area: 74,600 Sq. Ft. Stories: 3 Name: Macy's Furniture Sprinklers: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below: 1) Please show details and listings for 1 Hour Stair Tower. 2) Please show one hour enclosure at 2 floor stair tower. 3) Please provide page A5.1 for both sets of plans. When responding, provide an itemized letter stating in what way each numbered issue has been addressed in the revision. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectful) , o f Dan Nelson Senior Plans Examiner (503) 718 -2436 dann @tigard - or.gov Phone: 503.639.4171 • Fax: 503.684.7297 , • www.tigard - or.gov • TTY Relay: 503.684.2772 City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 April 9, 2008 tl RE: TENANT IMPROVEMENT ;.'R A ° R °D�' Project Information Building Permit: BUP2008 -00047 Construction Type: 2 -B Address: 9009 SW Hall Blvd. Occupancy Type: M /S2 Area: 74,600 Sq. Ft. Stories: 3 Name: Macy's Furniture Sprinklers: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below. 1) Please show accessible exits or how this will be accomplished. 2) Please show details and listings for 2 Hour Stair Tower. 3) Show emergency egress lighting on plans. 4) Provide the following information on the building data code summary; number of exits provided and width of exits provided. 5) Please provide information required by structural plan review. When responding, provide an itemized letter stating in what way each numbered issue has been addressed in the revision. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Dan Nelson Senior Plans Examiner (503) 718 -2436 dann @tigard- or.gov Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 eya o?Uar ozy0t WILLIAM POLK ASSOCIATES PLANNING ARCIRTEC RECEIVED RJRE LNTERIORS APR 2 2 ?008 C'Tl' Q;; C: G P +F?D BLLL1INO Memorandum DATE: April 21, 2008 TO: Dan Nelson PROJECT: Macy's Furniture Gallery JOB NO: MMD2008 -00005 FROM: Michael Stapleton RE: Stair Wall Assemblies CC: Remarks: The stair well walls in question are existing walls. I researched the old Lamont's drawings and they show them being 6" metal studs with 5/8" GWB both sides. I believe this will conform to the UL design listing No. U419. I hope this meets with your satisfaction. If not please let me know. Thank you, Michael Stapleton 911 WESTERN AVENUE, SUITE 565, SEATTLE, WASHINGTON 98104 (206) 622 -8443 FAX (206) 622 -8031 GSST.R180 - Freight Elevator Type Fire Doors Page 1 of 2 • UL Online Certifications Directory GSST.R180 Freight Elevator Type Fire Doors Freight Elevator Type Fire Doors THE PEELLE CO R180 #311 373 NESCONSET HWY HAUPPAUGE, NY 11788 USA Counter balanced type. May be provided in non - masonry walls. on 1996 -07 -03 The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow -Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow -Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non - misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2008 Underwriters Laboratories Inc. ®" file: / /C:\Documents and Settings \dann\Local Settings \Temporary Internet Files \Content.Ou... 4/24/2008 . . . . . . . , . . , ... ... _ . . . . ., . . , , ., ., , _ . . . . ... .. , .....„ ,-, ...- . . , . . .. .. . , . ,. , .. . . , , .. . , . .. . . .. ... . „ . . . . .. ' . , , ... . ... 2002 FIRE RESISTANCE DIRECTORY FIRE DOORS (GSNV) FIRE DOORS {GSNV) 2853 , ,. .. Curtain Type Fire Doors (6SQX)--Colitinued Dumbwaiter Type Fire Doors (GSRV)--Continueri RUSKIN MFG DIV OF TOMKINS INDUSTRIES INC ., R7618 D A MATOT INC _ R6748 3900 DR GREAVES RD, GRANDVIEW MO 64030 2501 W VAN BUREN, BELLWOOD IL 60104 Max Size Dumbwaiter doors may be provided for installation in non-masonry walls. bi. Curtain l'ype Assembly of , . .= Individual Oasis Individual Doors ". -;:,„ Width Height Width Height DALDOSS ELEVETRONIC SF A ' R9852 - - 7. : ,., , 36 36 — — WALE VERONA N 190 PO BOX 410, 38100 TRENTO ITALY 30 30 60+ 60+ Dumbwaiter doors may be provided for installation in non-masonry walls. 24 24 48 48++ . . , 16 .,,, ,.., :',,' 36 36 74 74+++ 47 48 95 KAFKA MFG CO It7879 4S++++ .:C .. ''-:'': +Made up from indivkival doors not exceeding 30 in. in width and 30 in. in 7600 INDUSTRIAL DR, FOREST PARR IL 60130 , ' i, „ -.- t height. Dumbwaiter type fire doors may be installed in masonry or drywall for -F-Rvlade up from individual doors not exceeding 24 by 24 in. . UP to 1 e / 2 11 ..rating. 4M . , . , i ntended .. Swing fire door and frame assembly ntended tor 1-1/2 '-++ t il u ilsadenpl) from individual inindiaal doors not not ceed liTig 36 36 36 36 . hr 1 i 0 titiorisiti sizes ddt td exceed 35 ( 914 . 4 trim) id width and height. May '' , .., be installed n masonry or drywall. :,f* '•'• i 14 4, ■■ 7,1, ' TFIE PEELLE CO R2071 . . VENT PRODUCTS CO INC 1t10974 34 CENTR4I AVE,I1AUPPAUGE NY 11788 1901 S KILBOURN AVE, CHICAGO IL 60623 Dumbwaiter doors may be provided for installation in non-masonry walls. .4„ ,,,Ti. "':,..: Max Size In. . . curtain TypeAndividud Type Model Freight Elevator Clad Type Fire Doors (GSST) Width Height 60 48 1 , This category covers freight elevator fire doors of the single-swing or 24 60 counterbalanced type. The doors consist of either form steel-sheets, 2 • 49 3 hollow-metal; or metal covered wood units. The counterbalanced 000r assembly includes the door panels, frame (optional), guides, latching device, and counterbalance mechanism. Each door or door assembly bears a "Freight Elevator Fire Door" Classifi- cation Marking with one of the following ratings: 1-1/2 HR, Temp Rise — WARD INDUSTRIES INC R16481 30 Min — 250 or 650 F Max or 1-1/2 HR with no reference to temperature 111 RIVERVIEW DR, MONESSEN PA 15062 - rise. The Classification Marking covers the design and construction of the Max Size door or door assembly , INSTALLATION: Curtain Type TYPe Freight elevator: doomare intended to be installed in concrete and Individual Doors Height irtaaburY vialikiurdess edierwise noted in the indiVidual Claskfieations. 49 0 ,,,,„,„ For Statidardtitart the installation of hoist way doors for elevators, see '"--' 48 105 Series NFPA 80 and ANSI/ASME A17.1 - "Safety Code For Elevators and Escala- 60 Sin Counter steel, hollow-metal, and metal'dad, freight elevator ripe doors are Classified for openings not exceeding 13 ft 6 in. In width and 12 ft , . n in height in masonry nor 10 ft 10 in. in width and 10 ft 6 in. in height i Dumbwaiter Type Fire Doors (GSRV) non-masonry walls. Single-swing freight elevator &oft are Classified for openings not exceed- This category covers dumbwaiter type frame and fire door assemblies. ' 64 ft wide -arid ft high in masonry or non-rnasonty walls. bwaiter doors are of counterbalanced and swinging types of the Rush In ,--, . => ',,.*1.• „ .„ ..ig of formed steel and included wall guides, frame, Tatching, and coon- D oor rratnes* *. . ring mechanisms. fi t ,, .. S • .' * ,;, 4° . ' t elevator doOrs are to be installed in Listed door di door assembly bears a "Dumbwaiter Frame and Fire Door Assem- frames fn' - .' - 'de t :pr indi Counte .ors May be inStalled in concrete Classification Marking with one of the following ratings. 1-1/2 R alanced type freight *vator do ii , :iii ; ;;,., •. Rise —30 Min — 250 F Max; 1-1/2 HR Temp Rise —30 Min — 650 F and masonry wa0s without a fralideCoiniter-balanced type freight elevator or 1-1 HR, 1 HR, or 3/4 HR with no reference to temperature rise, doors shall be instaliedirt non-minor * walls and'inay be installed in con- 'Classification Marking on all these doors covers the design and con- crete or masonry Walls with the frame supplied with the dborassembly or dian of the door, frame, and hardware. , in a Listed frame ataindie indicated in th (fidtvidual frame classifications. When s ' ALLAT1ON: a frame is used With countertiattliced dOisra, it is to be installed in accor- Vrtf' 0 standards on the installation of hoist way doors see NFPA 80 and dance with the install .. ,atkin histru ctibtr with each door assembly ,::';',". .! ASME A17.1 - "Safety Code For Elevators And Escalators", - tol ro ,v, the h: rram„ indicated„. (c ', 0 , ). Glazing Panels: bwaiter doors are Classified for openings not exceeding 49 in. in G . . and 90 in. in height- eirleseThe door ma t b e:pose prov d id arei ed IY ,Sladtgdmoeastenriptale'tx"eeetclid pan- .'" bwaiter doors are intended to be installed in concrete and masonry - . , II unless otherwise noted in the individual Classifications, so in. with neither dimentabn exceed** ut. - - is?......; ..0,i # bwaiter doors intended to be installed in non-masonry walls must be For additional information and CI:assif:t.cation Marking see Fire Doors, .. in accordance with the installation instructions provided with each (GSNV). The basic standard used to investigate pmducts in this category is IlL100, -,,:!, .ly to provide the protection indicated. .... „ "Fire Tests of Door Assemblies". ::4; Panels. '',, , ,."3'• bwaiter doors may be provided with Classified glazing material „, ,. 'ithts not exceeding 3 m. diameter per opening. COMPREHENSIVE MFG SERVICES L L C, DRA COIJRION R1344 ' '''' , ■ 9' i'aitional information and Classification Marking see Fire Doors 3044 LAMSON AVE, ST LOUIS MO 63115 ' ' Counter-balanced type. May be „provided for installation in non-masonry basic standard used to investigate products in this category is 1.11.10B, walls. Tests of Door Assemblies", DUPONT METAL MFG CO INC R10312 ! -€. I - - ,fi x Bt ' � f a ^ �4.,, d s o- 4 . • W ;� 4 2002 FIRE RESISTANCE DIRECTORY 2854 FIRE DOORS (GSNV) FIRE DOORS (GSNV) Freight Elevator Clad Type Fire Doors (GSST)— Continued Passenger Elevator Type Fire Doors (GSUX)— Continued EMS GROUP INC R13149 BRIO- SOUTHERN INC R814 5410 EUCLID, ST LOUIS MO 63115 7811 W 2ND CT, HIALEAH FL 33014 INTERNATIONAL ELEVATOR CO INC R14471 CEITA S R L R137f BOX 1108 3015 N SUMMIT, ARKANSAS CITY KS 67005 VIA FRATELLI BANDIBERA 12, 20016 PERO - MILANO ITALY Counterbalanced type. May be provided for installation in non-masonry walls. CMF CORP R188( MITSUBISHI ELECTRIC CORP R9506 1945 W 12TH AVE, DENVER CO 80204 2 -2 -3 MARUNOUCHI CHIYODA -KU, TOKYO 100 -8310 JAPAN Passenger elevator type fire doors. THE PEELLE CO R180 COLUMBIA ELEVATOR PRODUCTS CO INC R75` 34 CENTRAL AVE, HAUPPAUGE NY 11788 175 N MAIN ST, PORT CHESTER NY 10573 Counter balanced type. May be provided in non - masonry walls. Passenger .,Elevator F are Doors (GSUX) CONCORD ELEVATOR L NC R1071 Type } 107 ALFRED KIIEHNE BLVD, BRAMPTON ON CANADA L6T This category covers passenger elevator fire doors of the single -swing or , sliding hollow -metal type. The sliding door panels may be used in single slide a s semblies of the one, two, or three speed type, or they, may be used CONTINENTAL ELEVATOR CABS & ENTRANCES INC 8115! in center parting assemblies of the one or two speed type. Each door panel bears a "Passenger Elevator Fire Door" Classification 6089 6089 TAYLOR RD, NAPLES FL 33942 Mark with the following rating. 1 -1/2 h with temperature rise - 30 min - 650 F max, 1 -1/2 h, 1 h or 3/4 h with no reference to temperature rise. The CUSTOM CABS INDUSTRIES R69, Classification Mark covers the design and construction of the door or door SUITE D 7603 ST ANDREWS AVE, SAN DIEGO CA 92154 panels only. INSTALLATION DOVER ELEVATOR SYSTEMS INC R61 For standards on the installation of hoist way doors for elevators, see NFPA 80 and ANSI / ASME A17.1, "Safety Code for Elevators, Dumbwaiters PO BOX 2177, MEMPHIS TN 38101 and Escalators." Elevator Door Hardware DURATEC ENTERPRISES INC R163 The sliding door panels are intended to be installed with Listed hardware 1584 93RD LN NE, BLAINE MN 55449 consisting of hangers, track, header, sill, closer, and retaining clips (as indi- cated in the individual hardware Listing). See Passenger Elevator Door EL EVA A Hardware (GZKZ). ELEVADORES OTIS S A DE C V R125 The swinging door panels are intended to be installed with sill, hinges, CALLE ABEDULES NO 75 COL SANTA MARIA INSRGENTES, Listed frame, Listed latching device and Listed closing device. For Listed. 06430 MEXICO DF MEXICO frames, latching devices and dosing devices, see Door and Window Frames (GVTV), Single-Point Locks or Latches (GYJT) and Swinging Door Closers ELEVATOR DOORS INC R69 (GVEV). Doors should be provided with hinges or pivots in accordance with NFPA 80. 15 JANE ST, PATERSON NJ 07522 SIZES Sliding passenger elevator Fire doors are Classified for openings not . EMERSON ENGINEERING CO INC R59 exceeding 8 ft wide and 10 ft high. 2719 N EMERSON AVE, INDIANAPOLIS IN 46218 Single-swing passenger elevator Fire doors are Classified for openings not exceeding 4 ft wide and 8 ft high FUJITEC INC R92 provided with PANELS 401 FUJITEC DR, LEBANON ON 4 Sliding doors may be provided with visit �Zanels, Single -swing doors are intended to be provided with vision panels. R9E The vision panel should be of Classified glazing material. The area* ,a FUJITEC CO LTD single vision panel should be not less. than 25 so in. and the total area - 28-10 SMOTE `1 -CHORE IBARAKI, OSAKA 567 -8510 JAPAN one or more vision panels should not be more than 80 sib in, Each vision : panel should reject a 6 in. diameter bail,. S f GLOBAL ELEVATOR MFG CO INC R6f DOOR Passenger elevator fire doors used in dryawatl shaft construction are 605 RENNIE ST, HAMILTON ON CANADA 1,814 3P8 intended to be installed in Listed door frames to provide the protection P" indicated. When acceptable to the Authority Havmo jurisdiction, Classified GUNDERLIN LTD R14i 'r Passenger Elevator Fire Doors may be installed with Listed Passenger Eleva- 3625 E 11TH AVE, HIALEAH FL 33013 ' for Door Hardware, in an oversize Passenger Elevator Fire Door Frame i assembly furnished with a Certificate of Inspection. See Door and Window HAUINSTEIN & BURMEISTER INC R6! Frames (GVTV); ; INTERLOCKS 2629 - 30TH AVE 5, MINNEAPOLIS MN 55406 See Elevator Door Locking Devices and Contacts (FQXZ). , ADDITIONAL INFOR 4ATTON t , INDEPENDENT STEEL PRODUCTS L L C R11: For additional information and Classifcatio �Vlark, see Fire Doors 55 ENGINEERS IN FARIOIGDALE NY 11735 (GSNV). REQUIREMENTS INTERNACIONAL DE ELEVADORES S A DE C V R111 The basic standard used to investigate products in this category is 17[.108, "Fire Tests of Door Assemblies." KM 20.6 CARRF.TF.RA LIBRE TIJUANA - ROSARITA, ROSARITO BC MEXICO ACME STEEL DOOR CORP R11389 513 PORTER AVE, BROOKLYN NY 11222 LC OTIS ELEVATOR CO R15: I ASCENSEURS THYSSEN MONTENAY INC 811638 515 KOREA DONG CHANGWON -SHI, KYUNG NAM 641 - 10015 AVE BRUXELLES, MONTREAL QC CANADA H1H 4R1 BAY STATE ELEVATOR CO INC R7 LONG ELEVATOR & MACHINE CO INC Rili Pfl RnY 71 SPRTNT:PTW1.I) IL 627115