Plans RECEIVED
MAY 0 4 2015
CITY OF TIGAFID
�.. • .. BUILDING DIVISION
ti 72" Range 48" 14"
(� ` 1 : Salamander Broiler Fryer 12.5
'� "
0 Of y i 73 ii 8 Type I Hood
®'a •s's 1 \k0 0 0 0 O 11111111111111 —
a � o 0 - OHO 0 0 0 -
—
CCf Q 3 - L ° Q I
�� �z m � Ansul O O O 8.5'
> f i '0�' O O O Type I Hood
. c Er a .
a c ° ¢ -� System
Q v u° a u Cylinders o
& Controls.
36" 36"
Griddle Range
C UWE Crw?yy' V
A Y
1 �A
Fire System Drawing
Overhead View Ansul wet chemical fire system
Model R- 102. 3— 3 gallon cylinders.
Flow point capacity: 33:
Flow points used: -27-
b
BY: Guardian Fire Prot. Inc. FOR: Bajio Notes: System installed in accordance with
1012 SW "A" ST. 9009 SW Hall Ansul Design, Installation, Recharge,
Corvallis OR 97333 Tigard OR 97223 and Maintenance Manual.
• (541) 752-2258 System tested in accordance with
CCB# 100355 exp. 6 -23 -06 Scale: None U.L. Standard # 300.
This drawing may not be reproduced without written permission from Date: 4-05 Drawn By: MAF
Guardian Fire Protection Inc. City, state, county agencies
are excepted during the course of plan review or permit process.
Duct: 10" x15"
Fusible
2W Links
8 8.5' Type I Hood
460 0
Ansul a- 1N
1F 1F 1F
Cheesemelter 40" 40" 40"
2120 48" 48" 48"
10"
20"
� 1 17 n
36" Griddle 36" Range Steamer
Fire System Drawing
Front View
Small Hood
BY: Guardian Fire Prot. Inc. FOR: Bajio Notes: System installed in accordance with
1012 SW "A" ST. 9009 SW Hall Ansul Design, Installation, Recharge,
Corvallis OR 97333 Tigard OR 97223 and Maintenance Manual.
(541) 752— 2258 System tested in accordance with
CCB# 100355 exp. 6 -23 -06 Scale: None U.L. Standard # 300,
This drawing may not be reproduced without written permission from Date: 4-05 Drawn By: MAF
Guardian Fire Protection Inc. City, state, county agencies
are excepted during the course of plan review or permit process.
I
Ducts : Automatic tic gas
10" x 18" shut off valve.
• ii ____---
2W Fusible 2W
Links
12.5' Type I Hood 8 / 8
Aso ago 450 E 811E _ I
II II IIII I I
II II IIII I I
1A Q 1A iN� iN L -" JI` L _I
9 iN 1N Salamander Flow pts. used:
230 27" 15" 15" 60" a 15" 9 11 8
47' 40" 40" Pta 9 Back
290 290 290 290 Hood
15" is" 15" 15" O
20" 20" 20" 20"
Remote
Manual
Actuator
IIIIIIIIIIIII1 (in egress)
nI 4, In ni In
14" 48" 72" Range
Fryer Radiant
Broiler
Fire System Drawing ,
Front View
Large Hood
BY: Guardian Fire Prot. Inc. FOR: Bajio Notes: System installed in accordance with
1012 SW "A" ST. 9009 SW Hall Ansul Design, Installation, Recharge,
Corvallis OR 97333 Tigard OR 97223 and Maintenance Manual.
(541) 752-2258 System tested in accordance with
CCB# 100355 exp. 6 -23 -06 Scale: None U.L. Standard # 300.
This drawing may not be reproduced without written permission from Date: 4-05 Drawn By: IMF
Guardian Fire Protection Inc. City, state, county agencies
are excepted during the course of plan review or permit process.
so..Liizuuo io:o_t rA.A 002
• •
SECTION IV - SYSTEM DESIGN i , °
UL EX. 3470 ULC CEx747 Page 4-49
10 -1 -02 REV.2
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Distribution Piping Requirements - 9.0 Gallon System t 17p
► This optional configuration consists only of three 3 -gallon tanks, all
• pressurized from a single double -tank nitrogen cartridge with
R. • expellant gas hoses connected as shown in Figure 88. Tanks No.
1 and No. 2 must be connected directly to the regulator with sepa- � -} 1
rate expellant gas hoses and Tank No. 3 must be connected to
. Tank No. 2 with a third expellant gas hose as shown in Figure 88.
Each tank must be connected to an independent distribution pip- f
• ing network as shown in Figure 88. Distribution piping require - 1 -
ments for each network must be as follows: ,
1. The maximum length between the start of the first branch line _
and the start of the last branch line must not exceed 24 ft.� -" ��'
(7.3 m . When the supply �.p
( ) pply fine is split, the co mbined total of
both legs of the supply line (from the start of the first branch
line to the start of the last branch line) must not exceed 24 ft. f I I I
• (7.3 m). See Figure 84. u I I 1
2. The total length of all branch lines must not exceed 36 it. 3.0 i 3.0 i 3.0 r
• (10.9 m). See Figure 84. GALLON GALLON a GALLON
TANK TANK 1 TANK lb •
3. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. NO.3 NO.2 F. NO.1
supply line.
4. A maximum of two nozzles are allowed per duct branch line_ 1
5. When using this 9.0 gallon system configuration, no mani-
folding of distribution piping is allowed. Two TANK ENCLOSURE 3 GALLON REGULATED DOUBLE TANK arsooEN
ASSEMBLY ART NO. RE EASE ASSEMBLY, CARTRIDGE OR
6. When an ANSUL AUTOMAN Regulated Release is utilized in 419604 (INCLUDES (2) OR 3 GALLON LTA - 101 -30 CARTRIDGE
this configuration, additional regulator actuators cannot be S'1
M Er RE 'c ED ACTUATOR (REGULATED ACTUATOR
used.
• 7. Only 3 gallon tanks can be utilized in this configuration. FIGURE 88
I 8. The requirements of the following table must not be exceeded aOaa,
•�" • for each 3 gallon tank:
ReQtNrements Duct Plenum Appliance
SuoDly Line Branch Line Branch Line branch Line
Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in.
Maximum Length 40 ft. 8 ft. 4 ft. 12 ft.
(12.2 m) (2.4 m) (1.2 m) (3.7 m)
Maximum Rise 6 ft. 4 ft 2 ft. 2 ft.
(1.8 m) (1.2 m) (.6 m) (.6 m)
Maximum 90° 9 4 4 6
Elbows
Maximum Tees 1 2 2 4
Maximum Flow 11• 4 2 4
Numbers
'Exceptions:
1. Twelve (12) lbw numbers are allowed in any lank not containing Iwo -flow appliance nozzles. and/or, a 1N nozzle for wok or griddle protection. and /or. a IF nozzle for range protec-
tion, and/or, a 3N nozzle for fryer protection.
2 Twelve (12) flow numbers are allowed with any one lank using only Iwo -flow appliance nozzles
r 3. Twelve (12) flow numbers are allowed with any one tank using only three -flow appliance nozzles
Special Instructions:
r 1. When four (4) Dean Indus:nes GTI Gas Fryers are
N protected at {ow proximity as shown in Figure 58 on Page 4-32. the as.. large piping must be as shown n Figure 59 on
Page 4 -32.
2. For certain McOonald•s spplicdtions, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle. ne (1) 1/2N eladrostalic preopnlalor nozzle,
one (1) 1N plenum nozzle, and four (4) iwo •flaw appliance noales. Contact Amur Applications Engineering Department Ic additional Information.
uoiii /zuuo 1D:Di FAA 16 00 3
. SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -40
REV. 2 10 -1-02
TANK AND CARTRIDGE REQUIREMENTS ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS
Once the hazard analysis is completed and the total nozzle flow This section contains the guidelines for installing the actuation and
numbers are established, the quantity and size of agent tanks and expellant gas lines between the regulated release mechanism reg-
cartridges needed to supply the nozzles with the proper volumes ulator, each regulated actuator regulator, and each agent tank.
of agent at the proper flow rates can be determined. For cartridges These limitations should be considered when selecting the corn -
used in the regulated release mechanism, flow capacities, tank ponent mounting locations.
quantities and sizes, and regulated release cartridge options are
given in the table below. Actuation Gas Line — 6 to r Tanks Maximum
Total Quantity and Regulated Release ' 8 Tank maximum retlecIS the utifimtion or 3 tank regulated actuators.
Flow Size of Cartridge Options 1. Use only 1/4 in. Schedule 40 black iron, hot - dipped galva-
Numbers* Tank(s) plitrooerl Carbon Dioxide nized, chrome - plated, or stainless steel pipe and fittings.
1 — 5 (1) 1.5 Gallon LT -20 -R 101 -10 2. The actuation gas line piping is installed from the regulated
6 — 11 (1) 3.0 Gallon LT 30 R 101_20 release mechanism to each regulated actuator connected
11 — 16 (1) 1.5 Gallon Double within the system. The total length of the actuation gas line
101 -30 from the r
(1) 3.0 Gallon egulated release assembly to the regulated actuator
• assembly(ies) must not exceed - 20 ft. (6 m) when using an
16 — 22 (2) 3.0 Gallon Double 101 -30 ** • LT-20-R, an LT 30-R nitrogen cartridge, or a 101 -10 or a 101 -
20
When one or more regulated actuators are used, the following • carbon dioxide cartridge. See Figure 71.
tank and cartridge combinations apply for each regulated actuator:
Regulated Actuator Regulated Actuator
Tank(s) Cartridge
(1) 1.5 Gallon LT20 -R or 101 -10
(1) 3.0 Gallon LT -30 -R or 101 -20
(1) 1.5 Gallon and LTA- 101 -30 or 101 -30** or
(1) 3.0 Gallon double tank
(2) 3.0 Gallon LT-A -101 -30 or 101 -30" or
double tank
• For a c ons to rrarmum flow numbers, see Distribution
Ion Piping Recements for 1.5 gat.
Salon systems in this Section.
�� • " The 101-30 cartridge can net be used when (21 two 3.0 gallon tanks are manifokied together. )
For higher total flow numbers (23 to 110), multiple cartridges and
regulated actuators are required as shown in the System Selection
Guide in Section IX — Appendix.
REGULATED ACTUATOR ASSEMBLY
EXPELLANT GAS LINES
NOT INCLUDED IN ACTUATION
GAS LINE LENGTH TOTALS
REGULATED
.. o ll
ACTUATOR
ACTUATION GAS LINE WITH AN LT -20-R. ASSF
LT -30.R, 101.10 OR 101.20 CARTRIDGE
MAXIMUM LENGTH OF 20 FT. (6 m),
MAXIMUM NO. OF FITTINGS 9 !
REGULATED
ASSEMBLY �,
'ANSUL AUTOMAIr REGULATED RELEASE ASSEMBLY IL
�:/
i
il
• FIGURE 71 •
ors
05/09/2005 16:01 PAS 410ul
Guardian Fire Protection Inc.
1012 SW 'A' Street
Corvallis, OR 97333
541.752.2258
Fax: 541.752.4259
Attention:
Company Name:
Date: — 7_ 6),
Time: 3 5e p `�
Fax Number. SD •- 6)7 - G ,
Number of pages:
(including cover)
v/IC �, c
Regarding:
From:
Notes:
-4 PI c4
fa - ice
Ci C31 5. (..e4
1-04
05/09/2005 16:01 FAX 4 002
•
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -28
REV. 3 10 -1 -02
low.,.
Nozzle Application Chart
The following chart has been developed to assist in calculating the
quantity and type of nozzle required to protect each duct, plenum,
or appliance.
NOTICE
This chart is for general reference only. See
complete details for each type of hazard.
. Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping -
Hazard Dimensions Quantity Heights Part No._ Flow No.
Duct or Transition Length - Unlimited 1 - 430912 1100
(Single Nozzle) Perimeter- 50 in. (127 cm)
Diameter - 16 in. (40.6 cm)
■ Duct or Transition Length - Unlimited 1 - 419337 2W
(Single Nozzle) Perimeter - 100 in. (254 cm)
Diameter - 31 718 in. (81 cm)
■ Duct or Transition Length - Unlimited 2 - 419337 2W
(Dual Nozzle) Perimeter - 150 in. (381 cm)
Diameter - 48 in. (122 cm)
Electrostatic Precipitator Individual Cell 1 - 419334 1/2N
(At Base of Duct)
► Plenum Length - 10 ft. (3.1 m) 1 - 419335 1N
(Horizontal Protection) .
.Plenum Length - 6 ft (1.8 m) 1 - 430192 1100
I (Horizontal Protection) Width -4 ti (1.2 m} 1 419336 1W
Plenum Length - 4 ft. (1.2 m) 1 - 419336 1W
► (Vertical Protection) Width -41 (1.2 m)
•
Fryer /Split Vat Fryer" Maximum Size
(without drip board)
15 in. (38 cm) x
14 in. (36 —High Proximity 1 27 - 47 in. 419339 230"'' re f.Z
Medium Proximity 1 20 - 27 in. 419340 245
Maximum Size ,
(without drip board)
•
19 1/2 in. (49.5 cm) x
19 in. (48.2 cm)
High Proximity 1 21 - 34 in. 419338 3N
Low Proximity 1 13 - 16 in. 419342 29
Maximum Size
(without drip board)
18 in. (45.7 cm)
x 18 in. (45.7 cm)
High Proximity 1 25 - 35 in. 419338 3N
(64-89 cm)
♦.._ •- For nwniple nozzle proiechon of stngle fryers. see delaitod lnSorrnauon on Pages 4 -12 through 4 -14
•
1/0i ua / GM/3 10:U1 r:>,.. 41 003
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -29
• 10 -1 -02 REV. 3
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping -
Hazard Dimensions Quantity Heights Part No. flow No.
Fryer /Split Vat Fryer" Maximum Size
(with drip board)
21 in. (53 cm) x
14 in. (36 cm)
(Fry Pot must not exceed
15 in. x 14 in.
(38 cm x 36 cm))
High Proximity 1 27 - 47 in. 419339 230
Medium Proximity 1 20 - 27 in. 419340 245
• Maximum Size
(with drip board)
25 3/8 in. (64.4 cm)
•
x 19 1/2 in. (49.5 cm)
(Fry pot side must not
exceed 19 1/2 in.
(49.5 cm) x 19 in.
(48.2 cm)
High Proximity 1 21 - 34 in. 419338 3N
Low Proximity 1 13 - 16 in. 419342 290
Maximum Size
(with drip board)
18 in. (45.7 cm) •
x 27 5/8 in. (70.2 cm)
High Proximity 1 25 - 35 In. 419338 3N
(64-89 cm)
Range Longest Side 1 30 -50 in. 419333 1F
28 in. (71 cm) (76 - 127 cm) � _4 w/ J
Area - 336 sq. in. 40 - 48 in. / ILO/ n
(2168 sq. cm) (102 -122 cm) pv 4 it —
(With Backshelf)
Longest Side (High Proximity) 1 40 - 50 in. 419340 245
28 in. (71 cm) (102 -127 an)
Area - 672 sq. in.
(4335 sq. cm)
Longest Side
(Medium Proximity) 1 30 - 40 in. 419341 260
32 in. (81 cm) (76 - 102 cm)
Area - 768 sq. in.
(4955 sq. cm)
Longest Side (Low Proximity) 2 15 - 20 in. 419342 290 --
36 in. (91 cm) (38 - 51 cm)
Area - 1008 sq. in. I,
(6503 sq. cm) w . Y */Y 4
•
•
•
For multiple nozzle oraection of single fryers, see detailed information on Pages 4.7 through 4.11.
05/09/2005 16:01 FAX a 004
r .
•
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -30 .
REV. 3 10 -1-02
• • Nozzle Application Chart (Continued)
. Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping -
)-lazard Dimensions Quantity Heights Part No. Flow No
Griddle Longest Side (High Proximity) 1 30 - 50 in. 419341 260
48 in. (122 cm) (76 - 127 cm)
Area - 1440 sq. in. (perimeter
(9290 sq. cm) located)
Longest Side (High Proximity) 1 30 - 50 in • 19342 290
30 in. (76 c n) (76 - 127 cm)
Area - 720 sq. in. (center located)
(4645 sq. cm)
Longest Side (High Proximity) 1 35 — 40 in. 419335/417332 1 N/1 NSS
36 in. (91 cm) (89 -102 cm)
Area - 1080 sq. in. (perimeter located)
(6968 sq. cm)
Longest Side 1 20 - 30 in. 419342 290
(Medium Proximity) (51 - 76 cm)
48 in. (122 cm) (perimeter
Area - 1440 sq. in. located)
(9290 sq. cm)
Longest Side (Low Proximity) 1 10 - 20 in. 419343 2120 '---
48 in. (122 cm) (25 - 51 cm)
Area - 1440 sq. In. (perimeter ( I c. 4 4.4 G c � j � E e
(9290 sq. cm) located) lY
Chain Broiler* Longest Side - 34 in. (86 cm) 2 10 - 26 In. 419336/417333 1 W/1 WSS
(Overhead Protection) Area - 1088 sq. in. (25 - 66 cm)
(7019 sq. cm)
" Chain Broiler Length - 43 in. (109 cm) 2 1 - 3 in. 419335/417332 1 N/1 NSS
(Horizontal Protection) Width - 31 in. (79 cm) (3 - 8 cm)
Gas- Radiant Char - Broiler Longest Side - 36 in. (91 cm) 1 15 - 40 in. 419335/417332 1 WIN S ----
Area - 864 sq. in. (38 - 102 cm) ( ��,��
(5574 sq. cm) 7-.44,4 L
Electric Char - Broiler Longest Side - 34 in. (86 cm) 1 20 - 50 in. , 19335/417332 1 N/1 NSS
Area - 680 sq. in. (51 -127 cm) .
(4388 sq. cm)
• Lava -Rock Broiler Longest Side - 24 in. (61 cm) 1 18 - 35 in. 419335/417332 1N /1NSS
Area - 312 sq. in. (46 - 89 cm)
(2013 sq. cm)
Natural Charcoal Broiler Longest Side - 24 in. (61 cm) • 1 18 - 40 in. 419335/417332 1 N/1 NSS
Area - 288 sq. in. (46 - 102 cm)
(1858 sq. cm)
Lava -Rock or Natural Longest Side - 30 in. (76 cm) 1 14 - 40 in. 419338 3N
Charcoal Char - Broiler Area - 720 sq. in. (36 - 102 cm)
(4645 sq. cm)
• Minimum chain broiler exhaust opening - 12 in x 12 in. 131 an x 31 ant, and not less than 60% of internal broiler size.
n~
•
Ua /U /ZUUD 16:UZ 1 4005
•
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -31
10 -1 -02 REV. 5
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping -
Hazard Dimensions Quantity Heiohts Part No Flow No.
• Wood Fueled Char - Broiler Longest Side - 30 in. (76 cm) 1 14 - 40 in. 419338 3N
Area - 720 sq. in. (36 - 102 cm)
(4645 sq. cm)
Upright Broiler Length - 32.5 in. (82.5 cm) 2 - 419334 1/2N
Width - 30 in. (76 cm)
Salamander Length - 32.5 in. (82.5 cm) 2 - 419334 1 1/2N
Broiler Width - 30 in (76 cm) S'.y f W,,,,n, O6"(--
Wok 14 in.- 30 in. (36 - 76 cm) 1 35 - 45 in. 419341 260
Diameter (89 - 114 cm)
3.75 - 8.0 in. (9.5 - 20 cm)
Deep
11 in. - 24 in. (28 - 61 cm) 30 - 40 in. 419335/417332 1 N/1 NSS
Diameter (89 - 102 cm)
3.0 -6.0 in. (8 -15.2 cm)
• Deep
s-�