October 21, 1996 c-e- —
3 41'L'A-
City of Tigard
13125 SW Hall Blvd.
Tigard, OR 97223
Attention: Jim Funk
Reference: Tenant Improvement
8250 SW Hunziker
PC #6 -118c
BUP#96 -0357
Gentlemen:
We are in receipt of your letter dated October 4, 1996. Attached please find drawings:
1.A Structural design for bearing walls.
1.B Floor plan designating bearing walls.
1.0 Second floor and ceiling construction.
1.D Stairway detail in compliance with OSSC, Section 1106.23 and 1109.8.
1. Handrails in compliance with 1109.86 (detail).
Fire'and Life Safety:
/ Will comply with required number of exists per OSSC Section 1003.1. By limiting
occupancy to max of nine (9), no conference or lunch room.
�. Fire sprinkler application, with protection in second floor storage room and protection under
stairway.
Respectfully,
CENTREX CONSTRUCTION, INC.
Jim Severson
President
warehous \city ltr2l . oct
8250 S.W. HUNZIKER RD. • TIGARD, OREGON 97223 -5060 • TELEPHONE (503) 684 -0443 • FAX (503) 620 -6692
.
11W
CENTREX CONSTRUCTION
INCORPORATED MIRIW®MANIFIUI
DATE: September 11, 1996
TO: Jim Funk; Plans Examiner, City of Tigard
FROM: Jim Severson; 8250 SW Hunziker Road, Tigard
SUBJECT: Tenant Improvement - Building Plan Review
PC #6 -188c - BUP# 96 -0357
July 23, 1996 City of Tigard Letter
Page one of two
This Tenant Improvement is included in the new construction of the new warehouse being built at
8250 SW Hunziker Road under building permit # 960151.
This memo is in response to the City of Tigard letter dated July 23, 1996. Attached is a revised
floor plan for the tenant improvement labeled 'Attachment #1'.
V. The true value for all work being done is $26,750.00.
2( The distance from the exterior door of the offices to the property line is forty feet (40 ft.) see
'Attachment #2'.
ENERGY COMPLIANCE
1 Energy Compliance Forms 2a, 3a, 3b, and 5a through 5c from the April 1, 1996 Revised
Oregon Energy Code are attached ('Attachment #3). Forms 4a through 4j will be submitted
along with the application for the mechanical permit.
ACCESSIBILITY
v This tenant improvement is part of the new construction of the warehouse and is in accordance
with OSSC, Section 1113.1.1, ORS 447,241(4). As this is new construction in compliance
with ADA standards, there are no architectural barriers to remove.
'■,EV Attached is a parking lot plan showing the accessible parking access aisle, signage, and
routes from the public way to accessible building entry, showing dimension and grade
elevations, see 'Attachment #2'.
8250 S.W. HUNZIKER RD. • TIGARD, OREGON 97223 -5060 • TELEPHONE (503) 684 -0443 • FAX (503) 620 -6692
MIIMORAMIDUM
DATE: September 11, 1996
TO: Jim Funk; Plans Examiner, City of Tigard
FROM: Jim Severson; 8250 SW Hunziker Road, Tigard
SUBJECT: Tenant Improvement - Building Plan Review
PC #6 -188c - BUP# 96 -0357
July 23, 1996 City of Tigard Letter
Page two of two
STRUCTURAL
V , See 'Attachment #4'.
Tempered glazing as required in item #2 is in compliance with required specifications.
3. Bathroom design and specification is atta hed and is in compliance with requirements under
item #3, A. and B, see 'Attachment #5' /
l
FIRE AND LIFE SAFETY
d Type 2A fire extinguisher will be provided and installed as required by specification.
MECHANICAL
Mechanical permit application will be submitted under separate cover.
FIRE SPRINKLER
1. Attached are three sets of sprinkler plans, see 'Attachment #6".
Attachments 1-6
(3) copies
warehouse \cityltr. sep
July 23, 1996
Jim Severson CITY OF TIGARD
8250 SW Hunziker I
Tigard, OR 97223 I OREGON
RE: Tenant Improvement Building Plan Review
8250 SW Hunziker
PC #: 6 -118c BUP #: 96 -0357
Submittal documents for the above referenced project have been reviewed for conformance with
the applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The
following comments are noted:
1. Submit copies of all contractor's agreements showing bid prices or submit a true value for
all work being done.
What is the distance to the property line from the exterior door?
i �t°' } r1i QZ1 E.ai! ) � �;S` F �k •
?-Y F r
.� "S n u }' - .•+.i$':u. are�.ucr.cweu.....e,er a .vw.✓...s..- .w.-srii
Submit completed Energy Compliance Forms 2a, 3a, 3b, 4a through 4j, and 5a through 5c
from the April 1, 1996 Revised Oregon Energy Code.
An amount equal to 25% of the tenant improvement cost shall be budgeted for removal of
existing architectural barriers within the boundary of the site and tenant space. Barrier
ivv ,./ removal shall be in accordance with OSSC, Section 1113.1.1, ORS 447.241(4). Provide
the budget and list of improvements and their cost.
A. Provide a parking lot plan showing the accessible parking access aisle, signage,
and route from the public way to the accessible building entry [OSSC, Section
1103.1]. Show dimension and grade elevations.
z 1 ; The suspended acoustical ceiling system shall be anchored to resist lateral seismic forces
[Section 2336(b) and Table 23P]. Provide suspension wires not smaller than No. 12
gauge spaced at 4' on center, perimeter wires on terminal ends of cross and main
runners at a maximum of 8" from each wall, four No. 12 gauge wires splayed 90 degrees
from each other at an angle not exceeding 45 degrees from the plane of the ceiling with a
strut centered and extending to the structural members supporting the floor or roof above
and spaced 12' on center in both directions starting 6' from each wall. All lighting fixtures
weighing less than 56 lbs. shall be positively attached to the suspended ceiling system
[UBC Standard Section 47.1813]. When using an intermediate grade system, No. 12
gauge wires shall be attached to the grid members within 3° of each corner of the fixtures,
and lighting fixtures weighing less than 56 lbs. shall have two No. 12 slack wires
connected from the fixture to the structure above. Ceiling mounted air terminals or
services weighing less than 20 lbs. shall be positively attached to ceiling runners [UBC
Standard Section 47.1814]. Provide an illustration.
3125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
_Tenant Improvement Building Plan Review
PC #: 6 -118c B U P #: 96 -0357
Page #2
11 7 Z Glazing, in fixed or operable panels, adjacent to a door where the nearest exposed edge of
the glazing is within a 24" arc of either vertical edge of the door in a closed position and
where the bottom exposed edge of the glazing is less than 60" above the walking surface,
shall be tempered [2406.4(6)].
3. Provide the bathroom structural design and specification. Give ceiling joist size and span, �?C
door width, and accessible facilities. /1
A. Toilet room floors shall have a smooth, hard, nonabsorbent surface which extends )- nr
upward onto the walls at least 5 inches [OSSC, Section 807.1.2]. 44$1( B. When gypsum wall board is used as the base for the smooth, hard, nonabsorbent
surface material required in restrooms, water - resistant gypsum backing board shall 7,j,i_
be used [Section 2512].
RE" AND` LIFE SAFETlf=" - � , ° -^;
'ry r1 07.41
f j .4
f>� Provide a Type 2A fire extinguisher within the office space mounted no higher than 5 feet. n
above the finish floor [NFPA 10, Section 3.2.1].
X91 U
1. Submit a mechanical permit application and three (3) sets of plans and specifications. 4. y
A. Each bathroom fan shall exhaust not less than 50 cfm [OSSC, Section 1202.2.5]. 2 34, 1.-._
B. Provide a ventilation system that provides outside air in accordance with OSSC,
Section 1202.2.1 and Table 12 -A.
h six. MA am r; c r % , + 4-**M<a -5 �. '�
1. _ , _ _ _ _
Submit sprinkler permit application ad not less than three (3) sets of plans.
Please submit three copies of revised submittal documents and a letter indicating your response
to the above comments for review. Please call me at (503) 639 -4171 if you have any questions.
Sincerely,
Jim Funk � / I1 G f ►'k 4 % J
PLANS EXAMINER 1 f fi �• N ( 4:7 eC
c: Centrex Construction i
8250 SW Hunziker v t 4 t ,Y y - 4
Tigard, OR 97224
6;7 41,-- 4'4,1
U:\ PRMSYS\ DOCUMENl18UP96 _03.5TPC6- 118C.DOC � j1 t r� b-- R4-7
I .
c tilTkit-, kr 1 1
i,
r
October 4, 1996 - ^ ^� " I
Jim Severson CITY OF TIGARD
8250 SW Hunziker
Tigard, OR 97223 OREGON
RE: Tenant Improvement (2nd Review) Building Plan Review
8250 SW Hunziker
PC #: 6 -118c BUP #: 96 -0357
The original submittal and plan review did not include the second floor. Provide revised plans that
include the following:
Y Provide the structural design and specifications for constructing the two -story addition.
h i
Provide the footing design for supporting all bearing walls.
/61V Provide a foundation plan designating bearing walls.
C. Provide the second floor and ceiling construction showing joist size, spacing,
ceiling /floor covering, and insulation atop suspended ceiling.
I D. Provide a detail of the stairway in compliance with accessibility requirements of
OSSC, Section 1106.2.3 and 1109.8.
• 1. Handrails shall be in compliance with Section 1109.8.6 (show detail).
w
J Occupants on the second floor shall have access to two (2) exits if the occupant load
exceeds nine (9) [OSSC, Section 1003.1]. There shall be no conference, meeting or
lunch room provided on the second floor.
✓ Submit a separate fire sprinkler permit application.
IA. Provide protection in the second floor storage room.
B. Provide protection under the stairway.
Please submit three copies of revised submittal documents and a letter indicating your response
to the above comments for review. Please call me at (503) 639 -4171 if you have any questions.
Sincerely,
Jim Funk
PLANS EXAMINER
M: \PRMSYS\DOCUMENT\PC6118CA.DOC r {