October 4, 1996
Air Pro Heating CITY OF TIGARD
7405 SE Powell Boulevard
Portland, OR 97206 OREGON
RE: Centrex Warehouse Mechanical Plan Review
8250 SW Hunziker
PC #: 9 -69c MEC #: 96 -0326
Submittal documents for the above referenced project have been reviewed for conformance with
the applicable 1996 Oregon Specialty Codes and other applicable codes and standards. The
following comments are noted:
The warehouse exterior envelope does not meet the requirements for enclosing
conditioned space. The unit heater specified for the warehouse provides 32 btu per
square foot exceeding the 8 btu per square feet allowance for freeze - protected areas
[OSSC, Section 1312]. If the building is sprinkler protected, apply Section 1312,
Exception No. 1 and 1.1 and submit new plans and specifications.
The equipment schedule shall include the cfm, weight, and outside air requirements.
A. The heat/ventilation system shall provide outside air per occupant in all portions
of the building [UBC Section 1202.2.1 and Table 12 -P].
of 1. Provide outside air specifications on the revised plans.
The warehouse shall be provided with mechanical ventilation when natural ventilation
cannot be obtained, in accordance with OSSC, Section 1202.2. Provide ventilation.
A. Provide a floor plan of the entire tenant space and show location of all windows
and doors.
Each restroom shall be provided with an exhaust fan, exhausting not less than 50 cfm for
each water closet and /or urinal [OSSC, Section 1202.2.5].
Please submit three copies of revised submittal documents and a letter indicating your response
to the above comments for review. Please call me at (503) 639 -4171 if you have any questions.