Plans VIKING AUTOMATIC SPRINKLER COMPANY
3245 N.W. FRONT AVENUE
PORTLAND, OR 97210 -1509 >>
HYDRAULIC CALCULATIONS
FOR CITY OF TIGARD
Approved
Conditionally Approved ••••••
ARTISTIC A U T O B O D Y For only the wo described in:
TIGARD, OR. (PAINT BOOTH) PERMIT NO. Zda J D
See Leo • to: Fo ow
FILE NUMBER:
•- ch
DATE: OCT 24, 2001 Jo. Addr s' � '�
DateV AA o
- DESIGN DATA -
OCCUPANCY CLASSIFICATION: PAINT BOOTH
DENSITY: .40 gpm/sq. ft.
AREA OF APPLICATION: ENTIRE BOOTH
COVERAGE PER SPRINKLER: VARIES
NUMBER OF SPRINKLERS CALCULATED: 5 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 83.2 gpm
TOTAL WATER REQUIRED (including hose): 583.2 gpm
FLOW AND PRESSURE (el BOR): 83.2 gpm @ 25.8 psi
SPRINKLER ORIFICE SIZE: 1/2 inch
NAME OF CONTRACTOR: VIKING AUTOMATIC SPRINKLER CO.
DESIGN /LAYOUT BY: WAYNE WINSTON /DEREK WITTKOPF
AUTHORITY HAVING JURISDICTION: CITY OF TIGARD
CONTRACTOR CERTIFICATION NUMBER: 64837
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE it 38030713 )
HRS SYSTEMS, INC.
TUCKER, GA 30084