Correspondence ADM January 3, 2012
1111E111
ARCHITECTURAL
GROUP RECEIVED
INTERNATIONAL JAN 0 4 2012
CITY OF TIGA5D
BUILDING DIVISION
Dan Nelson
Senior Plans Examiner
City of Tigard
Re: Tenant Improvement (The Body Shop)
Permit Number BUP2011 -00262
9532 SW Washington Square
Dear Mr. Nelson:
We have received your plan review comments dated 12/16/11, and have the following
information in response:
1. Detail 2/A4.1 has been revised to clarify the suspension and bracing for the
suspended sheetrock ceiling. Additionally, structural calculations and details are
enclosed. Please note that the sheetrock portion of the ceiling is less than
1000sf, and is bounded by braced bulkheads, so horizontal restraint wire and
rigid bracing are not required.
2. Details 5/A4.1 and 6/A4.1 have been revised to clarify the suspension and
bracing of the storefront soffit. Additionally, structural calculations and details are
enclosed.
3. The estimated permit valuation of the project is $105,000.
We hope this information will allow for prompt approval of the plans, but if any additional
information is required, please contact our office at any time.
Sincerely, .
Quin Wichmann
Architectural Group International
15 W. SEVENTH STREET a COVINGTON, KENTUCKY 41011
PHONE: 859.261.5400 a TOLL FREE: 877.261.5400 0 FAX• 859.261 5530
eastoffice@agi- us.com a www.agi- global.com
Q/2o oz)R62.
Iminsep K KOHRS LONNEMANN HEIL ENGINEERS, PSC
♦� L FT. THOMAS, KENTUCKY
H DAYTON, OHIO
ENGINEERS COLUMBUS, OHIO
NEW YORK, NEW YORK
800.354.9783
WWW.KLHENGRS.COM
December 23, 2011
Dan Nelson, HLVLi V I
Senior Plans Examiner JAN 0 4 2012
(503) 718 -2436
dann @tigard- or.gov CITY OF TIGARD
BUILDING DIVISION
Re: The Body Shop
9532 Washington Square
Mechanical TI
Dear Mr. Nelson:
In response to your plan review letter dated December 23, 2011 pertaining to the application for permit for the
project listed above, we respectfully submit the following clarification:
1. Please show attachment of VAV to structure.
Response: The VAV box is existing to remain, and existing attachment to structure is existing to remain.
If we can provide you any further information regarding the above, please contact us at your convenience.
Respectfully,
KOHRS LON '' ' ANN HEIL ENGINEERS, P.S.C.
f Li Itia
'.bert A unnemann, P.E.
•
December 16, 2011 n
TI GARD,
RE: TENANT IMPROVEMENT City of Tigard
Project Information
Building Permit: BUP2011 -00262 Construction Type: 2 -B
Address: 9532 SW Washington Sq. Occupancy Type: M
Area: 1491 Sq. Ft. Stories: 1
Name: Body Shop Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below.
1) Provide calculations and construction details (including seismic bracing
details for non full height partitions) for all walls and sheetrock ceilings. Note:
The roof structure may be approximately 30' above the finished floor.
OSSC 106.1
2) Please provide calculations and construction details for the soffits and
storefront construction. Every structure, and portion thereof, including non
structural components that are permanently attached to structures and their
supports and attachments, shall be designed and constructed to resist the
effects of earthquake motions in accordance with ASCE 7 as modified by
Section 1613.7. The seismic design category for a structure is permitted to be
determined in accordance with Section 1613 or ASCE 7. OSSC 1613.1
3) Please provide a permit valuation based on the total work being performed.
Permit valuations shall include total value of work, including materials and
labor, for which the permit is being issued, such as electrical, gas,
mechanical, plumbing equipment, flooring, ceilings and any fixture attached to
the building. If, in the opinion of the building official, the valuation is
underestimated on the application, the permit shall be denied, unless the
applicant can show detailed estimates to meet the approval of the building
official. Final building permit valuation shall be set by the building official.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson
Senior Plans Examiner
(503) 718 -2436
dann @tigard- or.gov