Correspondence r» City of Tigard, Oregon 13125 SW Hall Blvd. . Tigard, OR 97223 1 " `# i" 4.
r May 15, 2007
®
RE: HILLTOP '
Permit Number BUP 2007 -00238 Construction Type: VB %r�{ I
Tenant Name: Hilltop Occupancy Type: B „
Address: 7320 SW Hunziker Rd. Occupant Load: 174
Area: 17466 Sq. Ft. Stories: 2
Sprinklers: No Hazard: N/A
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC),
2007 edition; the Oregon Fire Code (OFC), 2007 edition and NFPA 72 Alarm Code. The
submitted plans are approved subject to the following.
Manual Devices
1. Manual Fire Alarm activation devices shall be mounted a minimum of 42 inches and a
maximum of 48 inches measured vertically from the floor to the activating handle or
lever of the device. Section 907.4.2 OFC.
2. A test of the manual fire alarm shall be performed for the structural inspector at the final
inspection.
Visual Devices (Section 1109.14 OSSC)
1 Visual signal appliances shall be provided in the building in each area
2. Visual alarms shall be located not less than 80 inches and not more than 96 inches above
the floor level. When a low ceiling exists, the visual alarm shall be mounted at least 6
inches below the ceiling.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road fronting
the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully,
-
i
Dan Nelson, VV
Senior Plans Examiner
Phone: 503.639.4171 • Fax: 503.684.7297 0 www.tigard- or.gov • TTY Relay: 503.684.2772