Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 February 21, 2008 u1 • • RE: COMMERCIAL EXHAUST HOOD T I CARD Project Information Building Permit: MEC2008 -00069 Occupancy Type: A -2 Tenant Name: Wooden Shoe Deli Construction Type: VN Address: 7320 SW Hunziker Stories: 3 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition and The Oregon Fire Code 2007 edition. The following information shall be submitted prior to issuance of permit. 1) Provide drawings showing specific installation of type 1 hood. 2) Show how all thread rod holding hood is attached to structure. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectf II Dan Nelson, Senior Plans Examiner (503) 718 -2436 dann @tigard- or.gov Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 • • L• , J City of Tigard, Oregon • 13125 SW Hall Blvd. o Tigard, OR 97223 z ': February 4, 2008 e IX - e RE: COMMERCIAL EXHAUST HOOD -4414-1 Proiect Information Building Permit: MEC2008 -00069 Occupancy Type: A -2 Tenant Name: Wooden Shoe Deli Construction Type: VN Address: 7320 SW Hunziker Ave. Stories: 3 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition and The Oregon Fire Code 2007 edition. The following information shall be submitted prior to issuance of permit. A Performance Test shall be conducted upon completion and before final approval of the installation of the ventilation system. The performance test shall verify the rate of airflow to be in compliance with the approved plans. 507.17 OMSC The exhaust and make -up air system shall be electronically interlocked to ensure that the make -up air is provided whenever the exhaust system is in operation. 508.1 OMSC An automatic fire suppression system shall be provided to protect the surface of the heat - processing appliances and the exhaust system serving the appliances. 509.2 OMSC Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) Compensating hoods Manufacturers of compensating hoods shall provide label indicating minimum exhaust flow and /or maximum makeup airflow that provides capture and containment of the exhaust effluent. OMSC 508.2 • All deep -fat fryers shall be installed with at least a 406 mm (16 in.) space between the fryer and surface flames from adjacent cooking equipment. 12.1.2.4 • Where a steel or tempered glass baffle plate is installed at a minimum 203 mm (8 in.) in height between the fryer and surface flames of the adjacent appliance, the requirement for a 406 mm (16 in.) space shall not apply. 12.1.2.5 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Phone: 503.639.4171 o Fax: 503.684.7297 • www.tigard- or.gov o TTY Relay: 503.684.2772 When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. 3 Respectfully I , f,. Dan Nelson, Senior Plans Examiner (503) 718 -2436 dann @tigard - or.gov