Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
February 21, 2008 u1
•
•
RE: COMMERCIAL EXHAUST HOOD T I CARD
Project Information
Building Permit: MEC2008 -00069 Occupancy Type: A -2
Tenant Name: Wooden Shoe Deli Construction Type: VN
Address: 7320 SW Hunziker Stories: 3
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition and The Oregon Fire Code 2007 edition. The following
information shall be submitted prior to issuance of permit.
1) Provide drawings showing specific installation of type 1 hood.
2) Show how all thread rod holding hood is attached to structure.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectf II
Dan Nelson,
Senior Plans Examiner
(503) 718 -2436
dann @tigard- or.gov
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
•
•
L• , J
City of Tigard, Oregon • 13125 SW Hall Blvd. o Tigard, OR 97223 z ':
February 4, 2008 e
IX
- e
RE: COMMERCIAL EXHAUST HOOD -4414-1
Proiect Information
Building Permit: MEC2008 -00069 Occupancy Type: A -2
Tenant Name: Wooden Shoe Deli Construction Type: VN
Address: 7320 SW Hunziker Ave. Stories: 3
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition and The Oregon Fire Code 2007 edition. The following
information shall be submitted prior to issuance of permit.
A Performance Test shall be conducted upon completion and before final approval of
the installation of the ventilation system. The performance test shall verify the rate of
airflow to be in compliance with the approved plans. 507.17 OMSC
The exhaust and make -up air system shall be electronically interlocked to ensure that
the make -up air is provided whenever the exhaust system is in operation. 508.1 OMSC
An automatic fire suppression system shall be provided to protect the surface of the
heat - processing appliances and the exhaust system serving the appliances. 509.2
OMSC
Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
Compensating hoods Manufacturers of compensating hoods shall provide label
indicating minimum exhaust flow and /or maximum makeup airflow that provides capture
and containment of the exhaust effluent. OMSC 508.2
• All deep -fat fryers shall be installed with at least a 406 mm (16 in.) space
between the fryer and surface flames from adjacent cooking equipment. 12.1.2.4
• Where a steel or tempered glass baffle plate is installed at a minimum 203 mm (8
in.) in height between the fryer and surface flames of the adjacent appliance, the
requirement for a 406 mm (16 in.) space shall not apply. 12.1.2.5
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
inspectors throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
Phone: 503.639.4171 o Fax: 503.684.7297 • www.tigard- or.gov o TTY Relay: 503.684.2772
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
3 Respectfully