Correspondence February 20, 2004 till A�
I La
Darren Urton CITY OF TIGARD
Climate Control :11?_. EGON
16500 SW 72 Avenue
Tigard, OR 97223
RE: MECHANICAL EQUIPMENT @ MINUTEMAN PRESS
Building Permit: MEC2003 -00699 Construction Type: VN
Tenant Name: Minuteman Occupancy Type: B
Address: 7555 SW Hermoso Way Occupant Load: NA
Area: 7,270 Sq Ft Stories: 3
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01)
1999 edition. The submitted plans are approved subject to the following.
1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
2. Each appliance shall be provided with a shutoff valve separate from the appliance. The
shutoff valve shall be located in the same room and within six feet of the appliance
served. Access shall be provided to the shutoff valve. C409.5 OMSC
3. Equipment and appliances regulated by this code requiring electrical connections shall
have a positive means of disconnect in accordance with the Electrical Code. 301.7
OMSC
4. Appliances serving different areas of a building other than where they are installed
shall be permanently marked in an approved manner that uniquely identifies the
appliance and the area it serves. 304.10 OMSC
5. Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
6. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
7. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
Respec - ,' y,
.,. alc ,
Se tor Plans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
-,q
FIL
E COPY
January 2, 2004
Darren Urton
CITY OF TIGA tD
Climate Control OREGON <.
16500 SW 72 Avenue
Tigard, OR 97223
RE: MECHANICAL EQUIPMENT @ MINUTEMAN PRESS
Building Permit: MEC2003 -00699 Construction Type: VN
Tenant Name: S Minuteman Occupancy Type: B
Address: "SSW Hermoso Way - Occupant Load: NA
Area: 7,270 Sq Ft Stories: 3
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99
01) 1999 edition. The following information is required prior to the issuance of the
Mechanical Permit.
1. Provide equipment cut sheets for all mechanical equipment. Installation instructions i , <t su
'are also required for attic furnaces to clarify clearances to combustibles..
2. Mechanical units located in attic areas require access panels, passageways and service t-',
platforms as identified in section 306.3 OMSC. Provide cross - sections and floor plans„.
1f : q qyq�
indicating the locations and construction of the required access.
3. Provide cross - sections of the attic furnace to indicate clearances to combustible' i ` '`
construction as required by the manufacturer's installation instructions.
4. Provide Department of Energy Forms for the systems.
5. Identify on plans the type of material to be used for the ductwork. , R
6. Clarify the attachment to the structure for units Fl & F2. The detail provided is not
legible and does not indicate the size of the anchor attaching the threaded rod to the
structural component - ,g
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and pr • essing the documents
Respectfu ";: .Oo,. rY
ria t lalock,
REC
Senior Plans Examiner ,R