Loading...
Correspondence City of Tigard, Oregon 13125 SW Hall Blvd. ® Tigard, OR 97223 E47R' -f" January 22, 2009 RE: MECHANICAL Project Information I 7 130 Y Building Permit: MEC2009 -00021 Construction Type: 5B Tenant Name: Kaiser Occupancy Type: B Address: 7105 SW Hampton St. Occupant Load: NA Area: NA Stories: NA The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The submitted plans are approved subject to the following. 1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) 2. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC 3. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 4. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 5. Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC 6. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC 7. Smoke detectors shall be installed in return air systems with a design capacity greater than 2000 cfm. Upon activation, the smoke detector shall shut down the air distribution system. Smoke detectors shall be connected to a fire alarm system or shall activate an audible and visible alarm at a constantly attended location. 606.2, 606.4 & 606.4.1 OMSC 8. Inspector may require additional sway bracing at the final installation inspection. Phone: 503.639.4171 0 Fax: 503.684.7297 0 www.tigard- or.gov ® TTY Relay: 503.684.2772 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Dan Nelson, Senior Plans Examiner (503)718 -2436 dann @tigard- or.com 4 Johnson Controls Inc. 4011 SE International Way, #605 Johnson 010 Milwaukie, OR 97222 -8826 Controls Main 503 - 305 -2000 Fax 503 - 654 -1158 Date: February 5, 2009 To: Dan Nelson City of Tigard Community Development, Building Division 13125 SW Hall Blvd Tigard, OR 97223 Project: Permit # MEC2009- 00021, New RTU Installation Subject: Final Airflow Rate of New Rooftop Unit Dear Dan, This letter is a follow up to your conversation on February 2, 2009 with Johnson Controls' mechanic Bob Pasko. The new rooftop HVAC unit being installed at Kaiser Dental Clinic (7105 SW Hampton St) will be set at a final airflow rate of 1800CFM (4.5 Ton), down from the factory setting of 2000CFM (5 Ton). This is due to the capacity of the existing ductwork and it not being able to accept the full 2000CFM. We will add additional ductwork and diffusers to accommodate 1800CFM and balance accordingly. With the final airflow rate being below 2000CFM, the addition of a duct smoke detector will not be required. Please let me know if you have any additional questions. Thank you, V 1 r Or few r Tony M. Hunt G � Service Project Manager �/ Johnson Controls, Inc. 503/305 -2016 Office 503/654 -1158 Fax email: tony.m.huntPici.com Thursday, February 05, 2009 JCI Letter Page 1