Loading...
Correspondence ,. • a*.o ...October, 29 „ 2003 , • CITY OF 'TIGARD Curtis Gouverneur OREGON 12670 SW Hall, Boulevard -- Tigard, OR 97223 RE: CHANGE OF OCCUPANCY, S1 TO F2 Project Information Building Permit: BUP2003 -00612 Construction Type: VN Tenant Name: Oregon Beverage Works, Inc. Occupancy Type: F2 Address: 12670. SW Hall Boulevard Occupant Load: 98 Area: 19,600 Sq Ft , Stories: 1 Sprinkled: NA Alarms: NA The plan review Was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99- 01(TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following conditions. 1. Exit signs shall be illuminated at all times. 1003.2.8.5 OSSC 2. The means of egress' shall be provided with illumination of not, less than 1 foot candle at the floor level anytime the building is. occupied. The means of egress illumination r . shall be provided with a second source, of power in case of primary power loss. 1003.2.9. OSSC `.. 3. Provide 2 -A 'rated fire extinguishers so that no usable space has a distance greater than 75 feet to the extinguisher. Standard 10-1, Chapter 3 TVFR99 -O 1 . FYI A Plumbing permit is required for the process piping attached to the boiler. American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC which may not include all of the requirements of the ADA. - - -_ Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors - . throughout all phases of construction. 106.4.2 OSSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Certificate of Occupancy: No building or structure shall be used or occupied until the Building Official has issued a certificate of occupancy 109.1 OSSC Premises: Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed. City of Tigard, Letter of Transmittal The letter of transmittal assists the City of Tigard in tracking and pro in_ the documents. espect ' , tanB . • ck;. Senior Plans Examiner