Loading...
Correspondence OFFICE COPY November 9, 2004 ����°��w��������V���pipl'� p`` Chris Gardner CI TY OF TIGARD Limited Energy Electricians OR EGON 4020 SE 1st Place Gresham, OR 97080 RE: FIRE ALARM SYSTEM Building Permit: BUP2004 -00516 Construction Type: VN Tenant Name: City of Tigard Occupancy Type: B Address: 13125 SW Hall Boulevard Occupant Load: 240 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. General requirements 1. A key box shall be installed within 20 feet of the main entrance. The bottom of the key box shall be not less than 8 feet nor more than 10 feet above the walking surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 An existing key box at the main building entrance is acceptable. 2. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the Fire Chief. All functions of the system or alteration shall be tested. 1007.3.4.1 TVFR99 -01 3. The permittee shall provide written certification to the Fire Chief that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. 1007.3.4.2 TVFR99 -01. 4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL. Standard 10 -2, Section 1- 5.2.8.2, TVFR99 -01 Manual Fire Alarm activation devices shall be mounted in the following reach ranges: • Forward Reach - 15 inches to 48 inches above the floor. 1 109.2.3.5 OSSC • Side Reach — 9 inches to 54 inches above the floor. 1109.2_ °SSC�. Approved Plans Date /12- 13125 SW Hal Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Visuals (Section 1109.14 OSSC) • Visual alarms shall be located not less than 80 inches and not more than 96 inches above the floor level. When a low ceiling exists, the visual alarm shall be mounted at . least 6 inches below the ceiling. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully Brian B1: • ck, Senio ' Tans Examiner