Loading...
Correspondence , ,0270/0 a TUALATIN VALLEY FIRE & RESCUE • SOUTH DIVISION a • " ® COMMUNITY SERVICES • OPERATIONS • FIRE PREVENTION Tualatin Valley Fire & Rescue July 30, 2001 Brad Kilby, Associate Planner City of Tigard 13125 SW Hall Blvd Tigard, OR 97223 Re: Brahma Premananda Ashram & Temple Dear Brad, I have reviewed the submittal for the above named project and have the following comments: 1. The minimum required fire flow is 1500 gpm @ 20 psi . Prior to the issuance of building permits, documentation shall be provided that indicates the minimum fire flow is available at the required hydrants. (UFC Appendix III -A) 2. A minimum of 2 fire hydrants shall be provided for this development. The hydrants shall be located so that all portions of both buildings are within 250 feet of a hydrant. (UFC 903.4) 3. The Fire Department Connection (FDC) shall be located within 70 feet of a fire hydrant. • 4. Fire hydrant locations shall be identified by the installation of reflective markers. The markers shall be blue. They shall be located adjacent and to the side of the centerline of the access roadway that the fire hydrant is located on. In case that there is no center line, then assume a centerline, and place the reflectors accordingly. (UFC Sec. 901.4.3) 5. Approved fire apparatus access roadways and firefighting water supplies shall be installed and operational prior to stockpiling combustibles on -site or the commencement of combustible construction. (UFC Sec. 8704) 6. A Knox brand key box shall be provided on the building. Contact the Fire Marshal's Office for installation details and an application. (UFC Chapter 9) 7. A building survey and plans, in accordance with TVF &R Ordinance 99 -01, Appendix III -F, shall be submitted. A copy of Appendix III -F, the building survey form and the instructions are available on the Fire District web site. To access this information via Internet, go to www.tvfr.com, choose "Fire Prevention ", then choose "New Construction ". (UFC Appendix III -F) Please contact me at (503) 612 -7010 with any additional questions. Sincerely, Eric T. McMullen Eric T. McMullen Deputy Fire Marshal ; I! iji ■ "r 4e. A I ■• I oec /ao 7, t elfz• ; 12) &r7,0,34-07 3 A..1044. eh S.4 /*/ / -- , I _6 ,vj eri/ frge ■Se >7 Z.- I ) 4orff 44 OeOr )-7 , e€A4J., / . .• • .. 4 - - - -