Specifications
0(4 Paoo3 o /off /- eve( Scheduled Events (Skeds) D9210 Access Control Module • Day -of -week or date of the year schedules Access can be granted from a Wiegand style access • Four holiday schedules of 365 days each control device (access reader) when connected to a D9210 Access Control Module. Access may also be granted from • Up to 64 scheduled events with 26 different functions a REQUEST TO EXIT or a REQUEST TO ENTER input. • Remotely programmable with User control capability The D9210 Access Interface Module provides for connec- from the command center tions of the access door point and the door strike. Up to The D7412's internal clock and calendar help the panel two D9210s can be incorporated on each system. Each operate individual scheduled events (Skeds). You can D9210 controls one door. program each Sked to perform a specific function (such as • Each access door can be configured independently from arm /disarm, relay control, point bypassing, etc.). Each the other doors. Sked is programmed for a time and either a day of the • The same alarm door contact point controls the access week schedule or a date of the year schedule. door and is part of the alarm system (the door does not The User can change the time for the Sked if the Sked is need to have double contacts). programmed for local time editing. Holiday schedules can • The door contact can be either normally open or be used to enable or disable individual Skeds during the normally closed and is used to reset the door strike time holiday periods. when the door either opens or closes depending upon programming. Fire Test • The door contact can terminate a programmable door In the Fire Test Mode, the D7412 suppresses reports to the entry buzzer (if used). receiver so you can test initiating and indicating devices • The door contact is shunted when valid access is being without transmitting alarms to the central station. When granted through the door. you put the D7412 in Fire Test Mode, the panel sends a report to the central station to indicate the start of the test. • An optional buzzer can be triggered prior to the end of a Test events then become "local only ". The command door shunt period to warn the user that a "door left open" center shows how many points are to be tested. condition is about to occur. Each time a device initiates an alarm, the programmed • The access point can be configured to generate an point text displays at the command center. The automatic alarm or a trouble (or have no response) when the door sensor reset feature of the Fire Test Mode allows you to is left open beyond the door shunt period. continue testing additional devices without time consuming • The reading of access cards, in addition to the granting trips to the command center to manually reset sensors. At of access, can control whether the system will disarm the end of the test, the command center displays the along with granting of access. number of untested points. You can also view the point text • The door strike can be programmed to be held open for each untested point. automatically during the disarm period and then auto - When you take the D7412 out of Fire Test Mode, the panel matically re lock when the area is armed. sends a report to the receiver indicating the completion of • The system can be configured to generate an alarm, a the test. trouble, (or have no response) depending upon the area's armed condition when the door is opened outside Combining Access Control with Security of an authorized access period. and Fire Detection • An option is provided that can control whether access granted conditions or no entry conditions send A combined system can help prevent false alarms by events to the log by door. making it easy to use just one system that controls • REQUEST TO ENTER and REQUEST TO EXIT can be security, access, and fire functions. programmed to shunt the door without activating the The access control features of the D7412 can deny access strike. during armed periods. It can also grant access only to certain authorized users depending on whether the area is master armed, perimeter armed, or disarmed. The alarm Specifications system can automatically disarm when designated General authorized users are granted access. The contractor shall furnish and install, where indicated on The D7412 can control two (2) Access Doors as part of the the plans, a Radionics D7412 Control /Communicator. The 75 intrusion and fire detection points. panel shall be listed by Underwriters Laboratories for You can use up to 396 Wiegand user identification devices NFPA 72 Applications. in the D7412 system. Up to four of the Wiegand user The D7412 shall support initiating and indicating modules devices can be associated with each of the 99 user and Radionics Command Centers. The D7412 Control/ names, passcodes and area authority levels. Communicator power supply shall provide 1.4 Amps of power for all processing functions and 12 VDC auxiliary requirements. © 1997 Radionics, Inc. D7412 Specification Sheet L826 P/N 34019D (10/97) 33 Q (4 P O05( Specificat Housing Red or white textured UV stabilized, color impregnated engineered plastic. Exceeds 94V -0 UL flammability rating. Lens Optical grade polycarbonate (clear) Mounting Flush mount: 2'/2 inch (64 mm) deep one -gang box (indoor wall mount only) Surface mount: EST model 27193 surface mount box, wiremold box, or equivalent surface -mount box With optional trim plate: One -gang, two -gang, four -inch square, octagonal, or European single -gang box Wire connections Screw terminals: single input for both horn and strobe. #18 to #12 AWG (0.75 mm to 2.5 mm wire size _ Operating environment Indoor only: 32 -120 °F (0 -49 °C) ambient temperature. 93% relative humidity Agency UL 1971, UL 1638, UL 464, ULC S525, ULC S526, CE, FCC, (MEA, FM, CSFM pending). . listings /approvals (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.) Dimensions (HxWxD) Signal: 4 -1/2" x 2 -3/4" x 13/16" (113 mm x 68 mm x 21 mm) Trimplate: 5" (127 mm); Height - 5 -7/8" (149 mm); Depth -'/i' (13 mm) G1 -HD series temporal -tone horns: non - coded, filtered 16 -33 Vdc or unfiltered 16 -33 Vdc FWR (or coded when horn set to steady tone) Operating voltage G1 -HDVM series temporal -tone horn - strobes: non - coded, filtered 16 -33 Vdc or unfiltered 16 -33 Vdc FWR (or coded (audible NAC only) when used with optional G1M Genesis Signal Master) G1 -VM series strobes: non - coded, filtered 16 - 33 Vdc or unfiltered 16 -33 Vdc FWR G1 -P series steady -tone horns: coded or non - coded, filtered 20 -31 Vdc or unfiltered 20 -27 Vfwr Strobe output rating UL 1971, UL 1638, ULC S526: selectable 15 cd, 30 cd, 75 cd, or 110 cd output G1 -VM strobes and G1 -HDVM series temporal -tone horn - strobes: one flash per second synchronized with Strobe flash rate optional G1M Genesis Signal Master indefinitely within 10 milliseconds (or self- synchronized within • 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) Temporal setting (private mode only): synchronized to temporal output of horns on same circuit Compatible synchronization G1M, G1M -RM, SIGA -CC1S, SIGA -MCC1S modules` G1 -HD temporal -tone horns and G1 -HDVM series temporal -tone horn - strobes: temporal rate synchronized Horn pulse rate with optional G1M Genesis Signal Master indefinitely within 10 milliseconds (or self - synchronized within 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) G1 -P steady -tone horns: continuous, steady tone only Temporal audible pattern 1/2 sec ON, '/2 sec OFF, Y sec ON, 1/2 sec OFF, Y sec ON, 11/2 sec OFF, then repeat cycle Not compatible with G1 -P Series horns. dBA output Average Sound Output (dBA) Temporal Horns, Horn - strobes (G1 -HD, G1 -HDVM series) - High dB Setting (High dB setting, anecholi , 24V, measured at 10ft) 70 80 50 0 30 20 10 0 10 20 UL464 Average Peak eo „° °° °° °° -- - o - -- w - .-- I ,l" So. Temporal Steady Temporal /Steady Temporal /Steady 16 Vdc 81.4 85.5 91.4 94.2 -,5• / ;s 24 Vdc 84.4 88.6 94.5 97.6 33 Vdc 86.3 90.4 96.9 99.5 60. 11 w• Temporal Horns, Horn - strobes (G1 -HD, G1 -HDVM series) - Low dB Setting .s 05 UL464 Average Peak Temporal Steady Temporal /Steady Temporal /Steady s. ° s 16 Vdc 76.0 80.1 86.3 89.2 24 Vdc 79.4 83.5 89.8 92.5 33 Vdc 82.1 86.5 92.5 95.3 _lg)fI output - (effective cc)) Steady Tone Horns (G1 -P series) Percent of UL rating versus angle UL464 Average Peak : a 20 Vdc 76.7 89.5 91 24 Vdc 77.1 90 91.1 31 Vdc 77.2 90.4 91.6 45• / s Notes 1. All values shown are dBA measured at 10feet (3.01m). i � 2. UL464 values measured in reverberation room. 45. _\ � +s• 3. Average and Peak values are measured inanechoicchamber. -w .. • I5• o• EDWARDS SYSTEMS TECHNOLOGY Page 4 of 6 Literature Sheet #85001 -0573 Issue 1 Not to be used for installation purposes. For the most current literature end updates visit www.est.net. f3 u pa Do-3_ oos Specifications Table SIGA -270 SIGC -270F SIGA -270P Catalog Number SIGC -270B SIGC -270PB SIGA -278 Single Action -Two Stage Description Single Action - One Stage (Presignal) Double Action - One Stage - Addressing Requirements Uses 1 Module Address Uses 2 Module Addresses Uses 1 Module Address Operating Current Standby = 250pA Standby = 396pA Standby = 250pA Activated = 400pA Activated = 680pA Activated = 400pA Construction b Finish Diecast Zinc - Red Epoxy w /Aluminum markings Lexan - Red w/White markings Type Code Factory Set Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal) Storage and Operating Operating Temperature: 32°F to 120 °F (0°C to 49°C) Environment Storage Temperature: -4°F to 140°F (-20°C to 60°C) Humidity: 0 to 93% RH On -board Green LED - Flashes when polled LED Operation On -board Red LED - Flashes when in alarm Both LEDs - Glow steady when in alarm (stand- alone) Compatibility Use With: Signature Loop Controller Agency Listings UL, ULC (note 1), MEA, CSFM Note 1: SIGC -270F, SIGC -270B and SIGC -270PB are ULC listed only. Suffix "F" indicates French markings. Suffix "B" indicates English /French bilingual markings. Ordering Information Table Testing Er Maintenance Catalog Ship Wt. To test (or reset) the station simply open the station and operate the Number Description lbs (kg) exposed switch. The SIGA -270 series are opened with a tool; the One Stage Fire Alarm Station, SIGA -278 requires the key which is supplied with that station. SIGA -270 English Markings - UUULC Listed g g The station's automatic self-diagnosis identifies when it is defective SIGC -270F One Stage Fire Alarm Station, and causes a trouble message. The user - friendly maintenance . French Markings - ULC Listed program shows the current state of each Signature series device SIGC -270B One Stage Fire Alarm Station, and other pertinent messages. Single devices may be deactivated French /Englisn Markings - ULC Listed temporarily, from the control panel. Availability of maintenance Two Stage (Presignal) Fire Alarm Station, 1 (5) features is dependent on the fire alarm system used. SIGA -270P English Markings - UUULC Listed Scheduled maintenance (Regular or Selected) for proper system SIGC -270PB Two Stage (Presignal) Fire Alarm Station, operation should be planned to meet the requirements of the French /English Markings - ULC Listed Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and SIGA -278 Double Action (One Stage) Fire Alarm ULC CAN /ULC 536 standards. Station, English Markings - UUULC Listed ACCESSORIES 32997 GA Key w/Tag - for pre - signal station (CANADA ONLY) 276 -K2 GA Key - for pre - signal station (USA ONLY) 27165 12 Glass Rods - for SIGA -270 series .1 (.05) (CANADA ONLY) 270 -GLR 20 Glass Rods - for SIGA -270 series (USA ONLY) 276 -GLR 20 Glass Rods - for SIGA -278 series 276B-RSB Surface Mount Box, Red 1 (.6) - for SIGA pull stations 1 EDWARDS SYSTEMS TECHNOLOGY It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST. C 2001 EST Panted in U.S.A. Page 4 of 4 Literature Sheet #85001 -0279 Issue 6 Not to be used for installation purposes. Scheduled Events (Skeds) D9210 Access Control Module • Day -of -week or date of the year schedules Access can be granted from a Wiegand style access • Four holiday schedules of 365 days each control device (access reader) when connected to a D9210 Access Control Module. Access may also be granted from • Up to 64 scheduled events with 26 different functions a REQUEST TO EXIT or a REQUEST TO ENTER input. • Remotely programmable with User control capability The D9210 Access Interface Module provides for connec- from the command center tions of the access door point and the door strike. Up to The D7412's internal clock and calendar help the panel two D9210s can be incorporated on each system. Each operate individual scheduled events (Skeds). You can D9210 controls one door. program each Sked to perform a specific function (such as • Each access door can be configured independently from arm /disarm, relay control, point bypassing, etc.). Each the other doors. Sked is programmed for a time and either a day of the • The same alarm door contact point controls the access week schedule or a date of the year schedule. door and is part of the alarm system (the door does not The User can change the time for the Sked if the Sked is need to have double contacts). programmed for local time editing. Holiday schedules can • The door contact can be either normally open or be used to enable or disable individual Skeds during the normally closed and is used to reset the door strike time holiday periods. when the door either opens or closes depending upon programming. Fire Test • The door contact can terminate a programmable door In the Fire Test Mode, the D7412 suppresses reports to the entry buzzer (if used). receiver so you can test initiating and indicating devices • The door contact is shunted when valid access is being without transmitting alarms to the central station. When granted through the door. you put the D7412 in Fire Test Mode, the panel sends a report to the central station to indicate the start of the test. • An optional buzzer can be triggered prior to the end of a Test events then become "local only ". The command door shunt period to warn the user that a "door left open" center shows how many points are to be tested. condition is about to occur. Each time a device initiates an alarm, the programmed • The access point can be configured to generate an point text displays at the command center. The automatic alarm or a trouble (or have no response) when the door sensor reset feature of the Fire Test Mode allows you to is left open beyond the door shunt period. continue testing additional devices without time consuming • The reading of access cards, in addition to the granting trips to the command center to manually reset sensors. At of access, can control whether the system will disarm '' the end of the test, the command center displays the along with granting of access. number of untested points. You can also view the point text • The door strike can be programmed to be held open for each untested point. automatically during the disarm period and then auto - When you take the D7412 out of Fire Test Mode, the panel matically re lock when the area is armed. sends a report to the receiver indicating the completion of • The system can be configured to generate an alarm, a the test. trouble, (or have no response) depending upon the area's armed condition when the door is opened outside Combining Access Control with Security of an authorized access period. and Fire Detection • An option is provided that can control whether access granted conditions or no entry conditions send A combined system can help prevent false alarms by events to the log by door. making it easy to use just one system that controls • REQUEST TO ENTER and REQUEST TO EXIT can be security, access, and fire functions. programmed to shunt the door without activating the The access control features of the D7412 can deny access strike. during armed periods. It can also grant access only to certain authorized users depending on whether the area is master armed, perimeter armed, or disarmed. The alarm Specifications system can automatically disarm when designated General authorized users are granted access. The contractor shall furnish and install, where indicated on The D7412 can control two (2) Access Doors as part of the the plans, a Radionics D7412 Control /Communicator. The 75 intrusion and fire detection points. panel shall be listed by Underwriters Laboratories for You can use up to 396 Wiegand user identification devices NFPA 72 Applications. in the D7412 system. Up to four of the Wiegand user The D7412 shall support initiating and indicating modules devices can be associated with each of the 99 user and Radionics Command Centers. The D7412 Control/ names, passcodes and area authority levels. Communicator power supply shall provide 1.4 Amps of power for all processing functions and 12 VDC auxiliary requirements. © 1997 Radionics, Inc. D7412 Specification Sheet L826 P/N 34019D (10/97) 33 Application t2 aoo3 - ° O 5- (9 9 With intelligent 4D multisensor detectors, unwanted alarms suited for all applications. Normal detector spacing guidelines go down to nearly zero and the detection of all types of fire should be followed. increases to nearly 100 %. The European standard DIN EN 54 part 9 describes six standard test fires used to rate the SIGA -IPHS detectors are compatible only with EST's Signa- sensitivity of heat, ionization, and photoelectric smoke ture Loop Controller. detectors. No single sensing element is equally suitable for all test fires. The table below shows that the 4D detector is Type of Detector SIGA -IS SIGA -PS SIGA -HRS and SIGA -PHS SIGA -IPHS Test Fire Ion Photo SIGA -HFS Rate -of- Photo /Heat Ion /Photo /Heat Rise /Fixed Temp 3D 4D Open Wood optimum unsuitable optimum very suitable optimum Wood Pyrolysis suitable optimum unsuitable optimum optimum Smouldering Cotton very suitable optimum unsuitable optimum optimum Poly Urethane Foam very suitable very suitable suitable very suitable optimum n Heptane optimum very suitable very suitable optimum optimum Liquid Fire without unsuitable unsuitable optimum very suitable very suitable Smoke Specifications Table Catalog Number I SIGA -IPHS Agency Listings UL, ULC Ion Sensor (unipolar) 0.1351.1.0 Americium 241 Photo Sensor Light Scattering Principle Heat Sensor Alarms at 65 °F (35 °C) above ambient Storage and Operating Air Velocity Range: 0 to 500 ft/min (0 to 2.53 m /s) Environment Operating Temperature: 32 °F to 100 °F (0 °C to 38 °C) Storage Temperature: -4 °F to 140 °F (- 20 °Cto 60 °C) Humidity: 0 to 93% RH, Non - condensing Altitude: 6,000 ft. (1828m) above sea level maximum Sensitivity Range ULI /ULC - 0.67% to 3.70% obscuration /foot User Selected Alarm Most Sensitive: 1.0 % /ft. Sensitivity Settings More Sensitive: 2.0 % /ft. Normal: 2.5 % /ft. Less Sensitive: 3.0 % /ft. Least Sensitive: 3.5 % /ft. Pre -alarm Sensitivity 75% of Alarm Sensitivity Setting Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal) Operating Current Quiescent: 45µA @ 19 V Alarm: 45µA @ 19 V Emergency Stand -alone Alarm Mode: 18mA Pulse Current: 100µA (100 msec) During Communication: 9 mA maximum Construction & Finish High- Impact Engineering Polymer - White or Black Compatible Mounting Bases SIGA -SB and SIGA -SB4 Standard Base, SIGA -RB and SIGA -RB4 Relay Base, SIGA -IB and SIGA -1B4 Isolator Base LED Operation On -board Green LED - Flashes when polled On -board Red LED - Flashes when in alarm Both LEDs - Glow steady when in alarm (stand - alone) Compatible Remote Red LED (model SIGA -LED) Flashes when in alarm Compatibility Use With: SIGNATURE Loop Controller Address Requirements Uses 1 Device Address 85001 -0245 5of6Iss.5 Accessories All detector mounting bases have wiring terminals that are - when the detector enters the alarm state, the relay is accessible from the "room- side" after mounting the base to the energized. electrical box. The bases mount to North American 1 -gang boxes and to 3 -1/2" or 4" octagon boxes, 1 -1/2" Isolator Base SIGA -IB, SIGA -1B4 - This base includes a (38 mm) deep. They also mount to European BESA and built -in line fault isolator. A detector must be installed for it to 1 -gang boxes with 60.3 mm fixing centers. The SIGA -SB4, operate. The integral isolator relay is controlled by the SIGA -RB4, and SIGA -lB4 mount to North American 4" sq. detector or the loop controller. A maximum of 96 isolator electrical boxes in addition to the above boxes. They include bases can be installed on one circuit. The isolator base does the SIGA -TS Trim Skirt which is used to cover the "mounting not support the SIGA -LED Remote LED. ears" on the base. The isolator operates as follows: Standard Base SIGA - SB, SIGA - SB4 - This is the basic - a short on the line causes all isolators to open within 23 msec. mounting base for EST Signature Series detectors. The - at 10 msec intervals, beginning nearest the loop controller, the SIGA - LED Remote LED is supported by the Standard Base. isolators close to provide the next isolator down the line with power. Relay Base SIGA - RB, SIGA - RB4 This base includes a - when the isolator next to the short closes, it reopens within 10 msec. relay. Normally open or closed operation is selected during installation. The dry contact is rated for 1 amp (pilot duty) © In Class A operation, the process repeats beginning on the 30 Vdc. The relay's position is supervised to avoid other side of the loop controller. accidentally jarring it out of position. The relay base does not support the SIGA -LED Remote LED. Remote LED SIGA -LED - The remote LED connects to the SIGA -SB or SIGA -SB4 Standard Base only. It features a The relay is controlled by the detector and operates as North American size 1 -gang plastic faceplate with a white follows: finish and red alarm LED. - at system power -up or reset, the relay is de- energized. - when a detector is installed in the base with the power on, the SIGA - Trim Skirt - Supplied with 4" bases, it can also be relay energizes for 4 seconds, then de energizes. ordered separately to use with the other bases to help hide when a detector is removed from a base with the power on, surface imperfections not covered by the smaller bases. Use the relay is de energized. black model with SIGA - IPHSB. • fit. , .:.. .... ..... ... >. .E �. G» ... ........, ......:::. ::. ........ .. .: ..:.:, - :,,....::.. .... ... .... ... .....:.. ....... r::. ....... .. ;_::::;:; = • .:> ;..'s:: >': <::: >:.:. t >::::ri:.;!:..: ,;.r.. : >:.: >:. >:: °:_:r; a .i'Reta :.:E ;. ;Remote At&rmLEI) Ordering Information Table Catalog Number Description Carton Dims- Ship Wt. Inches (mm) lbs (kg) SIGA -IPHS Intelligent 4D Multisensor Detector - UL/ULC Listed 5 (127)w x 3.6 (91)h .5 (.23) SIGA -IPHSB Intelligent 4D Multisensor Detector (Black) - ULJULC Listed x 5 (127)d Accessories SIGA -SB Detector Mounting Base SIGA -SB4 4" Detector Mounting Base c/w SIGA -TS Trim Skirt SIGA -RB Detector Mounting Base w /Relay 6 (152)w x 1 (25)h x .2 (.09) SIGA -RB4 4" Detector Mounting Base w /Relay c/w SIGA -TS Trim Skirt 6 (152)d SIGA -IB Detector Mounting Base w /Fault Isolator SIGA -IB4 4" Detector Mounting Base w /Fault Isolator c/w SIGA -TS Trim Skirt SIGA -LED Remote Alarm LED 3.8 (97)w x 2.8 (71)h .2 (.09) x 6 (152)d SIGA -TS Trim Skirt (supplied with 4" bases) 6 (152)w x 1 (25)h x .1 (.04) SIGA -TSB Trim Skirt - Black (use with black detector) 6 (152)d It is our intention to keep the product information current and accurate We can not cover specific applications or anticipate all requirements All specifications are subject to change with- out notice. For more information or questions relative to this 85001 - 0245 Specification Sheet, contact EST. 6 of 6 Iss. 5 © 1999 EST Printed in U.S.A. • LOo O bi to Specifications Table SIGA -270 SIGC -270F SIGA -270P Catalog Number SIGC -270B SIGC -270PB SIGA -278 Single Action -Two Stage Description Single Action - One Stage ( Presignal) Double Action - One Stage Addressing Requirements Uses 1 Module Address Uses 2 Module Addresses Uses 1 Module Address Operating Current Standby = 250pA Standby = 396pA Standby = 250pA Activated = 400pA Activated = 680pA Activated = 400pA Construction b Finish Diecast Zinc - Red Epoxy w /Aluminum markings Lexan - Red w/White markings Type Code Factory Set Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal) Storage and Operating Operating Temperature: 32°F to 120 °F (0°C to 49°C) Environment Storage Temperature: -4°F to 140°F (-20°C to 60°C) Humidity: 0 to 93% RH On -board Green LED - Flashes when polled LED Operation On -board Red LED - Flashes when in alarm Both LEDs - Glow steady when in alarm (stand - alone) Compatibility Use With: Signature Loop Controller Agency Listings UL, ULC (note 1), MEA, CSFM Note 1: SIGC -270F, SIGC -270B and SIGC -270PB are ULC listed only. Suffix "F" indicates French markings. Suffix "B" indicates English /French bilingual markings. ;V Ordering Information Table Testing Er Maintenance To test (o r reset) the station simply open the station and operate C Shi Wt P Y the P P Description exposed switch. The SIGA -270 series are opened with a tool; the Ai ' Number lbs (kg) P P SIGA -278 requires the key which is supplied with that station. SIGA -270 One Stage Fire Alarm Station, a� .. English Markings - UUULC Listed The station's automatic self- diagnosis identifies when it is defective One Stage Fire Alarm Station, and causes a trouble message. The user - friendly maintenance SIGC -270F French Markings - ULC Listed g program shows the current state of each Signature series device SIGC -270B One Stage Fire Alarm Station, and other pertinent messages. Single devices may be deactivated French /Engi,sn Markings - ULC Listed temporarily, from the control panel. Availability of maintenance Two Stage (Presignal) Fire Alarm Station, 1 (.5) features is dependent on the fire alarm system used. SIGA -270P English Markings - UUULC Listed Scheduled maintenance (Regular or Selected) for proper system SIGC -270PB Two Stage ( Presignal) Fire Alarm Station, operation should be planned to meet the requirements of the French /English Markings - ULC Listed Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and SIGA -278 Double Action (One Stage) Fire Alarm ULC CAN /ULC 536 standards. Station, English Markings - UUULC Listed ACCESSORIES 32997 GA Key w/Tag - for pre - signal station (CANADA ONLY) 276 -K2 GA Key - for pre - signal station . (USA ONLY) 27165 12 Glass Rods - for SIGA -270 series .1 (.05) (CANADA ONLY) 270 -GLR 20 Glass Rods - for SIGA -270 series (USA ONLY) 276 -GLR 20 Glass Rods - for SIGA -278 series 276B-RSB Surface Mount Box, Red 1 (.6) - for SIGA pull stations EDWARDS SYSTEMS TECHNOLOGY It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST. m 2001 EST Printed in U.S.A. Page 4 of 4 Literature Sheet #85001 -0279 Issue 6 Not to be used for installation purposes. tilAAVO 03 - 00 5 ( Specifications Housing Red or white textured UV stabilized, color impregnated engineered plastic. Exceeds 94V -0 UL flammability rating. Lens Optical grade polycarbonate (clear) Mounting Flush mount: 2'/2 inch (64 mm) deep one -gang box (indoor wall mount only) Surface mount: EST model 27193 surface mount box, wiremold box, or equivalent surface -mount box • With optional trim plate: One -gang, two -gang, four -inch square, octagonal, or European single -gang box Wire connections Screw terminals: single input for both horn and strobe. #18 to #12 AWG (0.75 mm to 2.5 mm wire size Operating environment Indoor only: 32 -120 °F (0 -49 °C) ambient temperature. 93% relative humidity Agency UL 1971, UL 1638, UL 464, ULC S525, ULC S526, CE, FCC, (MEA, FM, CSFM pending). listings /approvals (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.) Dimensions (HxWxD) Signal: 4 -1/2 x 2 -3/4" x 13/16" (113 mm x 68 mm x 21 mm) Trimplate: 5 (127 mm); Height - 5 -7/8 (149 mm); Depth -'/2" (13 mm) G1 -HD series temporal -tone horns: non - coded, filtered 16 -33 Vdc or unfiltered 16 -33 Vdc FWR (or coded when horn set to steady tone) Operating voltage G1 -HDVM series temporal -tone horn - strobes: non- coded, filtered 16 -33 Vdc or unfiltered 16 -33 Vdc FWR (or coded (audible NAC only) when used with optional G1M Genesis Signal Master) G1 -VM series strobes: non - coded, filtered 16 - 33 Vdc or unfiltered 16 -33 Vdc FWR G1 -P series steady -tone horns: coded or non - coded, filtered 20 -31 Vdc or unfiltered 20 -27 Vfwr Strobe output rating UL 1971, UL 1638, ULC S526: selectable 15 cd, 30 cd, 75 cd, or 110 cd output G1 -VM strobes and G1 -HDVM series temporal -tone horn - strobes: one flash per second synchronized with Strobe flash rate optional G1M Genesis Signal Master indefinitely within 10 milliseconds (or self- synchronized within 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) Temporal setting (private mode only): synchronized to temporal output of horns on same circuit Compatible synchronization G1M, G1M -RM, SIGA -CC1S, SIGA -MCC1S modules* G1 -HD temporal -tone horns and G1 -HDVM series temporal -tone horn - strobes: temporal rate synchronized Horn pulse rate with optional G1M Genesis Signal Master indefinitely within 10 milliseconds (or self- synchronized within 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) G1 -P steady -tone horns: continuous, steady tone only Temporal audible pattern Y sec ON, 1 /2 sec OFF, 1/2 sec ON, /2 sec OFF, Y sec ON, 11 sec OFF, then repeat cycle *Not compatible with G 1 -P Series horns. dBAoutput Average Sound Output (dBA) ' Temporal Horns, Horn - strobes (G1 -HD, G1 -HDVM series) - High dB Setting (High dB setting, anechoi,,, 24V, measured at 10ft) oo- ,p „ ,W 90 °, h N b ,J UL464 Average Peak - * m m " �' Temporal Steady Temporal /Steady Temporal /Steady 16 Vdc 81.4 85.5 91.4 94.2 75• 75• 24 Vdc 84.4 88.6 94.5 97.6 33 Vdc 86.3 90.4 96.9 99.5 6a d5 /' 6 "• Temporal Horns, Horn - strobes (G1 -HD, G1 -HDVM series) - Low dB Setting ,s• UL464 Average Peak J0 JO Temporal Steady Temporal /Steady Temporal /Steady - .15• 0 - 15 16 Vdc 76.0 80.1 86.3 89.2 24 Vdc 79.4 83.5 89.8 92.5 33 Vdc 82.1 86.5 92.5 95.3 I _,i h f O..ITput - (effective cc!) Steady Tone Horns (G1 - series) Percent of UL rating versus angle UL464 Average Peak 20 Vdc 76.7 89.5 91 24 Vdc 77.1 90 91.1 31 Vdc 77.2 90.4 91.6 75' /' %5 Notes \. 2 .60• 60• 1. All values shown are dBA measured atlOfeet (3.01m). L J 2. UL464 values measured in reverberation room. ---- \' 45• 3. Average and Peak values are measured in anechoic chamber. 30 30• 15' -- IS• 0• EDWARDS SYSTEMS TECHNOLOGY Page 4 of 6 Literature Sheet #85001 -0573 Issue 1 Not to be used for installation purposes. For the most current literature and updates visit www.est.net.