Correspondence FILE COPY
„
June 9, 2003
CITY OF TIGARD
OREGON
Integumend LLC
10215 SW Hall Boulevard
Portland, OR 97223
RE: NEW COMMERCIAL BUILDING
Project Information
Site Permit: SIT2003 -00013 Construction Type: V N
Tenant Name: Integumend Occupancy Type: B
Address: 10215 SW Hall Boulevard Occupant Load: NA
Area: 9,348 Sq Ft Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following.
EROSION
• Erosion control measures shall be in place prior to excavation or grading.
FIRE
• The private fire service main shall be at least 30 inches below grade.
• The private fire service main shall be flushed thoroughly before connection to the
system riser in order to remove foreign materials that might have entered the main
during the course the installation. The flow rate shall not be less than the water
demand rate of the system.
• All piping shall be inspected prior to backfill.
ACCESSIBILITY
• Accessible parking spaces, access aisles and accessible route to public way shall be
sloped as indicated on sheet 2/5
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of - . nsmittal. The letter of transmittal assists the City of
Tigard in tracking and proces '. 1e doc. e
Respectfu ,
an lal•
Senior`. Examiner
PILE COPY
r a
1 �uoNll000," 6
May 23, 2003= ` -'^'�'
CITY OF TIGAR®
OREGON
Integumend LLC
10215 SW Hall Boulevard
Portland, OR 97223
RE: NEW COMMERCIAL BUILDING
Project Information
Site Permit: SIT2003 -00013 Construction Type: V - N
Tenant Name: Integumend Occupancy Type: B
Address: 10215 SW Hall Boulevard Occupant Load: NA
Area: 9,348 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following.
• Provide details for the underground fire sprinkler supply. See attached copy of
NFPA 24 section 1 -4.2 for the items necessary for a plan review.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfu • ,
. n '•
Senio .' ans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
FILE CCPY
May 19, 2003
Integumend, LLC
9495 SW Locust
Portland, OR 97223
RE: INTEGUMEND @ HALL BOULEVARD
Project Information
Site Permit: SIT2003 -00013 Construction Type: NA
Tenant Name: Integumend Occupancy Type: B
Address: 10215 SW Hall Blvd Occupant Load: NA
Area: 9,342 Sq Ft Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans have been reviewed and the following information is required
prior to the issuance of a Site Permit:
• Several combinations of plan sets were submitted. Is the Ll sheet the plan intended to
be used for "Site Work Review "?
• The "SITE WORK PERMIT CHECK LIST" was not filled out correctly. I have
enclosed a copy of the checklist and instructions. Please complete it and resubmit it to
the City of Tigard.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and p ocessing the documents.
Respect 1
rian : . oc
Senior Plans Examiner