January 26, 2006
CITY OF TIGARD
OREGON
Lasher Design
Todd Lasher
5632 N Atlantic Ave
Portland, OR 97217
RE: T I -2 HOUR WALL/FLOOR CEILING & BATHROOMS - REVIEW
Project Information
Building Permit: BUP2006 -00057 Construction Type: II B
Tenant Name: The Light -Up Co. Occupancy Type: S2B
Address: 11225 SW Greenburg Rd. Occupant Load: 27
Area: 7,816 sq ft Stories: 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The submitted plans are
approved subject to the following conditions.
1. All exit doors shall be openable from the inside without the use of a key or any
special knowledge or effort. 1003.3.1.8 OSSC
2. The main exit shall be provided with signage indicating "THIS DOOR MUST
REMAIN UNLOCKED DURING BUSINESS HOURS" Section 1003.3.1.8 OSSC
3. Provide one 2 -A rated fire extinguisher in the new area. The extinguisher shall be
located so that no usable space has a distance greater than 75 feet to the extinguisher.
OFC 906.3
4. Live Loads Posted: The live loads for which each floor has been designed shall be
conspicuously posted by the owner in that part of each story in which they apply,
using durable metal signs, and it shall be unlawful to remove or deface such notices.
The occupant of the building shall be responsible for keeping the actual load below
the allowable limits. 1607.3.5 OSSC
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
•
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully,
Val He e
Senior Plans Examiner