Loading...
Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. ® Tigard, OR 97223 ' e r - March 3, 2008 t OFFICE COPY RE: MECHANICAL REFRIGERATION IrG Project Information Building Permit: MEC2008 -00084 Construction Type: 5 -B Tenant Name: Good Neighbor Center Occupancy Type: B Address: 11130 SW Greenburg Rd. Occupant Load: NA The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. 1) Prefabricated refrigeration panels installed in Oregon shall bear one Oregon insignia of compliance located on the exterior side of the panel located nearest the door prior to final inspection. 2) Every refrigerant - containing part of every system that is erected on the premises shall be tested and proved tight after complete installation, and before operation. Tests shall include both the high and low- pressure sides of each system and shall not be pressured down until verification of the City of Tigard Building Inspector. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. .Respectfully an Nelson, Senior Plans Examiner (503)718 -2436 dann @tigard -or.gov Phone: 503.639.4171 ® Fax: 503.684.7297 ® www.tigard- or.gov • TTY Relay: 503.684.2772