Loading...
Report N SYSTEM /4 - 3 Se- K BALANCE NEBB TEST REPORT #2007 -005 PROJECT: Lincoln Tower 1 Stairwell Pressurization Fans A_kCHT.: -- ENGR.: -- DATE: 22 January 2007 Vol w l* 41 Z WILum' c. IIEU EEN n CERTIFICATE 24 1170 REPUBLICAN STREET 1500 NE SANDY BOULEVARD, SUITE #1 PO Box 24327 MPO SEATTLE, WASHINGTON 98109 PORTLAND, OREGON 97232 BARRIGADA, GUAM 96921 PHONE (206) 621 -1810 PHONE (503) 235-8924 PHONE (671) 637 -7810 FAX (206) 343 -9820 FAX (503) 235 -8925 FAX (671) 637 -7842 NATIONAL ENVIRONMENTAL BALANCING BUREAU Panes 1 of R Neudorfer Engineers, Inc Portland, Oregon LINCOLN TOWER 1 Fire & Life Safety testing was conducted on January 18, 2007 in Lincoln Tower 1 under the following conditions: • Building temperature = 70 • Outside temperature = 34 °F • Sunny and cold • Humidity approximately 37 Final fan data set points are as follows: • Stairwell #1 Pressurization: o The VFD speed must be set to 60hz o The pressure to atmosphere in stairwell #1 when the fan running = +0.26 "wg when the door at the bottom of the stairs is closed. • Stairwell #2 Pressurization: o The VFD must be set to 60hz o The pressure to atmosphere in Stairwell #2 when the fan is running = +0.35 "wg when the door at the bottom of the stairs is closed. • Stairwell #3 Pressurization: o The VFD must be set to 49hz o The pressure to atmosphere in Stairwell #3 when the fan running = +0.28 "wg when the door at the bottom of the stairs is closed. • Stairwell #4 Pressurization: o The VFD speed must be set to 52hz o The pressure to atmosphere in stairwell #4 when the fan running = +0.26 "wg when the door at the bottom of the stairs is closed. The stairwell to corridor differential pressures were set as close as possible to the 0.25" to 0.35 "wg. The final pressures listed below are based upon a balance that considered maximum door pulls of 30Ibs, minimum differential pressure from the stairwell to the corridor of 0.05 "wg and the suggested differential between stairwells and corridor of 0.25" to 0.35 "wg In addition to the stairwell shaft spring actuated isolation damper, and a barometric dampers are installed in each stairwell shaft relief opening. When the system is alarmed, the isolation damper opens and the first barometric damper opens to relieve a minimum of 2500cfm. As the shaft pressure at the top increases to the point that the differential across the top floor stairwell to the corridor reaches approximately 0.35 "wg, the second barometric damper begins to relieve excess shaft pressure. The barometric dampers were adjusted to maintain maximum shaft pressure while not exceeding the 30Ib door pull specification. Pans 7 of R The following Table-1 shows the door pull, and differential pressure relationship between the corridor and stairwell. Table -1 . 3 • - S ta'irwell_#23 .# r Door Door Door Door . Floor dP Pull lbs Floor dP Pull lbs 5 0.26" 18 5 0.26" 16.5 3 0.35" 19 3 0.24" 16 1 0.26" 15 1 0.13" 16 t "• f � t s r irr ,Y tt a pans o R The following Table -1 shows the door pull, and differential pressure relationship between the corridor and stairwell. Table -1 _ � �.{.,. , Stairwell:. # :2,;�,3::T� . ,�, � , ... Door Door �' � ,,. Door Door Floor dP Pull lbs Floor dP Pull lbs 5 0.28" 21 5 0.27" 18 „ 0 . .4.. �,' 0 27 . f� , , ,N 1R9.. n..,. � �,, n $ , _ }, Z 3 0.27" 23 3 0.27" 19 1 0.27" -- 1 0.27" 25 -. 4 Y rt f .. - a... ". >�_ 'k�.: ... ..J _ , ..�,r n,.. �.. h,. _ _ .•�r�, -" .. a, v =.. ., ) -�, ..,, ... .� t,t4 _o. „�.., -. , . %.`� .Y _- }cYa ai.� .,.. .n.._.. �.. .;„l�.i k �. "n .._e, *_. .A - _.._ - .- .�" v •�. .'s ,.Y'. . .s .,.. ^.Y _a v. � A" __ .. -'�. ^ 4 - - � • b � i ;;; P':` �'r „'.' j -� ; C'4 f r X 'r :.. .. ,-..' l' -- .et•'9 , - a.. -Y. -, •i +a,�l':ti e;,.'.Y. -, %' _: � k.a � ':' ^. ,, c ..., .'s. � �;3 w�, � ..'� .... - ... ,.. _ . ...- 4. -... !,Y a �. . -. 1. No access to stairwells from within the ground floor lobby. 2. Ground level door pull measurements were not taken because doors push outward. 3. Pressure relationship between ground floor lobby and elevator shaft in primary recall mode. pan: 4 of f2 N NEUDORFER ENGINEERS, INC. Consulting Engineers 1500 NE Sandy Blvd AIR APPARATUS Portland, Oregon 97232 (503) 235 -8924 Fax (503) 235 -8925 TEST REPORT PROJECT Lincoln Tower 1 StainvellPressurizaion SYSTEM/UNIT Stairwell #1 LOCATION /ZONE UNIT DATA MOTOR DATA Make Cook Make /Frame Baldor 184T Model No. 225CPS H.P/RPM 5.0 1750 Serial Number 034S908684 Volts/Phase/Hertz 460 3 60 Arr. /Class -- / -- F.L. Amps /S.F. 6.6 1.15 Discharge UP Make Sheave Maska Make Sheave MASKA Sheave Dia. /Bore 2VP50 1 1/8" Sheave Dia./Bore 2AK56 H 1 7/16" Sheave 0 Distance 20.0" M No. Belts /Size (2) A51 Rotation OK No. Filters /Size -- / -- Belt Tension/Alignment OK OK Overload Amps 'LEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL, Total CFM (1) (1) Discharge S.P. -- +0.75" Total S.P. -- 0.78" Suction S.P. -- - 0.03" Total E.S.P. -- -- Reheat Coi1AS.P. -- -- Fan RPM -- 1345 Cooling Coi1AS.P. -- -- Preheat- Coi1AS.P. -- -- Motor Volts 460 460 (2) Filters AS.P. -- -- Motor Amps 6.6 5.9 (2) Outside Air CFM -- -- Vortex Damp. Position -- -- Return Air CFM -- -- Out Air Damp. Position -- -- Exhaust Air CFM -- -- Ret Air. Damp. Position -- -- Motor to Retract -- -- Motor to Extend -- -- REMARKS: (1) Flow was just measured for pressurization. (2) Amperage and voltage were read from the VFD. (3) Fan is tested and set at 60 Hz. TEST DATE READINGS BY NATIONAL ENVIRONMENTAL BALANCING BUREAU Panes c of R N NEUDORFER ENGINEERS, INC. Consulting Engineers 1500 NE Sandy Blvd AIR APPARATUS Portland, Oregon 97232 (503) 235 -8924 Fax (503) 235 -8925 TEST REPORT PROJECT Lincoln Tower 1 Stairwell Pressurization SYSTEM/UNIT Stairwell #2 LOCATION /ZONE UNIT DATA MOTOR DATA Make Cook Make/Frame Baldor 184T Model No. 225CPS _ H.P/RPM 5.0 1750 Serial Number 034S908684 Volts/Phase/Hertz 460 3 60 Arr. /Class -- / -- F.L. Amps /S.F. 6.6 1.15 Discharge UP Make Sheave Maska Make Sheave MASKA Sheave Dia./Bore 2VP50 1 1/8" Sheave Dia./Bore 2AK56 H 1 7/16" _ Sheave 0 Distance 20.0" _ _ _ No. Belts /Size (2) A51 Rotation OK No. Filters /Size -- / -- Belt Tension/Alignment OK OK Overload Amps TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL Total CFM (1) (1) Discharge S.P. -- +0.68" Total S.P. -- 0.71" Suction S.P. -- -0.03" Total E.S.P. -- -- Reheat Coi1AS.P. -- -- Fan RPM -- 1345 Cooling Coi1AS.P. -- -- Preheat CoilAS.P. -- -- Motor Volts 460 460 (2) Filters AS.P. -- -- Motor Amps 6.6 5.5 (2) Outside Air CFM -- -- Vortex Damp. Position -- -- Return Air CFM -- -- Out. AirDamp. Position -- -- Exhaust Air CFM -- -- Ret. Air. Damp. Position -- -- Motor to Retract -- -- Motor to Extend -- -- REMARKS: (4) Flow was just measured for pressurization. (5) Amperage and voltage were read from the VFD. (6) Fan is tested and set at 60 Hz. 'ZEST DA'Z'E Jan 2007 READINGS BY TD NATIONAL ENVIRONMENTAL BALANCING BUREAU Pane h of R ,_ . ,.„ N NEUDORFER ENGINEERS, INC. Consulting Engineers 1500 NE Sandy Blvd AIR APPARATUS Portland, Oregon 97232 (503) 235 -8924 Fax (503) 235 -8925 TEST REPORT PROJECT Lincoln Tower 1 Stairwell Pressurization SYSTEM /UNIT Stairwell #3 LOCATION /ZONE UNIT DATA MOTOR DATA Make Cook Make/Frame Baldor 184T Model No. 225CPS H.P/RPM 5.0 1750 Serial Number 034S908684 Volts/Phase /Hertz 460 3 60 Arr. /Class -- / -- F.L. Amps /S.F. 6.6 1.15 Discharge UP Make Sheave Maska Make Sheave MASKA Sheave Dia./Bore 2VP50 1 1/8" Sheave Dia./Bore 2AK56 H 1 7/16" Sheave 0 Distance 20.0" No. Belts /Size (2) A51 Rotation OK No. Filters /Size -- / -- Belt Tension/Alignment OK OK Overload Amps TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL Total CFM (1) (1) Discharge S.F. -- +0.30 Total S.P. -- 0.33" Suction S.P. -- - 0.03" Total E.S.P. -- -- Reheat CoilAS.P. -- -- Fan RPM -- 1010 Cooling CoilAS.P. -- -- Preheat .CoilAS.P. -- -- Motor Volts 460 460 (2) Filters AS.P: -- -- Motor Amps 6.6 5.0 (2) Outside Air CFM -- -- Vortex Damp. Position -- -- Return Air CFM -- -- Out Air Damp. Position -- -- Exhaust Air CFM -- -- Ret Air. Damp. Position -- -- Motor to Retract -- -- Motor to Extend -- -- REMARKS: (7) Flow was just measured for pressurization. (8) Amperage and voltage were read from the VFD. (9) Fan is tested and set at 45 Hz. 'LEST DATE Jan 2007 READINGS BY TD NATIONAL ENVIRONMENTAL BALANCING BUREAUNATIONAL ENVIRONMENTAL BALANCING BUREAU PAnP7nfR N NEUDORFER ENGINEERS, INC. Consulting Engineers 1500 NE Sandy Blvd AIR APPARATUS Portland, Oregon 97232 (503) 235 -8924 Fax (503) 235 -8925 TEST REPORT PROJECT Lincoln Tower 1 Stilwell Pressurization SYSTEM /UNIT Stairwell #4 LOCATION /ZONE UNIT DATA MOTOR DATA Make Cook Make /Frame Baldor 184T Model No. 225CPS H.P/RPM 5.0 1750 Serial Number 0345908684 Volts/Phase/Hertz 460 3 60 Arr. /Class -- / -- F.L. Amps /S.F. 6.6 1.15 Discharge UP Make Sheave Maska Make Sheave MASKA Sheave Dia./Bore 2VP50 1 1/8" Sheave Dia./Bore i 2AK56 H 1 7/16" Sheave 0 Distance 20.0" No. Belts /Size (2) A51 Rotation OK _ No. Filters /Size -- / -- Belt Tension/Alignment OK ^ OK Overload Amps TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL Total CFM (1) (1) Discharge S.P. -- +1.06" Total S.P. -- 1.09" Suction S.P. -- - 0.03" Total E.S.P. -- -- Reheat CoilAS.P. -- -- Fan RPM -- 1165 Cooling Coi1OS.P. -- -- Preheat CoilAS.P. -- -- Motor Volts 460 460 (2) Filters AS.P. -- -- Motor Amps 6.6 5.5 (2) Outside Air CFM -- -- Vortex Damp. Position -- -- Return Air CFM -- -- Out, AirDamp. Position -- -- Exhaust Air CFM -- -- Ret Air. Damp. Position -- -- Motor to Retract -- -- Motor to Extend -- -- REMARKS: (10) Flow was just measured for pressurization. (11) Amperage and voltage were read from the VFD. (12) Fan is tested and set at 52Hz. TEST DA'Z'E Jan 2007 READINGS BY TD NATIONAL ENVIRONMENTAL BALANCING BUREAU PanaRnfR