Correspondence August 8, 2006
rA
CITY OF TIGARD
Capitol Electric Company OREGON
Dan Wilson
11401 NE Marx St
Portland, OR 97220
RE: FIRE ALARM SYSTEM MODIFICATION - REVIEW
Project Information : HORN STROBES
Building Permit BUP2006 -00369 Construction Type: 1 -B
Tenant Name: K -Force Occupancy Type: B
Address: 10300 SW Greenburg Rd. Stories: 5
Hazard: Light
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition,
Oregon Fire Code (OFC) 2004 edition and NFPA 72. The submitted plans are approved subject to the
following.
TESTING- NFPA 72 Chapter 10, OFC 901.5, 903.5
1. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence
of the building official and fire code official. All functions of the system or alteration shall be tested.
2. The permittee shall provide written certification to the Fire Chief that the system has been installed in
accordance with the approved plans and specifications. A copy of the completed form shall be
maintained on the premises and made available to the Fire Chief.
3. Sprinkler systems shall be tested and maintained in accordance with Oregon Fire Code.
POWER- NFPA 72 section 4.4.1.2, 4.4.7.3, OFC 907.5
4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and
connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to
authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT
CONTROL- 907.5 OFC
5. All power supplies shall be installed in conformity with NFPA 70.
6. All primary and secondary power supplies shall be monitored for the presence of voltage at the point of
connection to the system. Failure of either supply shall result in a trouble signal in accordance with
4.4.3.5. The trouble signal also shall be visually and audibly indicated at the protected premises.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
VISUAL ALARMS- NFPA 72 — chapter 5 & 7, OSSC chapter 9 & 11
9. Visual alarms shall be located not less than 80 inches and not more than 96 inches above floor level.
When a low ceiling exists, the visual alarm shall be mounted within the dimensions stated above and at
least 6 inches below the ceiling. No place in a room shall be more than 50 feet from a visual signal.
10. Visual signal appliances shall be provided in the building in each of the following areas:
• Restrooms and any other general use area (e.g., meeting rooms)
• Hallways/Corridors
• Lobbies
• Common use areas.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained
on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of
construction. 106.3.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such
a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed City of
Tigard, Letter of TransmittaL The letter of transmittal assists the City of Tigard in tracking and
processing the documents.
Respectfully,
)$
Val Henzel,
Senior Plans Examiner
- NAC EOL VOLTAGE CALCULATION
CAPITOL ELECTRIC CO., INC.
(503) 255 -9488 Office
(503) 255 -1966 Fax
Job Name: One Lincoln
Job Address: 10300 SW Greenburg Road Tigard, OR 97223
Job Number: Conductor Wire Guage I 14 I
Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) I 3.07
Date: 8/1/2006
Cable Length In Feet (source to end of line) I 302 I
Total Circuit Current I 1.051
j Nominal System Voltage I 20.4 I
Panel Description: Silent Knight 5495 Power E, MI Minimum Device Voltage I 16 I
Panel No.: NAC 2.1 (West)
Output No.: 1 `) . 1 006 Point To Point Method EOLv 19.22
` � , SD Circuit Within Limits ? YES
• NAC Devices Mfg By: Wheelock cvN .. \ A Ask
Still-DII4G End Of Line Method EOLv 18.45
Circuit Within Limits ? YES
Load Centering Method EOLv ( 19.43
Circuit Within Limits ? I I YES
Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At
No. Rating Current Previous Device Device
R ar �+. ( Feet )
_
e!
- K- Force, Suite 230 RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 70 19.95
2 K- Force, Suite 230 AS- 24MCW -FW (75) H/S WHT -M 75 Cd 0.190 26 19.79
3 K- Force, Suite 230 AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 7 19.76
4 K- Force, Suite 230 RSS- 24MCW -FW (15) STB WHT 15 Cd 0.060 22 19.66
5 K- Force, Suite 230 AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 16 19.59
6 K- Force, Suite 230 RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 23 19.51
7 K- Force, Suite 230 AS- 24MCW -FW (30) H/S WHT -M 30 Cd 0.110 16 19.46
8 K- Force, Suite 230 RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 26 19.39
9 K- Force, Suite 230 AS- 24MCW -FW (30) H/S WHT -M 30 Cd 0.110 22 19.34
10 K- Force, Suite 230 , AS- 24MCW -FW (110)H /S WHT -M 110 Cd 0.253 74 19.22
11 19.22
12 19.22
13 19.22
14 19.22
15 19.22
16 19.22
17 19.22
18 19.22
19 19.22
20 19.22
Linc -1, NAC 2.1 EOLv Calc- West.xls OUTPUT 1
NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO., INC.
(503) 255 -9488 Office, (503) 255 -1966 Fax
JOB NAME: One Lincoln
ADDRESS: 10300 SW Greenburg Road Tigard, OR 97223 DATE: 8/1/06
PANEL DESCRIPTION: NAC 2.1 (West) PREPARED BY: Dan Wilson
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
NAC EXTENDER
Silent Knight 5495 NAC Panel 1 0.075 0.075 0.175 0.175
CIRCUIT # 1
0.000
Wheelock AS- 24MCW -FW 110 Cd H/S (M) 1 0.253 0.253
Wheelock AS- 24MCW -FW 75 Cd H/S (M) 1 0.190 0.190
Wheelock AS- 24MCW -FW 30 Cd H/S (M) 2 0.110 0.220
Wheelock AS- 24MCW -FW 15 Cd H/S (M) 2 0.074 0.148
Wheelock RSS- 24MCW -FW 75 Cd Strobe 0.165 0.000
Wheelock RSS - 24MCW -FW 30 Cd Strobe 0.092 0.000
Wheelock RSS - 24MCW -FW 15 Cd Strobe 4 0.060 0.240
Wheelock AH -24 -W HORN (H) 0.080 0.000
.. ... TOTAL 1.051
CIRCUIT # 2 ;42414: t _
0.000
0.000
0.000
0.000
0.000
0.000
0.000
•
0.000
0.000 TOTAL 0.000
CIRCUIT # 3
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
._. _ TOTAL 0.000
CIRCUIT # 4
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
TOTAL 0.000
Linc -1, NAC 2.1 Batt Calc- West.xls Page 1 of 2
NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO., INC.
(503) 255 -9488 Office, (503) 255 -1966 Fax
JOB NAME: One Lincoln
ADDRESS: 10300 SW Greenburg Road Tigard, OR 97223 DATE: 8/1/2006
PANEL DESCRIPTION: NAC 2.1 (West) PREPARED BY: Dan Wilson
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
AUXILIARY DEVICES a1 _ 3 f` WAVAV
0.000 0.000
0.000 0.000
0.000 0.000
TOTAL 0.000
STANDBY TOTAL CURRENT: ( 0.075
STANDBY HOURS: 24
STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT I 1.051
ALARM TOTAL CURRENT: I 1.226
ALARM MINUTES: 5
ALARM AMP HOURS: 0.102
TOTAL CALCULATED AMP HOURS 1.902
APPLIED SAFETY FACTOR 1.15
MINIMUM AMP HOURS REQURED 2.187
SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7 AMP HOUR BATTERIES
Linc -1, NAC 2.1 Batt Calc- West.xls Page 2 of 2
Capitol
Electric Co•, Inc.
August 1, 2006
NOISING maws
ClE1V011 AO ADO
Plans Examiner 0 NV City of Tigard 9UUZ
Building Services u
13125 SW Hall Blvd. a3/ p X1303®
Tigard, OR 97223
Re: Tenant Fire Alarm System Design
K -Force Tenant Improvement
One Lincoln Center, Suite 230
10300 SW Greenburg Road
Tigard, OR 97223
Please find attached a building permit application, Tri- County Commercial Application
Checklist, two sets of plans, calculations, and product submittals for the fire alarm tenant
improvements at the address shown above.
This building has an existing fire alarm system. ADA synchronized notification devices
will be installed in the tenant space in common use and general use areas. We will pre-
test new devices before requesting a final inspection.
Please call if you have questions or comments.
Respectfully,
Dan Wilson
Project Manager /Estimator
Fire /Life Safety Division
Capitol Electric Company, Inc.
(503) 255 -9488
NICET Level IV, Fire Alarm Systems #104512