Correspondence August 11, 2006 4J I
CITY OF TIGARD
Capitol Electric Company OREGON
Dan Wilson
11401 NE Marx St
Portland, OR 97220
RE: FIRE ALARM SYSTEM MODIFICATION - REVIEW
Project Information : HORN STROBES
Building Permit BUP2006 -00368 Construction Type: 1-B
Tenant Name: Nation Wide Occupancy Type: B
Address: 10300 SW Greenburg Rd.# 470 Stories: 5
Hazard: Light
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition,
Oregon Fire Code (OFC) 2004 edition and NFPA 72. The submitted plans are approved subject to the
following.
TESTING- NFPA 72 Chapter 10, OFC 901.5, 903.5
1. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence
of the building official and fire code official. All functions of the system or alteration shall be tested.
2. The permittee shall provide written certification to the Fire Chief that the system has been installed in
accordance with the approved plans and specifications. A copy of the completed form shall be
maintained on the premises and made available to the Fire Chief.
3. Sprinkler systems shall be tested and maintained in accordance with Oregon Fire Code.
POWER- NFPA 72 section 4.4.1.2, 4.4.7.3, OFC 907.5
4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and
connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to
authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT
CONTROL- 907.5 OFC
5. All power supplies shall be installed in conformity with NFPA 70.
6. All primary and secondary power supplies shall be monitored for the presence of voltage at the point of
connection to the system. Failure of either supply shall result in a trouble signal in accordance with
4.4.3.5. The trouble signal also shall be visually and audibly indicated at the protected premises.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
VISUAL ALARMS- NFPA 72 — chapter 5 & 7, OSSC chapter 9 & 11
9. Visual alarms shall be located not less than 80 inches and not more than 96 inches above floor level.
When a low ceiling exists, the visual alarm shall be mounted within the dimensions stated above and at
least 6 inches below the ceiling. No place in a room shall be more than 50 feet from a visual signal.
10. Visual signal appliances shall be provided in the building in each of the following areas:
• Restrooms and any other general use area (e.g., meeting rooms)
• Hallways/Corridors
• Lobbies
• Common use areas.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained
on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of
construction. 106.3.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such
a position as to be plainly visible and legible from the street or mad fronting the property.
When submitting revised drawings or additional information, please attach a copy of the endosed City of
Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and
processing the documents.
Respectful ,
c f-17/* -fr A l .c . /
Val Menzel,
Senior Plans Examiner
Capitol
Electric Co•, Inc.
Eta
2 2006
3UJLDING Division/
August 1, 2006
Plans Examiner
City of Tigard
Building Services
13125 SW Hall Blvd.
Tigard, OR 97223
Re: Tenant Fire Alarm System Design
Nationwide Tenant Improvement
One Lincoln Center, Suite 470
10300 SW Greenburg Road
Tigard, OR 97223
Please find attached a building permit application, Tri- County Commercial Application
Checklist, two sets of plans, calculations, and product submittals for the fire alarm tenant
improvements at the address shown above.
This building has an existing fire alarm system. ADA synchronized notification devices
will be installed in the tenant space in common use and general use areas. We will pre-
test new devices before requesting a final inspection.
Please call if you have questions or comments.
Respectfully,
8 -LW417
Dan Wilson
Project Manager /Estimator
Fire /Life Safety Division
Capitol Electric Company, Inc.
(503) 255 -9488
NICET Level IV, Fire Alarm Systems #104512
11401 NE Marx • Portland, Oregon 97220 -1041 • 503 - 255 -9488 • Fax 503 - 257 -7121
CCB# 48748 • www.capitolelectricco.com