Correspondence August 11, 2006 4J I CITY OF TIGARD Capitol Electric Company OREGON Dan Wilson 11401 NE Marx St Portland, OR 97220 RE: FIRE ALARM SYSTEM MODIFICATION - REVIEW Project Information : HORN STROBES Building Permit BUP2006 -00368 Construction Type: 1-B Tenant Name: Nation Wide Occupancy Type: B Address: 10300 SW Greenburg Rd.# 470 Stories: 5 Hazard: Light The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition, Oregon Fire Code (OFC) 2004 edition and NFPA 72. The submitted plans are approved subject to the following. TESTING- NFPA 72 Chapter 10, OFC 901.5, 903.5 1. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the building official and fire code official. All functions of the system or alteration shall be tested. 2. The permittee shall provide written certification to the Fire Chief that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. 3. Sprinkler systems shall be tested and maintained in accordance with Oregon Fire Code. POWER- NFPA 72 section 4.4.1.2, 4.4.7.3, OFC 907.5 4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL- 907.5 OFC 5. All power supplies shall be installed in conformity with NFPA 70. 6. All primary and secondary power supplies shall be monitored for the presence of voltage at the point of connection to the system. Failure of either supply shall result in a trouble signal in accordance with 4.4.3.5. The trouble signal also shall be visually and audibly indicated at the protected premises. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 VISUAL ALARMS- NFPA 72 — chapter 5 & 7, OSSC chapter 9 & 11 9. Visual alarms shall be located not less than 80 inches and not more than 96 inches above floor level. When a low ceiling exists, the visual alarm shall be mounted within the dimensions stated above and at least 6 inches below the ceiling. No place in a room shall be more than 50 feet from a visual signal. 10. Visual signal appliances shall be provided in the building in each of the following areas: • Restrooms and any other general use area (e.g., meeting rooms) • Hallways/Corridors • Lobbies • Common use areas. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or mad fronting the property. When submitting revised drawings or additional information, please attach a copy of the endosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectful , c f-17/* -fr A l .c . / Val Menzel, Senior Plans Examiner Capitol Electric Co•, Inc. Eta 2 2006 3UJLDING Division/ August 1, 2006 Plans Examiner City of Tigard Building Services 13125 SW Hall Blvd. Tigard, OR 97223 Re: Tenant Fire Alarm System Design Nationwide Tenant Improvement One Lincoln Center, Suite 470 10300 SW Greenburg Road Tigard, OR 97223 Please find attached a building permit application, Tri- County Commercial Application Checklist, two sets of plans, calculations, and product submittals for the fire alarm tenant improvements at the address shown above. This building has an existing fire alarm system. ADA synchronized notification devices will be installed in the tenant space in common use and general use areas. We will pre- test new devices before requesting a final inspection. Please call if you have questions or comments. Respectfully, 8 -LW417 Dan Wilson Project Manager /Estimator Fire /Life Safety Division Capitol Electric Company, Inc. (503) 255 -9488 NICET Level IV, Fire Alarm Systems #104512 11401 NE Marx • Portland, Oregon 97220 -1041 • 503 - 255 -9488 • Fax 503 - 257 -7121 CCB# 48748 • www.capitolelectricco.com