RE: EXISTING NON - COMPLYING SYSTEM UPGRADE — 4 STAIRWELL
PRESSURIZATION SYSTEMS
Project Information
Building Permit: MEC2006 -00465 Construction Type: 1B
Tenant Name: Lincoin Ctr 1 Occupancy Type: B
Address: 10300 SW Greenburg. Occupant Load: unk
Stories:
The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC)
2004 edition. The submitted plans are approved subject to the following.
1. Testing of system shall be complete and approved prior to mechanical equipment approval.
909.20.6.3 OSSC
2. Equipment and appliances shall be installed as required by the terms of their approval, in
accordance with the conditions of the listing, the manufacturer's installation instructions
and this code. Manufacturer's installation instructions shall be available on the job site at
the time of inspection. OMSC 304.1
3. The building or structure shall not be weakened by the installation of mechanical systems.
Where floors, walls, ceilings or any other portion of the building or structure are required to be
altered or replaced in the process of installing or repairing any system, the building or structure
shall be left in a safe structural condition in accordance with the Building Code. The cutting,
notching and boring of framing members shall comply with OMSC 302 Sections 302.3.1
through 302.5.3.
4. Equipment and appliances regulated by this code requiring electrical connections shall have a
positive means of disconnect in accordance with the Electrical Code. OMSC 301.7
5. Appliances shall be accessible for inspection, service, repair or replacement without removal of
permanent construction. OMSC 306.1
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Respectfull ,
Val Henze ,
Senior Plans Examiner
Val Henzel -City of Tigard One Lincoln_doc Page 1
SimplexGrinnell Barry Rolfs
6305 Rosewood St. A&D Design Manager
Lake Oswego, OR 97035 brolfs @tycoint.com
(503) 683 -9000 February 8, 2006
Fax: (503) 675 -6521
Val Henzel, Senior Plans Examiner
City of Tigard
13125 SW Hall Blvd.
Tigard, OR 97223
RE: MEC2006-00465
One Lincoln
10300 SW Greenburg Rd.
Tigard, OR 97223
Dear Ms. Henzel:
In reference to the mechanical project at One Lincoln (MEC2006- 00465) in which stairwell
pressurization fans are being added to four stairwells, please note that all stairwell pressurization
fans will be activated upon any smoke detection by an automatic detector in the building's fire
alarm system. Programmable relay modules that are part of the fire alarm system will control the
fans. Deactivation of the stairwell pressurization fans will take place when the alarm condition
has been cleared and the fire alarm system has been reset. This will also be accomplished by
the building fire alarm system.
Please find the attached pdf files showing the operational matrix outlining control of the stairwell
pressurization fans and the riser diagram indicating the stairwell pressurization fan control
modules.
Please feel free to contact me with any questions you may have. Thank you.
Barry
Barry Rolfs
A &D Design Manager
SimplexGrinnell