Specifications d 0 ,250 R9( t 00s4 two Fire & 4 Security Mt 17 2001 SimplexGrinnell Cu l ur afaARD BU1LDI G DIVISION FIRE ALARM EQUIPMENT SUBMITTAL Project Name: Lincoln Four Building Customer Name: Shorenstein Realty Services Customer Contact: Kelly Brewster SimplexGrinnell Representative: Bryan Adams v 6„Simplex TrueA /arm Fire Alarm Controls UL, ULC Listed; FM, CSFM, Model 4010 Fire Alarm Control Panel for TrueAlarm and MEA (NYC) Approved* Analog Sensors and IDNetTM Addressable Devices IlliiliiiiiiililiiiIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIV , , °: Standard features include: ; >� • Up to 250 addressable TrueAlarm sensor or addressable i , ; device points using 1DNet communications that operate V* with either shielded or unshielded twisted pair wiring ** 1 • Four, 2 A notification appliance circuits (NACs) with solid state current protection • Internal event reporting DACT module (standard on models 4010 -9101, 4010 -9102, & 4010 -9150) UL listed to Standard 864 Installation convenience features: .i • Power - limited design with electronic modules contained 911111111191 111 1 411 11 11 1 111011l,1 4 11111111 ' ° on one -piece chassis • Up -front terminal blocks for wiring access 4010 Fire Alarm Control Panel (with standard door) • Compact NEMA 1 rated cabinet is available in beige or red and can be pre- shipped for early installation DegGti'o tio'n Setup, programming, and maintenance features: TrueAlarm fire alarm control panels have the ability • Device level ground fault search, locate and isolate to provide location accuracy for monitoring and control. • Auto Program for general alarm operation When equipped with TrueAlarm analog sensing for • TrueAlarm individual analog sensing with front panel smoke and heat detection, the processing power of the information and selection access control panel also has the ability to analyze conditions at • "Dirty" TrueAlarm sensor maintenance alerts, service each location to provide accurate detection with and status reports including "almost dirty" significantly reduced maintenance costs. t1 • Default TrueAlarm sensor device type operation The 4010 TrueAlarm Fire Alarm Control Panel has been • Duplicate address error detection specifically designed to provide addressable operation and • Front panel or PC programming analog detection in a cost - effective package for • TrueAlarm sensor peak value performance report application sizes that previously were considered only • WALKTESTTM silent or audible system test t appropriate for conventional zoned monitoring. • Software verification simulation mode Installation and Service Ease. The 4010 mounts on a single chassis for quick installation and removal. Supports the following IDNet devices: Terminal blocks are large and up -front for easy access • Addressable manual stations and inspection. Optional modules are easily and quickly • Quad -state zone adapter modules (ZAMs) for initiating installed and programmed as required. device monitoring The 4010 cabinet provides convenient stud markers for • IDNet ground fault/short circuit isolator base for drywall thickness and nail -hole knockouts for quicker TrueAlarm sensors mounting. Smooth cabinet surfaces are provided for • Quad -state line powered individual addressable modules locally cutting conduit entrance holes exactly where (IAMB) for initiating device monitoring and relay control required. 4010 cabinets and electronics can be ordered Available option modules include: separately, allowing early cabinet installation. • Door mounted 24 LED annunciator (std. on ULC models) Ground Fault Assistance. Ground fault problems • Network, or Point Reporting DACT often occur during installation. The 4010 provides Class A NAC adapter module isolating circuitry and software - controlled sequencing to • • RS 232 ports for printer and maintenance PC isolate ground faults to specific identified locations. This assistance helps the installer to accurately locate the • Additional power supply; Auxiliary Relay Module or wiring problem for quicker repair. City Interface . Refer to page 6 for hating details. This product has been approved by the California State • Equipment for Suppression Release Applications Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. (refer to data sheet 54010 -0003) See CSFM Listing 7170 - 0026:226 for allowable values and /or conditions concerning material presented in this document. It is subject to re- examination, revision, and possible Compatible with Simplex auxiliary panels: cancellation. Accepted for use— City of New York Department of Buildings — MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the • TrueAlert Addressable Controllers and NAC power latest status. Listings and approvals under Simplex Time Recorder Co. are the property of extenders (IDNet controlled and conventional) Tyco Safety Products Westminster. "TrueAlarm analog smoke detection and IDNet addressable devices are protected by one • 4003 Voice Control Panel or more of the following U.S. Patents: 5,155,468; 5,173,683; 5,543,777; 5,400,014: • 4081 Battery Cabinet with Charger for 50 Ah batteries 5.552.765: 5,552,763, DES. 377,460. t WALKTEST system test is protected under U.S. patent # 4,725.818. S4010- 0001 -9 10/2004 J 401000erafor Control S ummary; 401.0 Dri splay§Panel=and,Diag Extensive Feature List. The 4010 Fire Alarm Control Convenient Status Information. With the locking Panel provides access to an extensive feature list that door closed, a window allows viewing of the status includes: display. The 4010 status panel provides a two line by 40 character, super twist LCD information display and eight • Providing easy and powerful operator information with status LED indicators as shown in the illustration below. ' a logical, menu -driven display • Extensive and automatic diagnostics for maintenance From this display, the LED indicators will describe the reduction general category of activity being displayed with the LCD History Logs available from the LCD or capable of providing more detail. For the authorized user, unlocking • (optionally) being printed the door will provide access to the control switches and allow further inquiry by scrolling the display for • Software Verification, allowing detailed logic additional detail. (Refer to control panel functional programming simulation to be conducted without illustration below.) activating connected outputs Control Panel (or service PC) label editing WALKTEST Diagnostic Operation Mode. The • patented WALKTEST process allows a single person to • Password access control perform system test. The system records test inputs such • Auto Program Quick Configuration (Quick -CFIG) of as intentional alarms or trouble and either logs the connected modules and IDNet devices for general alarm response (silent WALKTEST operation) or outputs a operation to quickly get the system up and running brief, recognizable audible notification signal (audible WALKTEST operation). ;Extended Operafeeeo fifi$ Panel tih'aloi s5 FIVE STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash to indicate the condition and then when acknowledged, remain on until reset THREE PROGRAMMABLE LEDs 2 X 40 LCD READOUT, LED backlighted during normal conditions and abnormal N provide custom labeling (labels insert into operating conditions, provides up to 40 characters for custom label information a pocket), the top two LEDs are P 4 FIRST ALARM DISPLAY: Operation can be selected for maintained display of first selectable as red or yellow, the bottom alarm until acknowledged LED is selectable as green or yellow hid ':SYSTEM IS NORMAL 12' 02 ri"Sam Moil 18 =04 CONTROL' SYSTEM RESET res PANEL VIEW with v., ft ® ® ;. 4010 door closed control panel to normal when a . .� all alarmed inputs are r � E , rt s r ' €r sx �� , retumed to normal {{' t t 1 \ ALARM ACK acknowledges a Fire Alarm condition, NINE EXTENDED FUNCTION KEYS (accessible with logs the acknowledge and silences the operator panel and all annunciator tone - alerts door open) select and scroll through display prompts for locating additional system information, performing maintenance functions, or for front panel programming SUPV ACK acknowledges system supervisory ALARM SILENCE causes audible notification appliances conditions, logs the acknowledge, and silences the operator panel and all annunciator tone - alerts to be silenced, used after evacuation is complete and while alarm source is being investigated ' l \ TROUBLE ACK acknowledges system troubles, logs the acknowledge, and silences the operator panel and all annunciator tone - alerts 2 S4010- 0001 -9 10/2004 ,, IDNet Addressable Inte'rface:$ TrueAlarm An alog�$ens ors,(Continued). Overview. The 4010 provides IDNet addressable device TrueAlarm heat sensors can be selected for communications. Using a two wire circuit, individual rate -of -rise detection as either 15° F (8.3° C) or 20° F devices such as manual fire alarm stations, TrueAlarm (11.1° C) per minute with an independent fixed limit of sensors, and sprinkler waterflow switches can be directly 135° F (57° C) or 155° F (68° C). TrueAlarm heat sensors ' connected (or interfaced) to the IDNet controller to can also be programmed as a utility device to monitor for communicate their identity and status. This addressability temperature extremes in the range from 32° F to 155° F allows the location and condition of the connected device (0° C to 68° C). This feature can provide freeze warnings to be displayed on the 4010 panel LCD and on system or alert to HVAC system problems. annunciators. Additionally, control circuits (fans, dam dampers, etc.) may be individually controlled b y using a Toes additional to ID N p ) y y � g devices, up to 250 total relay IAM (individual addressable module). The 4009 • 1DNet NAC Extender or the TrueAlert Addressable ovo_— controller can be controlled for local or remote ®114740 1111E notification appliance expansion. (Refer to individual device documentation for further details.) _ Capacity. A total of 250 addressable monitor and control ? Modular TrueAlarm points may be intermixed on the same pair of wires. By TrueAlert Addressable Controller sensor with base using Zone Adaptor Modules (ZAMs) or Individual Addressable Modules (IAMs), conventional initiating devices can be connected to the IDNet circuit. girl IDNet Addressable Operation. The IDNet controller continuously interrogates each addressable device on the Supervised IAM Modular TrueAlarm sensor communication channel for status condition such as: with IDNet isolator base normal, off - normal, alarm, supervisory, or trouble. 11111199®916 Sophisticated poll and response communication n techniques ensure supervision integrity and allow for - ';`¢ "T- tapping" of the circuit for Class B (Style 4) operation. Addressable station ;1 ''•` i Wiring Requirements. Refer to the specifications chart [ 7 4009 IDNet NAC below. Distances are for shielded or unshielded wire. Extender Shielded wire may provide protection from unexpected ` i sources of interference and may be required for some applications. Quick-Connect Monitor ZAMs and pp TrueAlarm sensor Relay IAMs s Wiring Specifications ®® ® ® ®® ®elm®® Size 18 AWG minimum nii, ,, Preferred Shielded twisted pair (STP) 4010 Fire Alarm l ; Wire Control Panel with Acceptable Unshielded twisted pair (UTP) annunciator door Farthest Distance from Control Panel to Device Up to 2500 feet (762 m) r Total Wire Length Allowed With Up to 10,000 ft (3 km). ®°is®®®u®n®®® "T' Taps for Class B Wiring 4010 Control Panel with Typical IDNet Devices nTrueAlarlT AnaloTAensors Diagnostics Defa lliOe.vicef�TVpe TrueAlarm System Operation. IDNet communications are used for TrueAlarm smoke and temperature sensors. TrueAlarm operation gives the 4010 system the ability to Every four seconds, smoke sensors transmit an output automatically indicate when a sensor is almost dirty, dirty, value based on their smoke chamber condition. The 4010 and excessively dirty. The NFPA 72 (National Fire Alarm CPU maintains a current value, peak value, and an average Code) requirement for a test of the sensitivity range of the value of each sensor's output. Status is determined by sensors is fulfilled by the TrueAlarm ability to maintain comparing the current sensor value to its average value. the sensitivity level of each sensor. Tracking this average value as a continuously shifting Modular TrueAlarm sensors use the same base and different reference point filters out environmental factors that cause sensor types (photoelectric smoke sensor, or heat sensor) shifts in sensitivity. can be easily interchanged to meet specific location Programmable Sensitivity. The sensitivity of each requirements. This feature also allows intentional sensor sensor can be field programmed at the 4010 Control Panel substitution during building construction. When conditions for different levels of smoke obscuration (in percent) or are temporarily dusty, instead of covering the smoke sensors for specific heat detection levels. In order to evaluate (causing them to be disabled), heat sensors may be installed whether the sensitivity should be revised, the peak value without reprogramming the control panel. Although the is stored in memory and can be easily read and compared control panel will indicate an incorrect sensor type the heat to the alarm threshold directly in percent. sensor will operate at a default sensitivity to provide heat detection for building protection at that location. 3 S4010- 0001 -9 10/2004 TrueAlarm 'Inform = °" ° "'' Printer (Simplex True Alarm sensor data can be displayed on the model 4190 -9013) „ „„,:::"5:1': - . , -='i'v''''' � system LCD, on a remote maintenance PC, or printed on a , :,r_ -_ 'I remote printer. With the proper operator access, a i 182®1111111101111111111111111111 TrueAlarm Service Report can be generated to list the . specific details of each TrueAlarm device. This report, as Local `, <i,.- . .��.. well as the Status Report can either be displayed on the maintenance x x x computer 4VXI remote maintenance PC or captured permanently by using r � a remote 80 character printer. -- - - - - -' The report samples below illustrate the format provided on either the remote maintenance PC or a printer. This e��omaeoesluo�e' =t 4010 Fire Alarm 's One connection type per 4010, information is available at the system LCD by identifying control Panel selected by module choice; max. the specific point of interest and reading one point at a wiring distance is 300 ft (91 m) time. Y F s , @ 9600 baud Model 4190-9013 is a UL Standard 864 listed 80 column, , ,e i ftt( 24 pm dot matrix printer (refer to data sheet S4190- 0011). ,_ - _gt,,'� � ti, ; ,� Remote authorized maintenance (Model 2190-9039, a 24 VDC, 40 column printer, is_ '_ computer connected via dial -up compatible with the 4010 for event p printing y com rintin only. Refer to ® - S erv i ce M odem C onnect i on , ., data sheet S2190 0014.) RS -232 Connection Options (refer to module selection on page 6) TrueAlarm Status iWgreTry O36port Samples Simplex 4010 Fire Alarm System Page 1 REPORT 3 : TrueAlarm Status Report 2:43:03 pm Mon 18- Oct -04 Zone Sensi- Almost Name Custom Label tivity Device Status Dirty M1 -1 ANALOG PHOTO CLEAN ROOM 0.5 % NORMAL M1 -2 ANALOG ION CLEAN ROOM 1.3 % NORMAL M1 -3 ANALOG PHOTO MAIN LOBBY 2.5 % NORMAL *YES* M1 -4 ANALOG PHOTO CONFERENCE ROOM 1 2.5 % NORMAL M1 -10 HEAT DETECTOR GARAGE 135 F NORMAL M1 -11 ANALOG PHOTO KITCHEN 3.7 % NORMAL *YES* END OF REPORT Typical TrueAlarm Status Report Information Printout and /or Maintenance PC Screen Simplex 4010 Fire Alarm System Page 1 REPORT 4 : TrueAlarm Service Report 2:56:09 pm Mon 18- Oct -04 Dev Alarm Avg Current/ Peak/ State Num Custom Label at: val % alarm % alarm 1 ANALOG PHOTO - CLEAN ROOM 0.5/ 83 67 68/ 1% 72/ 10% NOR 2 ANALOG ION - CLEAN ROOM 1.3/209 94 97/ 2% 101/ 1% NOR 3 ANALOG PHOTO - MAIN LOBBY 2.5/185 117 117/ 0% 125/ 42% NOR 4 ANALOG PHOTO - CONFERENCE ROOM 1 2.5/161 93 93/ 0% 93/ 0% NOR 10 HEAT DETECTOR - GARAGE 135F/253 - -- 63/ -67F 66/ 69F NOR 11 ANALOG PHOTO - KITCHEN 3.7/216 116 116/ 1% 110/ 36% NOR END OF REPORT Typical TrueAlarm Service Report Information Printout and /or Maintenance PC Screen 4 S4010- 0001 -9 10/2004 Standard,Panel Feattares Optional:'ExpansioniSlot Modules': (Conf'd);" N2 Communications for Serial Annunciator Control. DACT, Event Reporting Module. For applications where Control for up to 6 remote Simplex Annunciator products simple event status information is required (Alarm, including 24 Point I/O Module, and LCD Annunciator. Trouble, Supervisory, and AC power failure). Includes extensive troubleshooting diagnostics. Dual RS - 232 Module. Available for interfacing to a Access Port. RS -232 service port for connecting PC tools printer and a maintenance PC. for service diagnostics and for programming the CPU Single RS - 232 Module with Service Modem Connection. Flash EPROM memory. Provides one port dedicated for connection to a printer, and IDNet Addressable Communications Channel. a second port dedicated for dial -in from a service computer, Addressable channel provides communications for up to typically located off -site. With an off -site computer, 250 remote addressable devices, including TrueAlarm programming changes and system diagnostics can be analog sensors and isolator bases (see descriptions on performed remotely, reducing service time for repair or page 3). reprogram. Security is maintained by password protection. Four NACs. Class B output is standard, rated for 2 A @ OptionalChassikfilountiModules 24 VDC nominal, with solid state current protection. Class A operation is optional with the addition of an Standard 4 A Expansion Module provides two taps of adapter module. 2 A each, 28 VDC, filtered, non - regulated, similar to the NAC operation can be selected for "on- until - Silence" or standard power supply capacity. "on- until- Reset," and can be Temporal pattern, 20 or Suppression Release Power Supply provides two taps 120 bpm March Time pattern, or continuous. Each NAC of 2 A each, regulated at 24 VDC ± 10 %. May also be is also individually selectable to control Simplex used for other applications requiring regulated voltage. synchronized visible notification appliances and to control Use for suppression release requires a front panel audible notification appliances using SmartSyncTM mounted release applique that is provided with this power control, allowing separate audible and visible appliance supply and also may be ordered separately. operation using a common 2 -wire circuit. (Class A , Style Z, SmartSync circuits require SmartSync Control Battery Meter Module provides panel mounted ammeter Module 4905 -9938, refer to data sheet 54903 -0010 for and voltmeter for power supply monitoring. details.) Dual Circuit Class A NAC Adapter Module mounts on the Two Auxiliary Output Circuits. Operation is main 4010 printed circuit assembly and provides the O programmable for trouble, alarm, supervisory, or other additional circuitry needed for Class A operation. fire response functions. Output is one Form "C" dry Dual Circuit City Connect Module provides the interface contact each, rated 2 A @ 24 VDC. An optional relay kit required for direct wired reporting to conventional city is available for switching up to 1/2 A at 120 VAC. connection circuits. (Available with or without disconnect Power Supply. Standard output is 4 A @ 28 VDC, switches.) filtered, non - regulated. Internal system power is provided Expansion Power Distribution Module provides two separately, allowing the 4 A to be available for NAC and additional termination points for the 1/2 A auxiliary power auxiliary power tap functions. Over - current protection is output, or for one tap of the expansion power supply. solid state and self - resetting. Auxiliary Power Tap. Provides up to 1/2 A of the Relay Option Module. Provides three relays, one each for standard power supply voltage, over - current protected. Alarm, Supervisory, and Trouble. Relay contacts are selectable for normally open or normally closed and are Battery Charger. Capable of charging up to 25 Ah sealed rated 2 A @ 32 VDC maximum. lead -acid batteries (4010 cabinet mounted). A recharge time of 24 hours is typical with stable 120 VAC input. For N2, COtlltil U111Cat1O17$ MOdUIeS . applications requiring larger batteries, external Up to six of the following modules may be connected to charger /cabinet assemblies are available. the Simplex N2 serial communications bus. A depleted battery cutout feature is programmable to advise 4606 - 9101 LCD Annunciators provide remote and /or to reduce current when battery voltage is low. acknowledge, reset, and alphanumeric status display. Optional oni;SlotrModu1.0., (Refer to data sheet S4606- 0001.) (The 4010 is available with a Simplex Network Interface. 24 LED Annunciator Doors are standard on ULC listed (The can be declared "public. ") models and are available as door -only assemblies for 4010 electronics only packages or other aftermarket applications. Network Interface, Fixed Media. Available for wired This option uses the 24 Point I/O module with all points applications. pre - assembled as LED outputs, with individual labels and Network Interface, Modular Media. Available for wired each LED is selectable as red or yellow. connections or fiber optic. Require separate media 4605 Series 24 Point I/O Modules are available for modules. May be both wired, both fiber optic, or one of remote mounting and provide 24 points that can be each. programmed as either general purpose switch inputs or DACT, Point Reporting Module. Provides serial output system controlled outputs. Typical applications are for information that can send location details to a remote remote annunciators and monitoring and control of other receiving station. related processes. (Refer to data sheet S4010- 0002.) 5 S4010- 0001 -9 10/2004 4 illScireAlarmtliiiii*Se;l6aion Chart and Module Locat on Rules,,(refertodiagra`m page 8) •Category ' Model'. 'Description ..' .', • . . Voltage. Color, ___>. 4010 -9101 UL Listed 4010 Fire Alarm Control Panel with: door, cabinet, power 120 VAC Beige 4010 -9102 supply /battery charger, IDNet interface, 4 NACs, 2 auxiliary relays, and Red 4010 -9201 external N2 communications interface; 4010 -9101 and 4010 -9102 Beige include internal common event reporting DACT 240 VAC 4010 -9202 Control Panel Red Assembly 4010 -9101C English ULC Listed 4010 Fire Alarm Control Panel; same as above 120 VAC Beige (select one) 4010 -9101 CF French except: with 24 LED Annunciator door; and without DACT 4010 -9150 UL Listed 4010 Fire Alarm Control Panel electronics only, 4010 -9150C ULC English for pre- shipped cabinets, requires door and cabinet 120 VAC NA 4010- 9150CF Listed French ordered separately; -9150 has event reporting DACT Optional Expansion Slot Features (two slots are available, select modules as required) Category ''" Model' . , ;Descripti861 . . > 4010 -9810 DACT Module (Common Event Reporting) Includes two, 7 ft (2.1 m) long RJ45 cables Reporting and 4010 -9816 DACT Module (Point Reporting) Network Modules (select one) 4010 -9821 Network Interface Module with fixed, wired connections 4010 -9817 Network Interface Module, Modular; requires 2 (In /Out) media modules (see below) RS -232 4010 -9811 Dual RS -232 Interface Module Communications (select one) 4010 -9812 Single RS -232 Interface Module with Service Modem connection 4010 -9818 Network Wired Media Module Media modules mount on the 4010 -9817 module Media Modules without impact to slot allocations ace. 4010 -9819 Network Fiber Optic Media Module P P Chassis Mounted Expansion Modules (select as required) Category , . , =Model Description,_ . , . • ' 4010 -9813 120 VAC input Additional 4 A Expansion Power Supply 4010 -9823 240 VAC input Power t Supply e ) 4010 -9814 CF Su ression Release Power Su I 4 A 24 VDC, re ulated ± 10 %; 120 VAC in ut (select one) ( ) PP PP Y. @ 9 p 4010 -9824 includes front panel suppression applique; CF suffix selects French 240 VAC input Ilk Optional Features 4010 -9820 Battery Meter Module (ammeter and voltmeter) (select one) 4010 -9825 24 VDC Expansion Power Distribution Module, provides two additional termination points for . an expansion power supply tap or the auxiliary power output 4010 -9806 Dual Circuit Class A (Style Z) NAC Adapter Module, two maximum Optional Features 4010 -9809 Dual Circuit City Connect Module (select as Select one indicated) 4010 -9829* Dual Circuit City Connect Module w/o disconnect switches maximum 4010 -9803 Relay Option Module Accessories Category .... Model ; _ °Descript _ ;.=' y ', ` _ . . • . .. ' 4010 9826 120 VAC Auxiliary Relay Kit, allows one auxiliary relay to control up to 1/2 A @120 VAC, select as required; 2 maximum 4010 -9830 Suppression Release Applique, required for suppression release applications; suffix CAF Optional Features (CAF) selects a French applique 2975 -9801 Semi -flush trim, beige, 1- 7/16" (37 mm) wide 2975 -9802 Semi -flush trim, red, 1- 7/16" (37 mm) wide Batteries 2081 -9272 6.2 Ah Battery, 12 VDC (required if 2081 -9274 10.0 Ah Battery, 12 VDC batteries are 2081 -9288 12.7 Ah Battery, 12 VDC internal; select one size; two batteries 2081 -9275 18 Ah Battery, 12 VDC; NOTE: This battery size will not allow bottom entry conduit are required) 2081 -9287 25 Ah Battery, 12 VDC Cabinets (select 2975 -9215 Red Cabinet Dimensions: 22" H x 18" W x 5 -3/8" D one if pre- shipped) 2975- 9214(CF) Beige Cabinet; CF suffix has French labels (559 mm x 457 mm x 137 mm) 4010 -9858 Red Door with dress panel Dimensions: 22" H x 18" W x 5/8" 0 Doors (select one 4010- 9857(CF) Beige Door with dress panel; CF has French labels (559 mm x 457 mm x 16 mm) if pre- shipped or for use with 4010 -9860 Beige Door with 24 LED Annunciator and dress panel; Dimensions: 22" H x 18" W x 4010 -9150) (CAF)* CAF suffix selects French for ULC applications 1- 23/32 "D (559 mm x 457 mm x 4010 -9861* Red Door with 24 LED Annunciator and dress panel 44 mm) [see also S4010 -0002] * As of document revision date: 4010 -9829 is not ULC listed; 4010 -9860 and 4010 -9861 are listed by UL and ULC and approved by CSFM and FM; 4010- 9860CAF is ULC listed and FM approved only. 6 S4010- 0001 -9 10/2004 4010 O.eratm: Input Requirements Voltage Range Frequency Maximum Current AC Input, 120 VAC base models 102 to 132 VAC 60 Hz 2 A ' AC Input, 240 VAC base models 204 to 264 VAC 50/60 Hz 1 A AC Input with 120 VAC expansion power supply 102 to 132 VAC 60 Hz 4 A • AC Input with 240 VAC expansion power supply 204 to 264 VAC 50/60 Hz 2 A Environmental Operating Temperature Range 32° to 120 °F (0° to 49° C) Operating Humidity Range up to 93% RH, non - condensing @ 100.4° F (38° C) maximum Output Ratings: ; ,, = 2 . Standard Power Supply Output 4 A total @ nominal 28 VDC Auxiliary Power Tap 1/2 A maximum of standard power Output switches to battery supply voltage backup during mains failure or Expansion Power Supply Output * Additional 4 A @ nominal 28 VDC brownout conditions Suppression Release Power Supply Output * Additional 4 A @ 24 VDC ±10% * Each power supply provides two output taps of 2 A each. Current Ratings for Optional Modules and Remote LCD Annunciator S .. ..Alarm: Model M odule - - C urrent: , : � � Current' ,; 4010 -9810 DACT (Common Event Reporting) 40 mA 40 mA 4010 -9816 DACT (Point Reporting) 40 mA 40 mA 4010 -9821 Network, wired communications 125 mA 125 mA 10 4010 -9817 Network Modular, add media cards separately 24 mA 24 mA . 4010 -9818 Network Wired Media 47 mA 47 mA 4010 -9819 Network Fiber Optic Media 36 mA 36 mA 4010 -9811 Dual RS -232 75 mA 75 mA 4010 -9812 Single RS -232 with Service Modem 100 mA 100 mA 4010 -9806 Dual Class A NAC Adapter 0 mA 0 mA 4010 -9809 Dual Circuit City Connect 20 mA 36 mA 4010 -9829 Dual Circuit City Connect w/o disconnect switches 20 mA 36 mA 4010 -9803 Relay Option Module 10 mA 37 mA 4010 -9860 83 mA 4010 -9861 24 LED Annunciator door 60 mA & ULC 4010s (all LEDs on) 4606 -9101 Remote LCD Annunciator (refer to data sheet S4606 -0001) 65 mA 140 mA System Current (supplied separate from power supply output) r ,: - •B With:',.'. Supervisory Alarm -. Current *.'° Curcen no IDNet devices 195 mA 295 mA 50 IDNet devices 230 mA 330 mA 100 IDNet devices 265 mA 365 mA 150 IDNet devices 300 mA 400 mA 200 IDNet devices 335 mA 435 mA 250 IDNet devices 370 mA 470 mA ** Current Calculation Information: 1. To determine total supervisory current, add currents of modules in panel to base system value and all auxiliary loads. 2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads and all auxiliary loads. 7 S4010- 0001 -9 10/2004 '40 ;Module La lout Reference; ' r . etsi g IDn N NAC1 NAC2 SAC3 NAC4 Iz IWIQ aam 1 1 1h1 - -- - III II f, ∎n■n 8 __ _ �.��..© g r Dt f III I►�,I►,I /II Ilhl�l�lkl ll ® Ii: !I! 1•P:•i w w�w•w w.w w•44- P2 4010 -9820 0 0 O 0 e3 754 ® 4010 -9809 Meter Module 4010 -9806 4010 -9806 or -9829 or City Module 4010 -9825 Expansion Class A Class A or Slots 1 & 2 Module Module 4010 -9803 24 VDC Power Distribution -- Relay Module Block RA © 0 0 0 0 0 01 1 - " - . I:1) O O O O O l , 4010 - 981 4 av 4098 -9814 4010 -9823, OOQOOOOO `\l or 4010 -9824 W, 0. Expansion Power Supply I wile., _._•� •-• -• -, . , � (0 � � o _- ■ AUX AUX1 AUX2 EAT POWER rMou rifki lnformati t , , t - _ , 7 -3/32" Typical conduit entry area (180 mm) y ` (cut holes as required) o Standard 1- 19/32" door profile (40 mm) 6 -1/4" ■ (159 mm) 314" 5 -1/2" 18" (457 mm) id Annunciator (19 mm) (140 mm) door profile Wall thickness guides for 0 V 1/2" (13 mm) wall board 11 C5 0 ` ; r. __`. si 1. ,_ �,. Standard Door, t� — � 5 /8" (16 mm) thick all thickness guides for ii - - - Q � 5/8" (16 mm) wall board) I a - Internal straps are o I O Annunciator Door, �� provided for wiring • -is a ,a' a o© 1- 23/32" (44 mm) thick management • 00000 0=1 (2 each side) 21" o cee©e0e ®O a (533 mm ® - — .,,,i..,y__I.'I___I__ o J Door and exposed ������� cabinet dimension %r _ 1 9 ;..:' _ - _ t for semi -flush mount - - -- i" 2- 15/32" (63 mm) r ? -r r° s--- 14 -1/2" (368 mm) a- Knockout screw /nail holes Battery Area 11,i'; 1 /(for semi -flush mount) ry r " ({/ No conduit entry or wiring in this area 1 -P; eN r ,, � o Wall board position reference -........= ._ Shaded area is for non -power limited wiring for semi -flush mount . Tyco. Simpler, the Simplex logo. TrueAlarm, WALKTEST, IDVet. SmartSvnc, and TrneAlerl are trademarks of Tyco International .4G or its affiliates in the U.S. and /or other countries NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA). Simplex Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4010-0001-9 10/2004 a www.tycosafetyproducts-usa-wm.com © 2004 Two Safety Products It estminstenr..411 rights reserved All specifications and other inf irntatit n.shown were current as ofdocu n eni revision dale and are subject to change without notice. o SiMpieX Fire Alarm Control Panel Accessories Listings* System Batteries, Sealed Lead -Acid; with Applications Reference for Battery Cabinets, and Battery Cabinets with Charger Features LOW Rechargeable, sealed lead -acid batteries: • Lead - calcium grid structure with immobilized I electrolyte in absorbent separator �.r • Low maintenance with no need to add water • Low self - discharge characteristics • One - piece, high impact polystyrene cell cover with high - -.. _. reliability dual seal construction • • UL 924 recognized pressure relief valves � x Available in a variety of capacities: • Batteries for internal mounting range from 6.2 Ah up to 50 Ah, depending on control panel cabinet size g �, • Larger batteries, up to 110 Ah, mount in external battery a9uoua re�cnga cabinets that are available with internal chargers � : • Includes battery chargers with communications' compatibility for use with 4010 Series fire alarm control "` • . panels and with 4100U Series fire alarm control panels De$0! • tior , Simplex rechargeable sealed -lead acid batteries provide Compatible Sealed Lead Acid Batteries can be reliable and repeatable discharge and recharge Installed Inside Fire Alarm Control Panel Cabinets characteristics for use in fire alarm and other systems , E• applications. They are designed with immobilized "` #E, electrolyte in an absorbent separator, allowing them to s �, � � �°°��� � �"� � � provide rated capacity on the first cycle. ti Because of their sealed construction, packaging is allowed'; within the system electronics enclosure (see illustration on page 2). When this is applicable, the quantity of system cabinets and the battery wiring distances are both • •_€ _ minimized. Where required, external battery cabinets can be close - nippled to the control panel to house larger Remote Battery Cabinets are Available for batteries with battery chargers available in some battery Larger Battery Requirements cabinet sizes. B atte E Deta'ilsa Battery „Detailsr(C Disposal. Battery chemicals and materials can be Charging. These batteries are intended to be used with recycled. Refer to information shipped with the battery or compatible Simplex battery chargers. on its case. Return to the battery manufacturer or to a Series Connections. These batteries are required to be similarly qualified battery processing facility for proper connected in series to produce 24 V system voltage. disposal. Battery sets must be of identical voltage, model number, appearance, and approximately the same date of manufacture for proper operation. * Refer to details on page 4 and to the referenced individual product data Testing. Battery capacity testing is recommended to be sheets for agency listing status of battery cabinets and chargers. The batteries performed by using a sealed lead -acid battery tester detailed in this document meet the requirements of UL, ULC, and Factory Mutual for use with respective equipment battery chargers as listed on page 3. designed to withdraw a minimum of battery charge. The Contact your local Simplex product supplier for proper battery selection per preferred tester applies a variety of amplitude and system requirements. Listings and approvals under Simplex Time Recorder duration controlled test pulses that compares terminal Co. are the property of Tyco Safety Products Westminster. voltage against those predicted for the specific battery size. (Testing is available through your local Simplex product supplier.) S2081- 0006 -18 5/2007 Batte f C464KictlonrReference;'- Actual appearance will vary with battery size. Sealed outer cover Quick connect or post type terminal Vent hole Potting material, black for (type varies with battery size) negative, red for positive • (polarity is also clearly �� marked with + and -) pit„,,,. 1111111 Pressure relief valve Inner cover 2 ......spiL-- Absorbent separator used to immobilize electrolyte I I Semi - permeable Lead - calcium grids 0 membrane separator Cell group ill p. Cell case (high impact polystyrene) #Batfe $1 4ctfication's Battery Model Capacity @ 20 Hour Width* Depth* Height with Approximate Discharge Rate - - . -- Terminals Weight* 2081 -9272 6.2 Ah 6 -1/8" (156 mm) 2 -5/8" (67 mm) 4" (102 mm) 5.75 lbs (2.6 kg) 2081 -9274 10 Ah 6" (153 mm) 4-1/16" (103 mm) 4" (102 mm) 9.2 lbs (4.2 kg) ,, , 2081 -9288 12.7 Ah 6" (153 mm) 4" (102 mm) 4" (102 mm) 9 lbs (4.1 kg) 2081 -9275 18 Ah 7 -1/4" (184 mm) 3 -3/8" (86 mm) 6 -5/8" (168 mm) 14.3 lbs (6.5 kg) 2081 -9287 25 Ah 6 -5/8" (168 mm) 5" (127 mm) 7" (178 mm) 19.4 lbs (8.8 kg) 2081 -9271 (rectangular case, 33 Ah 12 -1/2" (318 mm) 3 -3/8" (86 mm) 7- 1/16" (179 mm) 26.6 lbs (12.1 kg) typically for service) 2081 -9276 ( "square" case, 33 Ah 7 -3/4" (197 mm) 5 -1/4" (133 mm) 6 -3/4" (171 mm) 26.5 lbs (12 kg) use for new) 2081 -9296 50 Ah 9 -1/2" (241 mm) 5 -1/2" (140 mm) 8 -7/8" (225 mm) 41.8 lbs (19 kg) 2081 -9279 110 Ah 11- 3/16" (284 mm) 10 -1/2" (267 mm) 9" (230 mm) 82 Lbs (37 kg) * Dimensions and weight are per battery and are for reference only. Exact size may vary. Refer to the tables on page 3 mounting compatibility. These batteries are 12 V each and series connected for 24 V system use. NOTE: When wired in series for 24 V output, these batteries are to be of identical voltage, appearance, model number, and approximately the same date of manufacture. 6760404, to ' ..0ZI 'cations ! Nominal Voltage Rating 12 Volts per battery Discharge Rating 20 Hour Rate Typical Charge /Discharge Cycles 100 to 150 Preferred Charge Temperature Range 60° F to 90° F (15.6 °C to 32.2° C) 2 S2081- 0006 -18 5/2007 Battery #bilityfor„ Fire, AlarmControl +Panel Mounting;'=: NOTE: Refer to individual fire alarm control panel product data sheets for additional battery application information Simplex Control Panel Model Series (see legend and notes below) Battery Capacity • Model 4003 4004 4004R 4005 4006 8 4009 4100 & 4120 4020 4008 (all models) 4010 410011 (2, 4 or 6 -Unit) (2. 4 or 6 -Unit) 2081 -9272 6.2 Ah ✓ ✓ J ✓ ✓ J J 1, 2, or 3 bay J ✓ 2081 -9274 10 Ah ✓ ✓ ✓ ✓ J J ✓ 1, 2, or 3 bay ✓ J 2081 -9288 12.7 Ah ✓ NA ✓ ✓ ✓ ✓ ✓ 1, 2, or 3 bay J J 2081 -9275 18 Ah ✓ NA Note 3 ✓ Ext Ext Note 2 1, 2, or 3 bay ✓ ✓ 2081 -9287 25 Ah NA NA Note 3 Ext Ext NA ✓ 1, 2, or 3 bay ✓ Ext 2081 -9271 33 Ah 'NA NA Note 3 Ext NA- . NA Note 3 1, 2, or 3 bay Ext Note 4 (rectangular) 2081 -9276 33 Ah NA : NA Note 3 Ext ' NA . NA •• Note 3 1, 2, or 3 bay J Ext ( "square ") 2081 - 9296 50 Ah NA NA I Note 3 NA . NA NA Note 3 2 or 3 bay Ext Ext 2081 -9279 110 Ah Requires extemal battery cabinet ✓ = Can be placed in the respective equipment cabinet Ext = External battery cabinet is required, refer to selection chart on page 4 NA = Not applicable /not compatible NOTES: 1. These batteries meet the requirements of UL, ULC, and Factory Mutual for use with respective equipment battery chargers listed above. Contact your local Simplex product supplier for proper battery selection per system requirements. 2. 4010 Cabinets will accommodate 2081 -9275, 18 Ah batteries, but will not allow bottom entry conduit. 3. Use 4081 series companion cabinet and charger, refer to page 4. 4. 4020 Cabinets will accommodate 2081 -9271, 33 Ah batteries, but will not allow bottom entry conduit. 5. Some control panel models are listed for battery replacement reference only. Exfernal Batte_ryCabinet Compatibility Reference; Battery Cabinets without Chargers (connects to charger in panel) 2081 = 9275';: e,: 2081= 9287::.,; '`` :;;_,2081 - 9271`: :.; Z00;9276 ; 2081 = 9296'..2081 -9279 Cabinet Panel Compatibility 18 Ah* . 25 Ah "; ,' Rectangular 33 Ah , 33 Ah S0 Ali w. . 110 Ah 2081 -9270 multiple J ✓ J ✓ ✓ NA :" 2081 -9280 4100U/4100+ 2081 -9281 multiple J J J 1 J NA 2081 -9282 4009 -9801 multiple J ✓ *• NA_' NA NA NA, . 4009 -9802 multiple J NA J NQ NA NA Battery Cabinets with Chargers 2081 -9275 2081 -9287. .- 2081 - 9271 ,. 2081 -9276. 2081 -9296 2081 -9279 Cabinet Panel Compatibility . 18 Ah* 25 Ah' `Rectangular.33 Ah .Square 33 Ah ':50 Ah . 110 Ah 4081 -9301 4081 -9302 4004R and 4010 J J J J ✓ NA .. 4081 -9303 4081 -9304 > 4081-9306 •' • • • . • 4100U 'NA NA • NA NA' J J 4081 -9308 * Batteries smaller than those listed are normally mounted in the product cabinet ** 25 Ah capacity was effective as of 7/2005. ✓ = Can be placed in the respective equipment cabinet NA = Not applicable /not compatible 3 S2081- 0006 -18 5/2007 External,S 04 ; 0,016.el00:6Ift 66. Reference;; Battery Cabinets Without Chargers; Shallow Design with Front Door Model Color Listings Description • Dimensions 2081 -9281 Beige UL and 2-Unit, 4100 style cabinet without charger; with locking 25 -3/4" W x 20 -3/4" H x 6 -3/4" D solid door and battery shelf, primarily for use with 50 Ah 2081 -9282 Red FM batteries ( 654 mm x 527 mm x 171 mm) UL and For up to 25 Ah External battery cabinet without charger, 16 -1/4" W x 13 -1/2" H x 5 -3/4" D 4009-9801* Beige FM batteries* 41 3 mm x 343 mm x 146 mm with locking solid door and battery mm)* (413 ) For up to 33 Ah harness; for close rippled mounting to 25 -3/4" W x 20 -3/4" H x 4 -1/8" D 4009 -9802 Beige UL batteries fire alarm control panel cabinet (654 mm x 527 mm x 105 mm) * Depth increased for 25 Ah batteries effective 7/2005. Battery Cabinet Without Charger; Deep Design with Hinged Lid Model Color Listings Description - - . . = ; •. Dimensions 2081-9270 Red Not listed Battery cabinet without charger; cabinet has vented front, 26 -1/2" W x 12" H x 12" D and hinged lid with support rod and lock on top (673 mm x 305 mm x 305 mm) Chargers for use with 4010 Fire Alarm Control Panels and 4004R Suppression Release Systems (refer to data sheet S4081 -0001) Model Color Input Voltage Description Dimensions 4081 -9301 Beige Battery cabinet with charger for the 4010 and 120 VAC 4004R fire alarm control panel; for up to 50 Ah 4081 -9302 Red 22 -1/2" W x16 -3/4" H x 8 -3/8" D batteries; with front door (572 mm x 425 mm x 213 mm) 4081 -9303 Beige 220/240 VAC Listings include: UL, ULC, FM, CSFM, and MEA 4081 -9304 Red (NYC), see data sheet for details Battery Cabinet Without Charger for 110 Ah Batteries; for use with compatible panel mounted chargers (refer to data sheet S2081 -0012) Model & Compatible Listings Color Cabinet.Description- Chargers Charger Dimensions 4100 -9xxx 4100U System Power Supplies �( Series (SPS) 4100 -5111 Battery cabinet for 4100 -5112 4100U Additional SPS 2081 -9279, 110 Ah 4100 -5113 2081 -9280 batteries; includes 4100 -5125 Listings Red 80 A battery fuse, 4100 -5126 (RPS) Remote Power Supply 26 -1/2" W x 12" H x 12" D include: UL terminals and 4100 -5127 (673 mm x 305 mm x 305 mm) and CSFM battery connection 4100 -5120 cables; see data 4100 -5121 4100U TrueAlert Addressable sheet for details 4100 -5122 Power Supply (TPS) • 4100 -0104 4100 -0114 4100 Legacy power supplies 4100 -0124 4100U Compatible Battery Cabinet With Charger for 110 Ah Batteries (for ULC listed systems and for other applications unable to use panel mounted power supply charger; refer to data sheet S4081 -0002) - Model Color Input Voltage .Description . . : Dimensions . • 4081 -9306 Red 120 VAC Battery cabinet with charger for up to 110 Ah batteries; 220/230/240 VAC, NOTE: Required for ULC listed charging of 27 -7/8" W x 13 -1/2" H x 14 -5/8" D 4081 -9308 Red 110 Ah batteries; Listings include: UL, ULC, FM, (708 mm x 343 mm x 371 mm) multi - tapped CSFM, and MEA (NYC), see data sheet for details 4100 -9837 Green LED Power -on Indicator Kit, required for ULC listing, mounts above access panel using knockout provided Tt'co, Simpler, and the Simpler logo are trademarks of Tyco International Services AG or its affiliates in the U.S. and /or other countries. Tyco Safety Products Westminster • Westminster, MA • 01441 - 0001 • USA S2081 0006 - 18 5/2007 Si " ' l e www.tycosafetyproducts 2007 Tyco Safety Products IV'esoninster. All rights reserved. All specifications and other Information shown mere current as ofdocument revision date and are subject to change without notice. Simplex LifeAlarm Fire Alarm Controls UL, ULC Listed; FM, CSFM 4009 IDNet NAC Extender For Control from 4010 or and MEA (NYC) Approved* 4100U IDNet Communications, or Conventional NACs Features;: Provides additional notification appliance circuit - - (NAC) capacity with flexible operation modes and L, ' 4.4 power - limited design Four, Class B (Style Y) NACs are standard: up to 6 NACs 1 ... _ • Rated 2 A @ 24 VDC, compatible with standard 4009 IDNet 24 VDC notification appliances NAC Extender — — • — Can be selected to provide synchronization for Simplex e ' C�7 C visible notification strobe flashes '� • Capable of controlling TrueAlertTM non - addressable o notification appliances operating with SmartSyncTM - Optional IDNet wcnio,w xceereivvEx .: Channel Repeater two -wire control mode = _________= / - - -- � Input control can be from either: • IDNet addressable communications from a Simplex model 4010 or 4100U Fire Alarm Control Panel ** 2-Wire IDNet SIC • Or from one or two conventional 24 VDC NACs with Communications multiple output control options I Fiber Optic IDNet ` I Communications or , IDNet communications control benefits: •� NAC Control • Provides status monitoring and individual NAC control.. using a single address per 4009 IDNet NAC Extender IDNet Fiber ;., ,. • Supports IDNet "Device Level" earth fault location Optic Transmitter � `,' WALKTESTTM operation is available with either input choicer 4010 (shown) or 4100U Fire Alarm - , Internal 8 A power supply/battery charger: Control Panel • Charges internal batteries up to 12.7 Ah or up to 18 Ah Fire Alarm Control Panel with batteries in external cabinet Conventional NACs • Provides status monitoring of battery, input power, and earth faults 4009 IDNet NAC Extender Connection Reference Drawing Optional 4009 IDNet NAC Extender modules: • IDNet Communications Repeater provides Class B Inf'�oducton_. (Style 4) or Class A (Style 6) output ADA Compliance. Complying with the notification • IDNet Communications Fiber Optic Receiver/Repeater, requirements of ADA (Americans with Disabilities Act) available as Class B or Class A may require more notification appliance power than is • Four additional Class B NACs, rated 1.5 A @ 24 VDC available within the fire alarm control panel. When additional power is required, a Simplex 4009 IDNet NAC • Class A (Style Z), Two Circuit Adapter Module Extender can provide up to 8 A of NAC power with up to UL Listed to Standard 864 eight, supervised reverse polarity NACs. External ^Accessories'; Location Flexibility. The 4009 IDNet NAC Extender can be mounted close to a compatible dedicated host 4090 Series IDNet communication fiber optic panel or can be located remotely for convenient power transmitters: distribution. Multiple operation modes and multiple • For applications requiring the data integrity available connection options further increase location flexibility. with fiber optic communications Additional Information. For additional operation detail • Available as Class B (Style 4) or Class A (Style 7) and application information, refer to Installation • Mounts in standard six -gang electrical box Instructions 574 -181. External battery cabinet for 18 Ah batteries • ULC listed model is 4009- 9202CA This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. Simplex IDNet addressable communications are protected by U.S. Patent No See CSFM Listing 7300 - 0026 :214 for allowable values and /or conditions concerning 4,796,025 Refer to specifications for additional IDNet wiring information. 41000 material presented in this document It is subject to re- examination, revision, and possible requires revision 11 software or higher for compatibility 4010 requires 2 cancellation Accepted for use — City of New York Department of Buildings — MEA35 -93E. software or higher for compatibility. Additional listings may be applicable: contact your local Simplex product supplier for the latest status. t Simplex WALKTEST service testing is protected under U.S. Patent No 4,725,818. S4009- 0002 -3 7/02 Application, an'd',O:per'ation Information: Hardwire Control Applications. For applications where an existing (or new) conventional NAC needs IDNet Addressable Communications Compatible. additional power, the 4009 IDNet NAC Extender can be Up to five, 4009 IDNet NAC Extenders can be controlled controlled directly from the NAC. Either one or two on a single IDNet communications channel. Each output NACs, from either the same, or from different host fire NAC can be individually controlled for general alarm or alarm control panels, can be connected to control the 4009 _ selective area notification requiring only one point IDNet NAC Extender output NACs. Multiple control address per Extender. Individual Extender NACs can also selections provide flexible operation. (Refer to page 4 for be manually controlled from the host panel. IDNet more detail.) Alarms from the host panel will activate the controlled extenders will inform the host panel of troubles four, 4009 IDNet NAC Extender NACs (or optionally, via IDNet communications. eight NACs) to extend the alarm. Optional IDNet Repeaters. IDNet communications The 4009 IDNet Extender monitors itself and each of its can be repeated with the optional IDNet Repeater Module output NACs for trouble conditions, including earth or with the optional Fiber Optic Receiver Module. Up to faults. Extenders wired to conventional NACs will 100 of the IDNet channel points can be repeated once indicate a trouble by opening the path to the NAC's (refer to pages 3 and 5 for details). Repeated IDNet end -of -line resistor, but retaining the ability to respond to communications also support the "device level" earth alarms. Individual troubles are also annunciated by LEDs fault location utility of the host panel. located on the 4009 IDNet NAC Extender main circuit board. (Refer to page 7 for more diagnostic information.) } ire .! Y ` �.'U "c^zsts P,roducf Selectiorp Standard Models Model • ' Description • . 4009-9201 120 VAC input 4009 9202CA* 4009 IDNet NAC Extender with 4, Class B (Style Y) NACs and 8 A power supply 4009 -9301 240 VAC input * ULC listed model Optional Modules (for on -site installation) l Model .' � _. D escription - Comments . 4009 - 9807 Additional four point NAC module, rated 1 -1/2 A One maximum Class B (Style Y), 4009 -9808 Dual Class A (Style Z) adapter (for two NAC outputs) Select as required (4 maximum) 4009 9809 IDNet Repeater, output is Class A (Style 6) or Class B (Style 4) Select either an IDNet Repeater or a 4009 -9810 Fiber Optic Receiver Class B (Style 4) Fiber Optic Receiver as required 4009 -9811 Class A (Style 7 fiber, Style 6 IDNet) 4009 -9805 Red Applique for door Select if required 2975 -9801 Beige trim 1- 7/16" wide (78 mm), use if required for Semi -Flush Trim Kit 2975 -9802 Red trim semi -flush installations Battery Selection (select battery size per system requirements) , odel ; . _ _ . .,Description . - S.',,. - .Com M nts 2081 -9272 6.2 Ah Battery, 12 VDC 2081 - 9273 8 Ah Battery, 12 VDC Two batteries are required, 24 VDC 2081 -9274 10 Ah Battery, 12 VDC operation 2081 -9288 12.7 Ah Battery, 12 VDC 2081 9275 18 Ah Battery, 12 VDC Requires external battery cabinet, two batteries are required, 24 VDC operation External Accessories (select per system requirements) Model. Description - . - . - , Com 4090 -9105 IDNet Fiber Optic Class B (Style 4) operation Mounts in six -gang electrical box, refer to 4090 -9107 Transmitter Class A (Style 7) operation page 4 for mounting details 4009 -9801 External battery cabinet for 18 Ah batteries, beige 16-1/4" W x 13-1/2" x 4 -1/8" D (413 mm x 343 mm x 105 mm) 2 S4009- 0002 -3 7/02 Typical IDNet,Connection Example: �'� Typical IDNet compatible devices z- . - (Refer to individual devices for actual wiring requirements, some wiring is not shown.) I MIN * s t '' IDNet addressable communications channel, ' i ! i ' .4 _,....-/ shown Class B (Style 4) Conventional NAC operation (horns) Output NACs, four standard, eight with expansion option �- . . - 9 P P Select conventional t u ,. nr. �7�w.,-, � :•�,,r- o�,:,.2�;.�.•�':�_.�.� or SmartSync -. operation per NAC 4100U (shown) or 4010 Fire _ — ` Alarm Control Panel _ 7. _ tee � ( . 59 0t4c tlAC EXTEnv.R Wit;. SmartSync operation (horns and strobes) 4009 IDNet NAC Extender with - -_ -- - optional internal IDNet Repeater Conventional NAC a= a IN l°) operation (strobes) Repeated IDNet Channel: '° "° �� up to 100 devices maximum on repeater output, • 250 devices total on IDNet Channel IDNet devices and additional 4009 IDNet NAC Extender(s) ; NOTE: Up to five (5) 4009 IDNet NAC Extenders may be connected to one IDNet channel. IDNet communications can be repeated only once (can pass through only one series connected repeater or one fiber optic receiver). 4Typ cal Fiber SystemrC.onneetlons Two fiber cables, 3000 ft Output NACs 4090 -9105, Class B (914 m) maximum distance ®..®®aa (Style 4) Output F .e®®®EI®am® ®q II IIIIIIltlllIIIIIIIIIIIIIIIIIIWIIIIIIIIIIIIIIIIIIIil s Optic Transmitter /\ > -. LLLLL ) 611911111110211MEE 2 .,.,,,,,,,,-: 7 7.7 4 "5.E. ;.",:,a::' / i i a • IDNet addressable communications `" :•- channel Class B (Style 4) or Class A (Style 6), Class B shown Repeated IDNet Channel up to 100 devices maximum on repeater output, 250 devices total on IDNet Channel IIIIIIIlllllllllllllllllllllllllllllllllllllllllll Four fiber cables, 3000 ft \ 4010 or 41000 Fire (914 m) maximum distance \� Alarm Control Panel / iii • i • - 24 VDC power for ®mmonege®®® � : fiber op tic transmitters - • III , 4090 -9107, Class A (Style 7) II ` • Output Fiber Optic Transmitter "- r 4009 IDNet NAC Extenders with optional Output NACs internal IDNet Fiber Receivers NOTE: Up to five (5) 4009 IDNet NAC Extenders may be connected to one IDNet channel, IDNet communications can be repeated only once (can pass through only one series connected repeater or one fiber optic receiver). Fiber optic transmitters connect to only one 4009 IDNet NAC Extender. 3 S4009- 0002 -3 7/02 HardWifilOonttol ConnedionFlnfo triation : SmartSync Notification Appliancer NAC Input Selections. The 4009 IDNet NAC The TrueAlertTM Notification Appliance product Extender can be selected to: line includes addressable and non - addressable operation. • Track input NAC operation or to provide a locally Non addressable models are available with 2-wire generated code, selectable per NAC input Smart Sync operation or conventional 4 -wire operation. The following details apply to use with the 4009 IDNet • If selected for local coding, NAC outputs can be either NAC Extender: Temporal Coded or 60 Beats /min March Time Coded, one code selection per extender (input NACs must be on • TrueAlert non - addressable models with SmartSync continuous with Alarm) operation allow audible notification to be separately • Additionally, NAC outputs can be selected to provide controlled over the same wire pair that controls the Simplex strobe synchronization signal. This signal visible notification (protected under U.S. Patent No. will synchronize the flashes of synchronized strobes but 6,281,789) will be ignored by free -run strobes and audible devices. • 4009 IDNet NAC Extenders can be selected to provide (Strobes are for operation by noncoded NACs.) SmartSync operation whether controlled by IDNet communications or conventional NACs NAC input to NAC output control can be selected for • IDNet control allows output NACs to be individually standard and optional NACs per the following table: selected for conventional or SmartSync operation Conventional NAC Output Operation Options • With NAC input control, all output NACs are selected Input A . B. C . for either conventional or SmartSync operation NAC 1 NACs 1 & 2, 5 & 6 NACs 1 -4 NACs 1 -8 • Class A (Style Z) SmartSync operation requires NAC 2 NACs 3 & 4, 7 & 8 NACs 5 -8 None SmartSync Control Module (SCM) 4905 - 9938 (refer SmartSync NAC Output Operation to data sheet S4903 -0010 for details) Input NAC Co Function • Refer to data sheet S4009 -0003 for TrueAlert NAC 1 Strobe Control addressable operation details, contact your local All NAC outputs (1 Simplex product supplier for further information on NAC 2 Horn Control P P PP specific TrueAlert notification appliances JHa01,*(f ,font 4.;19 C. Co,1.1* on OneNLine Reference Diagram Up to eight (8) output NACs total; hardwire control can be i selected to map NAC inputs to different combinations of NAC outputs depending on system requirements NAC 1 input (see Note 1) • •• •• — __— Conventional NACs REFfrj •• _ 6 —.. 11 With hardwire control, o NAC outputs are all ' �.:° Output conventional or all u - _ _ _ _ _ _ _ _ _ _ �x. e r� iA ExTEteER ;,; NACs SmartSync operation ,. — —' _ e 0m SCM / 4009 IDNet NAC Extender (°1 Fire Alarm Control Panel with Conventional NACs SmartSync operation \ 4905 -9938 SmartSync Control Module is required NAC 2 input for Class A output wiring of SmartSync NACs (optional, see Note 1) To additional 4009 IDNet NAC Extenders (up to four (4), 4009 IDNet NAC Extenders per NAC); see Note 2 Notes: 1. For separate audible and visible output NAC control, or SmartSync NAC output operation, two (2) input NACs are required. NAC 1 is "on- until - reset" and NAC 2 is "on- until - silenced." 2 To synchronize strobe flash outputs for up to four (4) 4009 IDNet NAC Extenders, use the synchronized strobe output from a Synchronized Flash Module (4905 -9914 for Class B operation, 4905 -9922 for Class A operation) or, if available, from a NAC selected to provide synchronized strobe flash output. NOTE: DO NOT USE a NAC selected for SmartSync operation for this function. Refer to Installation Instructions 574 -181 for additional information and application guidance J 4 S4009- 0002 -3 7/02 Input Voltage 120 VAC Inpu (4009-9201) 3A @ 102-132 VAC, 60 Hz 240 VAC Input (4009-9301) 1.5A@204'2O4 VAC, 5O0OMz Conventional reverse polarity operation Hardwire Control from External NACs ' Sm8@24VDCin Alarm (rated 45mA maximum 211to2S1VDC) Input Requirements Maximum operating voltage is 18 to 32 VDC, filtered or unfiltered Output Ratings ' Auxiliary Output 500 mA @ 24 VDC nominal Standard NACs 2A each @24VDCnominal Total current must not exceed 8A Optional NACs (requires 4009-9807) 1.5 A each @ 24 VDC nominal Optional Modules � � . � |DN��RnpeaterK8odu|e � `� �' ^ �- �� . ' ' ` ^' ` � � . ` . . Input Power 70 mA @A24VDC. system supplied IDNet Input, One Address Maximum distance from IDNet source is 2500 ft (762 m) Repeated IDNet output for up to 100 devices (total lDNet devices not to exceed 250 per channel) Maximum distance to farthest device from 4009 IDNet NAC Extender output is |DNet Output Spedfioahons 2500 ft (762 m) Total distance including "T-taps" is 10,000 ft (3048 m) Class 8 (Style O) loop maximum distance is25OOft(7O2m).nu^T~taps 'Finer • • ' ` ' �/p� ` ' *' '� �' ���/�y ` � • ��pUc ' ~ "��`'���s��6��������i��' ` ~"��«�u����!� '� '���'-, 4OOS-901O. Class B (Style 4).O5mA@24VDC. system ouppfied Input Current 4009-9811, Class A (Style 7), 80 mA @ 24 VDC, system supplied IDNet Output Specifications Same as those for Repeater Module (see above) Fiber Optic Transmission Distance 3000 ft (914 > maximum � � � e � � Y�?�' y� �"����' u ,•��� Operating Temperature 32° to 120° F (0° to 49° C) Operating Humidity Range 10Y6 to 80% RH from 32° F to 104° F (0° C to 40° C) Wiring Connections* Terminal blocks for 18 AWG (stranded) to 12 AWG (solid) Input Voltage 18.9-32 VDC from compatible listed re alarm supply 4090-9105, Class B(�y|o4) ' 3OmA6D24VDC Input Current 4O9O'S1O7. Class A (Style 7).35mA@24VDC Type ST connectors Fiber Optic Connections and cable Multimode, graded index, 50/125pm, 62.5/125 pm, 100/40 pm or 200 pm requirements 4090-9105, Class B (Style 4) operation, two fiber cables required 4O8U'91O7. Class A (Style O) operation, four fiber cables required Module Size (with mounting bracket) O'13/1O^VVx3'3/4^Hx1'1/8^D(173mmxS5mmx29mm) Green LED flashing = transmit On-board Status Indicators Red LED flashing = receive Separate red LED on 4090-9107 = Class A (Style 7) receive Communications Dimp|ex|DNet Fiber Optic Transmission Distance 3000 ft (914 m) maximum VWhngConnections^ Terminal blocks for 18 AWG (stranded) to 12 AWG (solid) Operating Humidity 10% to 90% RH from 32° to 104° F (0° to 40° C) Operating Temperature 32° F to 120° F (0° to 49° C) - Metric wire equivalents: 1O4VVG=O.O2mm'.12AVV8=331mm 5 s4009-0002'3 7/02 • 4009 IDNet NACIEi endel Moiunting4and Module i Cabinet depth !. 16 -114" (413 mm) ' r4 -1/4" (108 mm) 1 6 10- 29/32" (277 mm) Door, 5/8" - (16 mm) thick �` L ® Cs 1 _ ht 1 1 .17.17 '1 ®® � 0 1_I_I- 11=1?I_ I Ii ' ' - Optional Class A 4009 -9807 Additional Four 13 -1/2" adapter modules point module (shown with `^," (343 mm) Class A adapters) ;., Exposed cabinet l 1 I dimension for —a' �, ua ( System Module J o o semi -flush mount i pl ` 1" (25.4 mm), s Knockouts for screw IDNet repeater 1 -318" (35 mm) with or nail mounting holes fiber optic rece semi -flush tri C o o ,u,.,.r:r.•,c,,..... , 1 . ter. — — — — — — C f 12 (305 mm) -I , `'� j ~--'-----..-- -. Battery location, no conduit entry or wiring in ' * this area (12.7 Ah battery outline shown) ; 1-, i 0 0 '` "` / Semi -flush trim option - Non -power limited wiring area (AC input) 1 -3116" wide (30 mm), —a- 3/8" (9.5 mm) thick — A ) Wall surface reference for semi -flush mount ) NOTE: Recommended conduit entrance varies with module selection. Refer to general installation ' instructions 574 -181, specific module installation instructions, and to field wiring diagrams - 842 -068 before locating conduit entrance. 44009 IDNet NAC Extender�`C�abme Do 4Ifti abit.51l1` r ter. Optional red applique (4009 -9805 ) to$44,44r.svoftlmv4".16nritatftrd6t402,00",para ft', itiK.,..**.M0170,„,„4470/4404Ptirni40140 14,0 4009 HNA�C EXTENDER a x +ss ss'ssIs- s'sis=` .•'• Mil •:••:•;••• :. •`•:• IN ME - . 6 S4009- 0002 -3 7/02 4090 9105/ 9107 =IDNet Fi bet. Optic Transm itter n Mounting InfthThatior Surface mount box: 0 0 0 0 0 0 Simplex model 2975 -9217 (ordered separately) n n l /� l Flush mount masonry box: use 6 -gang box, RACO # 960, 2 -1/2" deep �� 0 0 0 0 0 (64 mm), or RACO # 965, 3 -1/2" (89 mm) U (J (U ) L () U r deep, or equal (supplied by others) wr011 Iltali ' O C Flush mount ganged boxes: o • - use 6 -gang box, 1 -1/2" (38 mm) C ° x ': 0 minimum depth; six, RACO # 400 O • or equal, (supplied by others) ° 0 0 0 0 0 0 / IDNet fiber optic transmitter: 4090 -9107, Shown, Class A (Style 7) output 4090 -9105, Not shown, Class B (Style 4) output INSTALLATION NOTE: Fiber optic cable bend radius should be 2" (51 mm) minimum, or per Manufacturer's specification. 0 0 0 0 0 0� Six -gang blank cover plate Mulberry Metal Products 97156 or equal (by others) t Service ,agnosticTeatures Power -up Self- Diagnostics. Upon power -up, the LED Status Indicators are provided for the following: 4009 IDNet NAC Extender tests each module and • Each NAC (standard and optional) has a dedicated performs earth fault diagnostics. Trouble conditions are yellow LED that: communicated to the host control panel and are also — During supervision provides a slow flash to indicate displayed on diagnostic status LEDs in the 4009 IDNet a short circuit condition and a fast flash to indicate NAC Extender. When connected via IDNet an open circuit communications, detailed status information is available at the host. When controlled with conventional NAC — During an alarm, the LED follows the NAC output inputs, common troubles are signaled by providing a (on steady or flashing with coded output) polarized open circuit that disconnects the NAC wiring • Four, general status yellow LEDs provide nine from its end -of -line resistor but still allows a reversed separate indications listed in priority of urgency. As a polarity alarm to be received. trouble is eliminated, any remaining trouble(s) will Door Mounted Reference Label. The 4009 IDNet then be indicated until the 4009 IDNet NAC Extender NAC Extender has a detailed programming and is returned to normal operation. diagnostic label inside the front door that provides a quick • AC power status is indicated by a green LED that is reference for both installation and checkout. on when AC is normal. During low AC (brownout) conditions or with no AC, the LED is off. Additional power and battery status is indicated by the general status LEDs. 7 S4009- 0002 -3 7/02 40cdti I et NAC' Culrrent C.halrt Panel Module Selection (shaded model numbers are optional modules) Model Description Supervisory Actual Alarm Current Actual Alarm Current Supervisory 4009 -9201 120 VAC input Basic Panel 85 mA 85 mA 185 mA 185 mA 4009 -9301 240 VAC input 4009 - 9807.. Additional Four Point NAC 40 mA + + NAC loads + NAC loads (add below) (add below) 4009-9808 Dual Class A Adapter (current " included in basic panel value) 4009 - 9809 *. ID Net Repeater 70 mA 70 mA 4009 - 9810 * Fiber Optic Receiver, Class B 65 mA + 65 mA + 4009 - 9811 * Fiber Optic Receiver, Class A 80 mA • 80 mA IDNet Devices, 0.7 mA each, maximum of 100 Total devices + Total devices ( + (see note 5) x 0.7 mA each x 0.7 mA each Auxiliary Power Output, calculate per total 500 mA + 500 mA (A2) + device requirements (see note 5) maximum maximum Total Supervisory Current = (A) + Total 4009 IDNet NAC Extender Panel Alarm Current = (B1) * Only one of these three modules can be chosen for a single 4009 IDNet NAC Extender. t NOTE: IDNet Fiber Optic Transmitter current is supplied from the host fire alarm control panel. NAC Loads • NAC Type' NAC Circuit # NAC Alarm Current Circuit 1 + Circuit 2 + Standard Panel NACS, 2 A maximum per NAC (see note 5) Circuit 3 + Circuit 4 + Circuit 5 + • Circuit 6 + Optional Four Point NAC Module, 1.5 A maximum per NAC (see note 5) Circuit 7 + Circuit 8 + Total NAC Loads Alarm Current = (C) Total 4009 IDNet NAC Extender Panel Alarm Current (enter B1 from above) = .(B2) + Procedure: Total Alarm Current = (D) 1. Calculate total panel supervisory current (A). 2. Calculate total panel alarm current (B1) [convert mA to A, example: 350 mA = 0.35 A]. Copy (B1) into block (B2). 3. Calculate total NAC loads alarm current from notification appliance ratings (C). 4. Add (C) + (B2) to determine total alarm current (D). 5. Total of IDNet Device Current (A1) + Auxiliary Power Output Current (A2) + NAC Loads Alarm Current (C) is 8 A maximum. 6. Refer to Simplex battery selection document 900 -012 for recommended battery size for specific standby requirements (i.e. 24 hours supervisory, 5 minutes of alarm). Internal cabinet space is provided for batteries up to 12.7 Ah. Tyco. Simplex, the Simplex logo, Lrje ilarm. IDNet. WAIXTEST. Smart,Svnc, and TrueAlert are trademarks of Tvco International AG or as affiliates in the U.S. and/or other countries. l ex TEPG - US • 91 Technology Drive • Westminster, Massachusetts • 01441 - 0001 • USA S4009 0002 - 3 7/02 t 2002 TEPG -US (a Tyco company). All rights reserved Al! s pec fcanans and other mfarntauan www.tepg.com shown were current as al document revision die and are .subject so change without nonce o SiMPleX System Accessories, LCD Annunciators UL, ULC Listed; FM, CSFM, 4606 -9101 LCD Annunciator for 4010, and MEA (NYC) Approved* 4006, and 4008 Fire Alarm Control Panels Features Remote LCD annunciator for use with Simplex m model 4010, 4006, and 4008 fire alarm control SYSTEM ISNORMAL panels 12Y33: 13 am •MON 30'AUG 04 • ®'- P R LCD readout provides: • Two lines of 40 characters each C_, m • Wide viewing angle, super -twist design SempIex • LED backlighting Control switches and status LEDs for: > 4606 LCD Annunciator • Alarm, supervisory, or trouble acknowledge (keyswitch access controlled) DescnptionAContmued)' • Alarm silence • System reset Communications. Data communications require a single twisted, shielded pair that supports other Three programmable LED indicators: annunciators on the same communications channel. • Two LEDs are selectable as red or yellow Model 4010 Series panels control up to six annunciators; • One LED is selectable as green or yellow model 4006 and 4008 Series panels control up to four • With provisions for custom labeling annunciators. Additional features: Indications. Alarm, Supervisory, and Trouble conditions are also indicated by dedicated LEDs and a • Information is transmitted over a single twisted, tone -alert audible indication. Each condition has a shielded pair; separate wiring is required for 24 VDC dedicated acknowledge push- button switch that silences control panel power the tone -alert but leaves the LED on until all conditions in • Tone -alert sounder provides local audible indication that category are restored to normal. • Lamp and LCD are functionally tested each time the Activity Scrolling. Repeated operation of the keyswitch is turned on appropriate acknowledge switch will scroll the LCD • Mounts flush on standard 6 -gang electrical box display showing activity in the sequence of occurrence. Mounting and trim options: The internal tone -alert also sounds to indicate the operation of any of the push - button switches. • Surface mount box model 2975 -9217 (ordered separately) i O: � eraf ion� • Brushed aluminum trim model 4603-9111 (ordered separately) Keyswitch Access. All switches on the annunciator are controlled by the "ENABLE" keyswitch with a key that is Descrl a 110`11; removable only in the disabled position. Enabled Operations. When enabled, notification Local Annunciation. 4606 -9101 LCD Annunciators appliances can be deactivated by pressing the "ALARM allow compatible fire alarm control panels to provide SILENCE" switch. Pressing the "SYSTEM RESET" information and control switches at convenient locations switch restores the system to normal operation. When away from the control panel. The LCD is an 80 character, system activity is normal, the LCD displays the time, back -lit, alphanumeric display with information presented date, and "SYSTEM IS NORMAL." in clear and descriptive English. Typical content includes: point status (alarm, trouble, etc.), alarm type (smoke detector, manual station, etc.), number of system alarms, * This product has been approved by the California State Fire Marshal (CSFM) pursuant to supervisory conditions, troubles, and custom location Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7120- 0026:225 for allowable values and /or conditions concerning material presented in this labels up to 40 characters long. (Some 4006/4008 document. It is subject to re- examination, revision, and possible cancellation. Accepted for messages are limited to 20 characters, refer to the control use — City of New York Department of Buildings — MEA35 -93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and panel documentation for additional information.) approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. S4606- 0001 -4 9/2004 iProduc Selection, .Mod Description., . > 4606 -9101 Remote LCD Annunciator with beige trim 4603 -9111 Brushed aluminum trim option Refer to specifications on page 3 for 2975 -9217 Matching surface mount box; ivory finish additional details 4081 -9011 Line matching resistor; 100 Q, 1/2 W; (part number 733 -974) 2081 -9044 Overvoltage protector; required where annunciator communications and power wiring exits and enters a building; refer to data sheet S2081 -0016 for details 46 6 = 9901 a Bato orm r Infati 2 X 40 LCD READOUT, LED backlighted during normal conditions and abnormal operating conditions S FIVE STATUS INDICATOR LEDs provide system ' status indications in addition to LCD information; T HREE P LEDs, LEDs flash to indicate the condition and then when e ach with custom labeling pocket l acknowledged, remain on steady until reset ,. �. a�4t ';` a u yb i.+w 4F :t"s. .� u: 3 {.: ',. s` ti' § ka4 .?., -,e i -,'� ,. - .SYSTEM IS , ; NORMAL 1 ________ ""` a 1;2: � 1 5. 0 m. , ',",MON. ` -30 AUG 04 l � 1 , , v e ws 3;Y } * f r ..ins . - tt ^' 4 . � � Tacit cx�, � �� � x..44 v2.._. n p� ,, ,� sw tr R 'it'R�'�' °Z0. � yy 3. �.t f1 � .F r - L n�1, h "* : „.„ ti „;,:Aa .,.” ,,,,,,,. _.„,sz,,_ ...„..,;�,.sp ?< .F- - - ':�1,,,aii n `. ....,. ....,''s� :.:..s. �; ? ..t'..' ® ® 3 Simplex / , ALARM ACK acknowledges CONTROL ENABLE KEYSWITCH a Fire Alarm condition and controls all switch functions; key is silences the panel and all removable only in disabled position annunciator tone -alerts I SUPV ACK acknowledges system SYSTEM RESET restores control supervisory conditions and silences the panel to normal when all alarmed panel and all annunciator tone -alerts inputs are returned to normal I TROUBLE ACK acknowledges ALARM SILENCE causes audible notification system troubles and silences the appliances to be silenced; used after evacuation is panel and all annunciator tone -alerts complete and while alarm source is being investigated I i 2 S4606 -0001 -4 9/2004 •4606 9101 1 CD,:An fa,to 646 c f cat ions General Operating Specifications Voltage 18.9 to 32 VDC, system supplied Normal Operating Current 110 mA (with LED backlighting on) Battery Standby Current 65 mA (during battery backup, LED backlighting is turned off after 30 seconds without switch activity) Alarm Current 140 mA maximum (LED backlighting is on and tone -alert is sounding) Operating Temperature Range 32° to 120° F (0° to 49° C) Operating Humidity Range Up to 93% RH, non - condensing at 100° F (38° C) Communications Type N2 external annunciator communications line For 4010 Panels "" Capacity Up to 6 annunciator modules total, 4606 -9101 or 4605 series, 24 point I/O modules Type N2 communications format but with different capacity For 4006 & 4008 Panels`" Capacity Up to 4 annunciator modules total; compatible with 4606 -9101, 4610 -9111, and door mounted LED annunciator Data Single twisted, shielded pair, 18 AWG (0.82 mm Wiring Requirements Power and Earth 18 to 12 AWG (0.82 mm to 3.31 mm wires for 24 VDC system power and Earth ground for electrical box (ground per local code) Bus style wiring Up to 4000 ft (1219 m); 0.58 pF (580 nF) maximum capacitance; 3552 maximum Distance resistance "T -Tap" wiring Up to 10,000 ft (3048 m) total wiring; up to 2500 ft (762 m) to farthest device Line Matching Bus -style wiring Connect one at panel and one at end of line 100 S2, 1/2 W; PID 4081 -9011; ( Resistor "T -Tap" wiring Connect one at panel and one at farthest device (part number 733-974) MO Mounting Information Trim Dimensions 4 -1/2" H x 11- 13/16" W (114 mm x 300 mm) Assembly Depth 1- 5/16" (33 mm), 1 -1/2" at terminal block location (38 mm) Standard Trim Finish Steel, painted beige 4603 -9111, Optional Trim Brushed aluminum (ordered separately) Trim Hardware Supplied with both slotted and tamper resistant screws Boxes for Masonry boxes Six -gang box, 2 -1/2" (64 mm) deep minimum Flush RACO # 960, 2 -1/2" deep or RACO # 965, 3 -1/2" (89 mm) deep or equal Mounting Single gang boxes Six, single gang boxes, 3 -1/2" (89 mm) deep minimum, RACO # 600 or equal (supplied by Conduit entrance is box dependent, refer to additional mounting information on others) Box selection note page 4 and Installation Instructions 574 -188 2975 - 9217, Surface Mount Box Option* (ordered separately) Dimensions 12" W x 4 -5/8" H x 1 -3/4" D (305 mm x 117 mm x 44 mm) Finish Painted steel, ivory finish " Reference Wiremold box number V5748 -6. "" Refer to control panel data sheets S4010 -0001, S4006 -0001, and S4008 -0001 for additional information. 3 S4606- 0001 -4 9/2004 • i + 'sit �,. s �. � - s7 �. Mountm. Informatlion.; Flush Mount Ganged Boxes: Use 6 -gang box, 3 -1/2" (89 mm) min. depth, RACO # 590 using knockouts 2 -1/2" from front, or RACO # 600 using side knockouts or rear cable clamps, or equal (supplied by others) � 1 •ATYto1i r 1 o�i ��N t0S1 AWAY Flush Mount Masonry Box: 1 - O 101111, NEW I 1 f ; Use 6 -gang box, RACO # 960, 2 -1/2" deep (64 mm) using top or bottom knockouts, or RACO # 965, 3 -1/2" (89 mm) deep, using . o 0 0 • 0 knockouts 2 -1/2" from front, or equal (supplied by others) � U U " \ U ' .': 0 / /' Surface Mount Box: .. 0 0 0 0 0 0 Simplex model 2975 -9217 / Alk AL MA AI Jili /1 (ordered separately) o ® 0 1 'YKx NN �,f .e,:; tt, a ii:TI:41 , . ; r r �t ._. ` ' :; .•. i� Trim plate 0 0 -=i O Terminal block access at 0 0 09 rt"" rear of enclosure, this side Annunciator Assembly NOTE: Enclosure extension into box is 10" W x 2 -5/8" H x 1- 5/16" D, 1 -1/2" deep at terminal block access, offset to left (254 mm x 67 mm x 33 mm, 38 mm), select conduit entry accordingly. midi Winn 1,Referencew Interconnection Wiring Notes: 1. Communications require a single 18 AWG twisted, shielded pair. 2. Power requires two, 18 to 12 AWG wires for 24 VDC system power, plus Earth Ground to each electrical box. 3. Refer to the installation instructions supplied with the compatible IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII IIIIIIIIIIIII a control panel for additional information f`. tiq 1 � • • 2. t3 O il �, IS��10 ma,„∎ - o _ a o ._ 4606 -9101 LCD Annunciators IIIIIIIIIIIIIIIIIIIIIIIIIIIIUIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIr 3 4010/4006/4008 Fire Alarm Control Panel - (4010 shown for reference) Tyco. Simplex, and the Simplex logo are trademarks of Tvco International Services AG or its affiliates in the U.S. and /or other countries, iViremold is a trademark of The Wjrenmld Company Simp Ei ��� Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4606-0001-4 9/2004 a www.tycosafatyproducts -usa wm.com 0 2004 Two Safety Products Westminster .411 rights reserved All specifications and other in]onnation shown were cvnrrtt in ofdocument revision date and are subject to change xuhout notice Simplex Multi - Application Peripherals UL, ULC Listed; FM, CSFM, MAPNET II or IDNetTM Communicating Devices and MEA (NYC) Approved* Addressable Manual Stations Features • Individually addressable manual fire alarm -044t. _ _ stations with: :..w 4 • Power and data supplied via MAPNET II or IDNet .. pi addressable communications using a single wire PULL DOWN pa ** • Operation that complies with ADA requirements : • Pull lever that protrudes when alarmed l t' " = ` • Break -rod supplied (use is optional) 1kTM `" "'`' ' " a . • Models are available with single or double action (breakglass or push) operation > 4099 -9001 Addressable Manual Station • UL listed to Standard 38 (front and side view) Compatible with the following Simplex control °'` :` '''': ` ' ` `' '''' , ''t om " ' " ' " ''' ' ` .'•OP panels: � ,c ., r'r x r x i ® � .} • Model Series 4010/4100/4100U/4120/4020 fire alarm sRFr4K Guess' 'PUSH `' control panels equipped with either IDNet or - t. ift hi n tt' l' MAPNET II communications - r a , s • oreenreo • : * � S �' h � ONLY • Model Series 2120 communicating device _ �,�, A � ;, � ; i t transponders (CDTs) equipped with MAPNET II g t s �' t communications _ . ? � _ v ,fl r . Compact construction: 4099 -9002 4099 -9003 With 2099 -9828 • Electronics module enclosure minimizes dust Breakglass Push Institutional infiltration Cover kit • Allows mounting in standard electrical boxes O'o.- 00101] • Screw terminals for wiring connections Activation of the Simplex 4099 -9001 single manual station requires a firm downward pull to activate the Tamper resistant reset key lock (keyed same as alarm switch. Completing the action breaks an internal Simplex fire alarm cabinets) plastic break -rod (visible below the pull lever, use is Multiple mounting options: optional). The use of a break -rod can be a deterrent to vandalism without interfering with the minimum pull • Surface or semi -flush with standard boxes or requirements needed for easy activation. The pull lever matching Simplex boxes latches into the alarm position and remains extended out • Flush mount adapter kit of the housing to provide a visible indication. • Adapters are available for retrofitting to commonly Double Action Stations (Breakglass) require the available existing boxes operator to strike the front mounted hammer to break the Desen : t - . . . glass and expose the recessed pull lever. The pull lever then operates as a single action station. The Simplex model 4099 -9001 addressable station Double Action Stations (Push Type) require that a combines the familiar Simplex manual station housing spring loaded interference plate (marked PUSH) be with a compact communication module that is easily pushed back to access the pull lever of the single action installed to satisfy demanding applications. Its integral station. individual addressable module (IAM) constantly monitors status and communicates changes to the connected control Station reset requires the use of a key to reset the panel via MAPNET II or IDNet communications wiring. manual station lever and deactivate the alarm switch. (If the break -rod is used, it must be replaced.) • This product has been approved by the California State Fire Marshal (CSFM) pursuant to Station testing is performed by physical activation of Section 13144.1 of the California Health and Safety Code. See CSFM Listing the pull lever. Electrical testing can be also performed by 7150 - 0026:224 for allowable values and /or conditions concerning material presented in this document. It is subject to re- examination, revision, and possible cancellation. Accepted for unlocking the station housing to activate the alarm switch. use — City of New York Department of Buildings — MEA35 -93E Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and ., MAPNET II and IDNet addressable communications designs are protected by U.S. approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. Patent No. 4,796,025. S4099- 0001 -6 10/2003 Addr Manu Statio oosd,o- Sele_co-g Addressable Manual Stations Model , - ' • Description , 4099 -9001 Single action 4099-9002 Double action, Breakglass operation Addressable manual station, red housing with white letters and white pull lever 4099 -9003 Double action, Push operation Accessories :Model =.' . , .Description. Reference 2975 -9178 Surface mount steel box, red Refer to page 3 for dimensions 2975 -9022 Cast aluminum surface mount box, red 2099 -9813 Semi -flush trim plate for double gang switch box, red Typically for retrofit, refer to page 4 2099 -9814 Surface trim plate for Wiremold box V5744 -2, red 2099 -9819 Flush mount adapter kit, black Refer to page 4 for details 2099 -9820 Flush mount adapter kit, beige 2099 -9803 Replacement breakglass 2099 -9804 Replacement break -rod 2099 -9828 Institutional cover kit for field installation on 4099 -9001 S . ecificationS Power and Communications MAPNET II or IDNet, 1 address per station, up to 2500 ft (762 m) from fire alarm control panel, up to 10,000 ft (3048 m) total wiring distance (including T -Taps) Address Means Dipswitch, 8 position Wire Connections Screw terminal for in /out wiring, for 18 to 14 AWG wire UL Listed Temperature Range 32° to 120° F (0° to 49° C) intended for indoor operation Humidity Range Up to 93% RH at 100° F (38° F) Housing Color Red with white raised lettering Material Housing and pull lever are Lexan polycarbonate or equal Pull Lever Color White with red raised lettering Housing Dimensions 5" H x 3 -3/4" W x 1" D (127 mm x 95 mm x 25 mm) A.0.6 sab,,le :01F;Iush Mountfrid Single Gang Box Mount 4" Square Box Mount Single gang box, 2 -1/2" deep 4" (102 mm) square box, 2 -1/8" (54 mm) minimum (64 mm), RACO #500 or equal depth, RACO #231 or equal (supplied by others) (supplied by others) Mount flush or with 1to�1 1/16" (2 mm) -1.1 C' maximum extension 4" Square box o DO NOT RECESS (with cover plate II a ►� a I Station FIRE CI ALARM 1 side view Single gang cover plate, 3/4" (19 mm) extension, RACO #773 PULL DOWN or equal (supplied by others) Single gang ■�. box outline Wall surface Semi - Flush Mount Side View f3 Simplex 2 S4099- 0001 -6 10/2003 Addtes060 Manual Statioi. Surface Mountirigr_' 2975 -9178 Box 2975 -9022 Cast Box Preferred Mounting. For 5- 3/16" H x 4" W x 2- 3/16" D 5" H x 3 -7/8" W x 2- 3/16" D surface mounting of these (132 mm x 102 mm x 56 mm) (127 mm x 98 mm x 56 mm) (ordered separately) (ordered separately) addressable manual stations, the preferred electrical boxes are , �!? shown in the illustration to the right. i 0 it Additional Mounting Knockouts located Reference. Refer to page 4 for top and bottom Wiremold box mounting compatibility. FIRE CD ALARM All PULL DOWN o Access for 3/4" threaded 5" conduit located top and bottom (127 mm) ms £1 Simplex 1" (25.4 mm) 3 -3/4" (95 mm) 4099 Series Addressable Manual Station 1 Mitface Mount tidelView. withInte iiri etalh. Appl cation`Reference Refer to NFPA 72, the National Fire Alarm Code, and all applicable local 1 -1/4" codes for complete requirements for (32 mm) Simplex 2975 -9178 box manual stations. The following Field wiring (shown for reference) (shown for reference) summarizes the basic requirements. 1. Stations shall be located in the normal path of exit and distributed ).; in the protected area such that they Address setting under ;°tc are unobstructed and readily resealable label (accessible > I t � 7 r/ ` �vH accessible. with cover open) _► ''`r `P;, 2 -5/8" 2. Mounting shall be with the , 1 eb'` (67 mm) operable part not less than 3 -1/2 ft `' (1.1 m) and not more than 4 -1/2 ft Station cover C ` ' hinges open for (1.37 m) above floor level. _ , installation access 3. At least one station shall be E 41'c'17'1.44' provided on each floor. Additional '' " �.. Switch wiring stations shall be provided to obtain ;'s. ,.. g, (prewired) '?!'' S a travel distance not more than sq x ` / r W » ,ra..:z 200 ft (61 m) to the nearest station fi ,,,v,,,,"‘ ' ` ' from any point in the building. , ,� >� - �,; :" 4. When manual station coverage tg , -. appears limited in any way, . 5 " �;�� additional stations should be '''' A installed. 3 S4099- 0001 -6 10/2003 Add essa14.1: Manual Stat ion Fkiik itional ti tintihMityiormatiOrt / / For retrofit and new installations, additional . o , O Wiremold compatible mounting boxes ®O receptacle box and the required adapter plates 2099 -9814 Surfare trim , model V5744 -2 for / 8 " H x d box ( supplied by are shown in the illustration to 5 -1/8" H x 5"W others) the right. (130 mm x 127 mm) , O O / 'O - O Two gang switch box, each :i:V&V: a:;: 1 3" H x 2" W x 2 -3/4" D Mr &1 (76 mm x 51 mm x 70 mm) .. $ 5 (supplied by others) y J 4099 -9001 IDNet PULL DOWN X n7 addressable station ' „ ®� O® 1 i :; J l' 'm'; -.. O 2099 -9813 Semi-flush trim for 2 gang switch box, 6" H x 4 -1/2" W (152 mm x 114 mm) 3AddressabiIs Manual Stab ii Flush ,Motanti iinformationk Flush mount adapter kit 2099 -9819, Black 2099 -9820, Beige it ass : . .' T,-t5� € �'�'�t„! ' �` s a ;14'::04":"A � Box must be recessed into wall '4;2r41::., a 1" to 1 -1/8" (25.4 mm to 29 mm) . V'2 b4M +, .i .. 'k` '3� . ,+ d :ill b 4 : 4 SY. tm l� TY s„ O zU: - al/' r t;7 s r 4' (203 mm) = V ' -�, ' s",' Hole cutout must be a ' <, , f PULL L DO WN I m of 6 H by 5 W �a O 6 ' "� , (152mmby127mm) I 152 M M ) t'' A.,'`.. r,tV' 4. ;A:147 ilii1t ' : 440 ' inpg 4 - 0:,-4,14,-.: ' Cifr-0,,r; ".,- . ,. ',S it .' el , 11 ' . t.' ,41 5 ,91 0 d":1 * PM '.,',' -1 ::: ? ' 11 .1.* ifici:::,;,,,q e r k 4- 11/16" (119 mm) • 4$ � 7 3 u, .s square box, 2 -1/8" yf �•:� �. � <� �`� a w � , g .:�. (54 mm) minimum ���r, Wall depth (by others) 4 -3/4" (121 mm) - surface 6 -3/4" (171 mm) Front View Side View Tyco. Simpler, the Simplex logo, MAPNET II, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U S. and /or other countries. NFPA 72 and National Fire Alarm Code are registered trademark of the National Fire Protection Association (NFPA) Lexan is a trademark of the General Electric Co. Wiremold is a trademark of the Wiremold Company. Simplex Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4099- 0001 -6 10/2003 a www.fycosafetyproducts usa- Wm.com Gc' 2003 Tvco Safety Products Wesmunster. All tights reserved. All specifications and other information shown were current as ofdoc ,nent revision date and are subject 10 change without notice. Ei ® 1 le T rueAlarm ° Analog Sensing UL, ULC Listed; FM, CSFM, TrueAlarm Analog Sensors — Photoelectric, and MEA (NYC) Approved* Ionization, and Heat; Compatible Bases and Accessories Features: T rue Al arm ® analog sensing provides digital 0 =;g. "'f?" transmission of analog sensor values via MAPNET II or IDNetTM two -wire communications ** Fire alarm control panel provides: • Individual sensitivity selection for each sensor _,13111WIREIME31112EMEMEMIIIMIll • Sensitivity monitoring that satisfies NFPA 72`' lizzazza0;g41'' sensitivity testing requirements • Peak value logging allowing accurate analysis for sensitivity selection 4098 -9714 TrueAlarm Photoelectric Sensor Mounted in Base • Automatic, once per minute individual sensor calibration check that verifies sensor integrity r3 . F Descri • long • Automatic environmental compensation • Display of sensitivity directly in percent per foot Digital Communication of Analog Sensing. TrueAlarm analog sensors provide an analog • Multi stage alarm operation measurement that is digitally communicated to the host • Ability to display and print detailed sensor control panel using Simplex addressable communications. information in plain English language At the control panel, the data is analyzed and an average Photoelectric smoke sensors: value is determined and stored. An alarm or other 0 o abnormal condition is determined by comparing the • Seven levels of sensitivity from 0.2% to 3.7 /o sensor's present value against its average value and time. Heat sensors: Intelligent Data Evaluation. Monitoring each sensor's • Fixed temperature sensing average value provides a continuously shifting reference • Rate -of -rise temperature sensing point. This software filtering process compensates for environmental factors (dust, dirt, etc.) and component • Utility temperature sensing aging, providing an accurate reference for evaluating new Ionization smoke sensors: activity. With this filtering, there is a significant reduction • Three levels of sensitivity; 0.5 %, 0.9% and 1.3% in the probability of false or nuisance alarms caused by For use with Simplex ®: shifts in sensitivity, either up or down. • 4010, 4020, 4100, 4100U, and 4120 Series control Control Panel Selection. Peak activity per sensor is panels stored to assist in evaluating specific locations. The alarm set point for each TrueAlarm sensor is determined at the • Universal Transponders and 2120 TrueAlarm CDTs host control panel, selectable as more or less sensitive as equipped for MAPNET II operation the individual application requires. Magnetic test feature Timed /Multi -Stage Selection. Sensor alarm set points Functional and architecturally styled chamber can be programmed for timed automatic sensitivity enclosure: selection (such as more sensitive at night, less sensitive during day). Control panel programming can also provide • Louvered design enhances smoke capture by directing multi -stage operation per sensor. For example, a 0.2% flow to chamber level may cause a warning to prompt investigation while a • Entrance areas are minimally visible when ceiling 2.5% level may initiate an alarm. mounted Sensor Alarm and Trouble LED Indication. Each Optional accessories include remote LED alarm sensor base's LED pulses to indicate communications indicator and output relays with the panel. If the control panel determines that a UL listed to Standard 268 sensor is in alarm, or that it is dirty or has some other type of trouble, the details are annunciated at the control panel Refer to page 4 for ULC listing status. These products have been approved by the and that sensor base's LED will be turned on steadily. California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California During a system alarm, the control panel will control the Health and Safety Code. See CSFM Listings 7272- 0026:218, 7271- 0026:231, 7270- 0026: 216, and 7300- 0026:217 for allowable values and/or conditions concerning LEDs such that an LED indicating a trouble will return to material presented in this document. It is subject to re- examination, revision, and pulsing to help identify the alarmed sensors. possible cancellation. Accepted for use — City of New York Department of Buildings — MEA35 -930. Additional listings may be applicable, contact your local Simplex product **TrueAlarm analog sensors are protected by one or more of the following U.S. Patents: supplier for the latest status Listings and approvals under Simplex Time Recorder Co. 5,155,468, 5,173,683, 5,400,014; 5,543,777; 5,710,541; D383.407; D388.352; D392,573. are the property of Tyco Safety Products Westminster. MAPNET II and IDNet addressable communications designs are protected by U.S. Patent No. 4,796,025. S4098- 0019 -9 9/2003 TrueAlarm Sensor Bases and Accessories D.es'cn •tion { 'Se ,TM e"l TrueAlarm sensor bases contain integral addressable . . , . aseFeatu electronics that constantly monitor the status of the Base mounted address selection: detachable photoelectric, ionization, or heat sensors. Each • Address remains with its programmed location sensor's output is digitized and transmitted to the system • Accessible from front (dipswitch under sensor) fire alarm control panel every four seconds. Automatic identification provides default sensitivity Since TrueAlarm sensors use the same base, different when substituting sensor types sensor types can be easily interchanged to meet specific Integral red LED for power - on (pulsing), or alarm or location requirements. This feature also allows intentional trouble (steady on) sensor substitution during building construction. When Locking anti tamper design conditions are temporarily dusty, instead of covering the Magnetically operated functional test smoke sensors (causing them to be disabled), heat sensors Mounts on standard outlet box may be installed without reprogramming the control panel. Although the control panel will indicate an SensorlBasessxt incorrect sensor type, the heat sensor will operate at a 4098 - 9792, Standard sensor base default sensitivity providing heat detection for building 4098 - 9789, Sensor base with wired connections for: protection at that location. a 2098 -9808 Remote LED alarm indicator or 1 M0UI1tin •; 4098 -9822 relay (unsupervised) 4098 -9791, Sensor base with supervised relay driver output (not compatible with 2120 CDT): Electrical Box Requirements: (boxes are by others) • Relay operation is programmable and can be manually s i n gle gt gang, 2 " 4" octagonal or 4" square, 1 -1/2" deep; Y p p b Y single gang, 2" deep operated from control panel with relav : 4" octagonal or 4" square, 1 -1/2" deep, • Use with remote mount 2098 -9737 relay with 1 -1/2" extension ring • Also includes wired connections for remote LED 4" (102 mm) Square Box 4" (102 mm) Octagonal Box alarm indicator or 4098 -9822 relay Surface mount reference ,Wal Ba Option 2098-9737, Remote or local mount supervised relay: MIN j_ 0 0 40 • DPDT contacts for resistive /suppressed loads, power i - limited rating of 3 A @ 28 VDC; non -power limited 1 -1/2" (38 mm) rating of 3 A @ 120 VAC (requires external 24 VDC minimum box depth Flush mount reference, mount even with final coil power) surface, or with up to 1/4" (6.4 mm) maximum recess 4098 - 9822, LED Annunciation Relay: ` 2098-9737 Relay (mounts in 4098 -9822 Relay (mounts • Activates when base LED is on steady, indicating base electrical box or remotely) in base electrical box) local alarm or trouble • DPDT contacts for resistive /suppressed loads, power limited rating of 2 A @ 28 VDC; non -power limited O 1 0 at , rating of 1/2 A @ 120 VAC, (requires external tii �� 1V, 24 VDC coil power) f "` ,, 4098 -9832, Adapter plate: Relay Size: 2 -1/2" X 1 -1/2" X 1" (3.75 cubic inches) • Required for surface or semi -flush mounting to (64 mm X 38 mm X 25.4 mm) 4" square electrical box and for surface mounting to NOTE: Review total wire count, wire size, and accessories 4" octagonal box being wired to determine required box volume. • Can be used for cosmetic retrofitting to existing 6 -3/8" diameter base product .. j 1 6 -3/8" (162 mm) -1 • 2098 -9808, Remote red LED Alarm C , ' Indicator: t 4098 -9832 Adapter Plate, reauiredfor 1/4" mounting to surface mounted boxes • Mounts on single gang box ALARM (6.4 mm) and L. aquae.- , c s o (shown in illustration to right) 0 . '. 4 -7/8" (124 mm) _____,..1 15/16" tttt ) £35vnplex (24 mm) \ 0 B TrueAlarm Bases 4098 -9789, -9791, & -9792 2 S4098- 0019 -9 9/2003 TrueAlarm Sensors *4098 9714aPhotoelectric S ensor Featires TrueAlarm photoelectric sensors use a stable, pulsed Sealed against rear air flow entry infrared LED light source and a silicon photodiode Interchangeable mounting receiver to provide consistent and accurate low power smoke sensing. Seven levels of sensitivity are available EMI /RFI shielded electronics for each individual sensor, ranging from 0.2% to 3.7% per Heat sensors: foot of smoke obscuration. Sensitivity is selected and • Selectable rate compensated, fixed temperature monitored at the fire alarm control panel. sensing with or without rate -of -rise operation The sensor head design provides 360° smoke entry for • Spacing distance between heat sensors: optimum response to smoke from any direction. A built -in screen keeps insects from entering the smoke chamber. Fixed Temp. UL Spacing FM Spacing, Either Fixed Due to its photoelectric operation, air velocity is not Setting Temperature Setting normally a factor, except for impact on area smoke flow. 135° F (57.2° C) 60 ft (18.3 m) 15 ft x 15 ft (4.6 m) fixed temperature only; I 30 ft x 30 ft (9.2 m) fixed I 4 -7/8" (124 mm) ►I 155° F (68° C) 40 ft (12.2 m) temperature with rate -of -rise Smoke Sensors: -LED status indicator • Photoelectric or ionization technology g (541mm sensin mm) • 360 0 smoke entry for optimum response I mmilm 1 ■miIIIO _� -_ Vann i ��m® 4098; =9733 HeafSensoi TrueAlarm heat sensors are self - restoring and provide rate 4098 - 9714 Photoelectric Sensor with Base compensated, fixed temperature sensing, selectable with ,.r -. or without rate -of -rise temperature sensing. Due to its 4098 9717 lonization $ ensor' small thermal mass, the sensor accurately and quickly TrueAlarm Ionization sensors use a single radioactive measures the local temperature for analysis at the fire source with an outer sampling ionization chamber and an alarm control panel. inner.reference ionization chamber to provide stable Rate -of -rise temperature detection is selectable at the operation under fluctuations in environmental conditions control panel for either 15° F (8.3° C) or 20° F (11.1° C) such as temperature and humidity. Smoke and invisible per minute. Fixed temperature sensing is independent of combustion gases can freely penetrate the outer chamber. - rate -of -rise sensing and programmable to operate at With both chambers ionized by a small radioactive source 135° F (57.2° C) or 155° F (68° C). In a slow developing [Am 241 (Americium)], a very small current flows in the fire, the temperature may not increase rapidly enough to circuit. The presence of particles of combustion will cause operate the rate -of -rise feature. However, an alarm will be a change in the voltage ratio between chambers. This initiated when the temperature reaches its rated fixed difference is measured by the electronics in the sensor temperature setting. base and digitally transmitted back to the control panel for processing. TrueAlarm heat sensors can be programmed as a utility device to monitor for temperature extremes in the range Three levels of sensitivity are available for each from 32° F to 155° F (0° C to 68° C). This feature can ionization sensor: 0.5, 0.9, and 1.3% per foot of smoke provide freeze warnings or alert to 1-IVAC system obscuration. problems. (Refer to specific panels for availability.) I` 4 r 4 - 7/8" (124 mm) -1 • f 4 -7/8 "(124 mm) r] D'" status indicator 2 -1/8 II`�LED status indicator (54 mm) 1 ICI IHI I 2 -3/8" �� (60 mm) � 'I 11" "I, 4098 -9717 Ionization Sensor with Base A PEIdat on,Refergnce 4098 Heat Sensor with Base Sensor locations should be determined only after careful consideration of the physical layout and contents of the WARNING: In most fires, hazardous levels of smoke area to be protected. Refer to NFPA 72, the National Fire and toxic gas can build up before a heat detection Alarm Code ® . On smooth ceilings, smoke sensor spacing device would initiate an alarm. In cases where Life of 30 ft (9.1 m) may be used as a guide. For detailed Safety is a factor, the use of smoke detection is highly application information, refer to 4098 Detectors. Sensors, recommended. and Bases Application Manual (574 -709). 3 S4098- 0019 -9 9/2003 gTriueAl40 dAn40 Sensing, Pro61004. lecf on TrueAlarm Sensor Bases* Model •Description •- Compatibility Mounting "Requirements' 4" octagonal or 4" square box, 1 -1/2" min. ---- -r 4098 -9792 (C) Standard Sensor Base, no options Sensors 4098 -9714, -9733, & -9717 depth; or single gang box, 2" min. depth Sensor Base with connections for Sensors 4098 -9714, -9733, & -9717 4098 -9789 (C) Remote LED Alarm Indicator or 2098 -9808 remote LED alarm 4" octagonal or 4" square box Unsupervised Relay indicator or 4098 -9822 relay Sensor Base with connections for Sensors 4098 -9714, -9733, & -9717 Note: Box depth requirements depend Supervised connections Remofor te Relay and 2098 -9737 remote relay (supervised) 4098 -9791 (C) on total wire count and wire size, refer to accessories list below for reference. Remote Alarm 2098 -9808 remote alarm indicator or Indicator or Unsupervised Relay 4098 -9822 relay (unsupervised) TrueAlarm Sensors Model. 'Description ' Compatibility . Mounting.Requirements s. 4098 -9714 (C) Photoelectric Smoke Sensor Bases 4098 -9792, 4098 -9789, Refer to base requirements 4098 -9717 (C) Ionization Smoke Sensor and 4098 -9791 4098 -9733 (C) Heat Sensor TrueAlarm Sensor/Base Accessories Model Description Compatibility Mounting Requirements Remote Mounting requires 4" octagonal or Supervised Relay, mounts remote For use with 4098 -9791 base 4" square box, 1 -1/2" minimum depth 2098 -9737 or in base electrical box Base Mounting requires 4" octagonal box, 2 -1/8" deep with 1 -1/2" extension ring 2098 -9808 Remote Red LED Alarm Indicator Single gang box, 1 -1/2" minimum depth on single gang stainless steel plate Relay, tracks base LED status Bases 4098 -9789 and 4098 -9791 4" octagonal box, 2 -1/8" deep with 1-1/2" 4098 -9822 (C) (unsupervised, mounts only in base extension ring electrical box) Required for surface or semi -flush 4098 -9832 Adapter Plate Bases 4098 -9792, -9789, & -9791 mounted 4" square box and for surface mounted 4" octagonal box * Refer to data sheet S4098 -0028 for Sounder Base information. Refer to Installation Instructions 574 -707 and Application Manual 574 -709 for additional information. ULC listed model numbers are designated by (C) and require a "C" suffix such as 4098- 9792C. y .w;'. `Y' - ' •ice' ,S •ecifil Genera! Operating Specifications; �, ' Communications and Sensor Supervisory Power MAPNET II or IDNet, auto - select, 24-40 VDC w /data, 400 µA typical, 1 address per base Communications Connections Screw terminals for in /out wiring, 18 to 14 AWG (0.82 mm to 2.08 mm Remote LED Alarm Indicator Current 1 mA typical, no impact to alarm current Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG (0.82 mm ) UL Listed Temperature Range 32° to 100° F (0° to 38° C) Operating with 4098 -9717 or 4098 -9733 32° to 122° F (0° to 50° C) Temperature Range with 4098 -9714 15° to 122° F ( -9° to 50° C) Humidity Range 10 to 95% RH Smoke Sensor 4098 -9714, Photoelectric Sensor Air velocity = 0 -2000 fUmin (0 -610 m /min) Ambient Ratings 4098 -9717, Ionization Sensor Air velocity = 0 -400 ft/min (0 -122 m /min); Altitude is up to 8000 ft (2.4 km) Housing Color Frost White 4098 -9791 B Wit p h'Sueiv'ised, Remote; R 2098- 9737 for contact ratings} - Externally Supplied Relay Coil Voltage 18 -32 VDC (nominal 24 VDC) Supervisory Current 270 p.A, from 24 VDC supply Alarm Current with 2098 -9737 Relay 28 mA, from 24 VDC supply 4098 -9822 Unsupervi .Relay: Requirements -for Bases4098 - 9789 and 4098-6791 page 2 - for ; contact rating Externally Supplied Relay Coil Voltage 18 -32 VDC (nominal 24 VDC) Supervisory Current Supplied from communications Alarm Current 13 mA from separate 24 VDC supply Tyro. Simplex, the Simplex logo, TrueAlarm. MAPNET II, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S and /or other countries. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA). Si l Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • LISA S4098- 0019 -9 9/2003 www. tycosafetyproducts- usa -wm. com 2J' 2003 Tyco Safety Products Westminster All rights reserved All specifications and other information shown were cznrent as of document revision date and are subject to change without notice Simplex Trued /arm Analog Sensing UL, ULC Listed; FM, CSFM, Addressable Duct Sensor Housings with TrueAlarm and MEA (NYC) Approved* Photoelectric Sensor; Available with Multiple Relay Control Features;! TUMID Compact air duct sensor housing with clear cover to monitor for the presence of smoke" o Includes factory installed TrueAlarm r ® egoonba �� photoelectric smoke sensor and features: C .� f � ® moow5 • a • • Individual sensor information processed by the host ono e control panel to determine sensor status R : • Digital transmission of analog sensor values via MAPNET II or IDNetTM, 2 -wire conmiunications • Programmable sensitivity, consistent accuracy, environmental compensation, status testing, and monitoring of sensor dirt accumulation Duct Sensor Housing, Front View Model 4098 -9755: • Basic duct sensor housing (no relay output) powered m e by MAPNET II/IDNet communications Model 4098 -9756: o LEST • Duct sensor housing with supervised output for NOM -r) multiple remote relays; requires separate 24 VDC; „ s,,,, ,r includes one relay • Relay output is under panel control " • At the panel, relay output can be activated manually or 2098 -9808 2098 -9806 in response to a separate alarm or other input Remote Status /Alarm Indicator and Test Station General features: • UL listed to Standard 268A Ih frOdUCf10�17.:; • Clear cover allows visual inspection Operation. Simplex compact air duct smoke sensor • Test ports provide functional smoke testing access housings provide TrueAlarm operation for the detection of with cover in place smoke in air conditioning or ventilating ducts. Sampling • Mounts to rectangular ducts or round ducts; minimum tubes are installed into the duct allowing air to be directed to size is 8" (203 mm) square or 18" (457 mm) diameter the smoke sensor mounted in the housing. Magnetic test feature for alarm initiation at housing • g g TrueAlarm`,Sensor�Operatioir: • Optional weatherproof enclosure is available Digital Communication of Analog Sensing. separately (refer to data sheet S4098 -0032) Analog information from the sensor is digitally Diagnostic LEDs (on interface board): communicated to the control panel where it is analyzed. • Red Alarm/Trouble LED for sensor status and Sensor input is stored and tracked as an average value communications polling display with an alarm or abnormal condition being determined by • Yellow LED for open or shorted trouble indication of comparing the sensor's present value against its average. supervised relay control (4098-9756 only) Intelligent Data Evaluation. Monitoring each Sampling tubes (ordered separately): photoelectric sensor's average value provides a software • Available in multiple lengths to match duct size filtering process that compensates for environmental • Installed and serviced with housing in place factors (dust, dirt, etc.) and component aging, providing Remote module options (ordered separately): an accurate reference for evaluating new activity. The • Remote red Stahl /alarm LED (2098-9808) result is a significant reduction in the probability of false or nuisance alarms caused by shifts in sensitivity, either • Remote test station with LED (2098 -9806) up or down. • PAM -SD remote relays (refer to page 2 for details) ** Please note that smoke detection in air ducts is intended to provide • These products have been approved by the California State Fire Marshal (CSFM) pursuant to notification of the presence of smoke in the duct. It is not intended Section 13144.1 of the California Health and Safety Code. See CSFM Listing 3240 - 0026.241 for allowable values and /or conditions concerning material presented in this document. It is to, and will not, replace smoke detection requirements for open subject to re- examination, revision, and possible cancellation. ULC listed models are areas or other non -duct applications. designated with a "C" suffix such as 4098- 9755C. Accepted for use - City of New York Department of Buildings - MEA35 -93E. Additional listings may be applicable; contact your t TrueAlarm sensors and MAPNET II and IDNet communications are protected by one or local Simplex product supplier for the latest status. Listings and approvals under Simplex Time more of the following U.S Patents: 5,155,468; 5,173,683; 5,543,777; 5,400,014; Recorder Co are the property of Tyco Safety Products Westminster. 5,543,777; 5,710,541; D383,407; D388,352; D392,573; 4,796,025. S4098- 0030 -4 10/2003 TrueAlarm 'aSensor.Operation =(Conf�nuedj. Phootoelectnc Sensingx(Continued) Control Panel Selection. Peak activity per sensor is Typically duct sensor applications require less sensitive stored to assist in evaluating specific locations. The alarm settings (such as 2.5% per foot obscuration) due to the set point for each sensor is determined at the control ducts being a relative dirty environment. However, the panel, selectable as the individual application requires. standard seven levels of TrueAlarm sensor sensitivity are Sensor Status LED. Each sensor housin s red status available for each individual sensor, ranging from 0.2% to LED (located on the electrical interface board) pulses to 3.7% Per foot of smoke obscuration. Sensitivity is selected and monitored at the indicate communications with the panel. If the control fire alarm control panel. panel determines that a sensor is in alarm, or that it is Flre.:Alarm!COntrolbPanel Features;_ dirty or has some other type of trouble, the details are annunciated at the control panel and that sensor housing's • Individual smoke sensitivity selection status LED will be turned on steadily. During a system • Sensitivity monitoring that satisfies NFPA 72 alarm, the control panel will control the LEDs such that sensitivity testing requirements an LED indicating a trouble will return to pulsing to help • Peak value logging allows accurate analysis for identify any alarmed sensors. (Remote Status /Alarm sensitivity selection LEDs track the operation of the sensor housing LED.) • Automatic, once per minute individual sensor PhotoelectricSensm • calibration check verifies sensor integrity TrueAlarm photoelectric sensors use a stable, pulsed • Automatic environmental compensation infrared LED light source and a silicon photodiode • Smoke sensitivity is displayed in percent per foot receiver to provide consistent and accurate low power • Ability to display and print detailed sensor smoke sensing. information in plain English language • Relays of model 4098 -9756 are under panel control :.� for ON OFF, or override YDuct =;Sensor SelectipnChart Duct Smoke Sensor Housing with Photoelectric Sensor* Model .Description Compatibility Basic Duct Sensor Housing; operating power is supplied by Simplex fire alarm control panel models 4010, 4098-9755 4020, 4100, 41000, and 4120. Also 2120 CDT if either MAPNET II or IDNet communications (no relay output) configured for MAPNET II, TrueAlarm operation Duct Sensor Housing with supervised multiple relay output, Same e 2 relay operation is not 4098 -9756 requires separate 24 VDC fire alarm power and relay compatti ble w with ith 21120pt 20 CDT; end -of -line resistor; includes one PAM -SD relay Relay output is for up to 15 total PAM SD Relays (additional relays are ordered separately) Remote LED Indicator and Test Station, Select One if Required Model Description. Compatibility Mounting- • 2098 -9808 Red LED status indicator Use single gang box, 4098 -9755 "Wx2 "D H " 2 2098 9806 Test Station with keyswitch and red LED status indicator 4098 -9756 (76 3 3" x 51 2 mm x 51 mm) (turning switch to "TEST" initiates alarm for system testing) Epoxy Encapsulated Remote Relay (wiring is 18 AWG (0.82 mm color coded wire leads) Model -. - - ;=" . Description s , ., , Conipatibility. . "Mounting Relay; single Form C (10 A @ 120 VAC); refer to pages 3 and 4098-97M only; Locate relays within 3 ft PAM -SD 4 for additional relay information; order separately from Air connect up to 15 (1 m) of device being Products & Controls Ltd.; one included with 4098 -9756 controlled, per NFPA 72 * Each duct housing includes an internally mounted model 4098 -9714 TrueAlarm photoelectric sensor and an exhaust tube. A correctly sized sampling tube (ordered per application) is required, refer to chart below . cs f ( t : r .� e t ?, - - acs• -. - . Sampling Tube Selection Chart,,Ord'ered $eparately er Duct Width, Select One; Overall. Duct Width n , :: ; - ;Tube'Required' . Suggested Cut Length' 12" (305 mm) 2098 -9796 1/2 in. (12.7 mm) longer than duct width 13" to 23" (330 mm to 584 mm) 2098 -9804 1/2 in. (12.7 mm) longer than duct width 24" to 46" (610 mm to 1168 mm) 2098 -9797 2 in. (51 mm) longer than duct width 46" to 71" (1168 mm to 1803 mm) 2098 -9798 2 in. (51 mm) longer than duct width 71" to 95" (1803 mm to 2413 mm) 2098 -9799 2 in. (51 mm) longer than duct width 2 S4098- 0030 -4 10/2003 DuctiSensgr ;Detail aReference; NOTE: Refer to Installation Instructions 574 -776 for additional detail and maintenance information. 11 -318" (289 mm) _� ►{ Exhaust tube access hole ..1-{Conduit (by others)) A 4 0 9 8 - 9 7 1 4 in special interface base (supplied) q� t Metal plate with dual holes ; - t'° r r O — for 3/4" (19 mm) conduit, plug ',:,;' ' � supplied for unused hole •,: :, ', . O OOOOfl00 O , s -3 /a° ; r con ,6 "Font VIe11U g (171 mm) : tt; f a� ' D B 00[311 00, t Yellow LED, relay control trouble Sampling tube :� - �� x� , indicator (4098 -9756 only) ti p\ � - z 0 0 a� access hole 0 .l?1 • . • . k 0 ' ft Red sensor . - ' � � � � r ' � 0 , 0 status LED (Side of duct • ' " -�: \ ,,_,.,p,,.11,,,,;,:s,,,,_ ,_..,,.... _. N a.. v e ,. w..qa , rna, ...(n- Wiring i Y v ng terminals (Captive fastening screws (4 Ma netic test area :•Stationary baffle (built -in P 9 , - - - - -- , 4 - - Mount as shown (preferred) or Transparent cover Gasketed sensor area) with electronics area located to the LEFT or UP ONLY . 1 . _ 3 -318" 0 r I 'k, (86 mm) t� Bottom view Ot�O Tk- 4 +. j tt f { t'� , r - trsa t xK .. S0d ? t •ir 7.. Y S :; i`z • V;7.."-'!''':`;'''''''''''',.".: + r �- } fi h s^ - rya` t `, Jk • b> s u e. i ...i , 1 * / r +� ^ ' I 13/16" S ;r ' °'l` l i Gaskets (supplied) (21 mm) Duct wall it Exhaust tube (supplied)) Test ports (2) provided Sampling tube, ordered for measuring airflow separately per duct width and for aerosol injection End View with Duct and Tubes • Duct housing 18" Round duct outline PAM -SD Remote Relay (minimum diameter) (10 A @ 120 VAC, for use with 4098 -9756 only) • NOTE: Mount in separate electrical box within I— I 3 ft (1 m) of device being controlled per r NFPA 72 • ri r I I 8' S uare duct outline 1 ' °` x • E (Exhaust tube I _ I q J 111 (minimum width) r 13/16" s'' I t I (21 mm) J f 1 -1/2" Sampling tube, keyed for proper hole alignment (38 mm) f-- ► -1- 3/16" (30 mm) with holes facing into airflow (template is provided for proper tube installation) 3 S4098- 0030 -4 10/2003 Duct'sS tigi Locafion`Re erence Preferred Duct Sensor Locations: 1. A minimum of six duct widths downstream from Exhaust Sensor bends or inlets to avoid air turbulence. ,/Damper OK 1, 2. On the downstream side of filters to detect fires in the Exhaust dik ._Return filters. Air 3. In return ducts, ahead of mixing areas. • Do not locate 4. Upstream of air humidifier and cooling coil. sensor here 5. With accessibility for test and service. Return air „ damper 6. For additional information, refer to NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems. Fresh Supply air ,� ~ Air Locations to Avoid: � Do /' 1. Where dampers closed for comfort control would Filter Sensor Do not locate 411 sensor here bank OK interfere with airflow. 2. Next to outside air inlets (unless the intent is to Bend or other (L monitor smoke entry from that area). obstruction 3 . In return air damper branch ducts and mixing areas Return air where airflow may be restricted. 6 Duct a pr inlet � 6 Duct ® widths /1 ._ widths � i' minimum -° i l minimum Outdoor Applications Note: For outdoor applications, refer to data sheet S4098 -0032 for information on weatherproof enclosure 4098 -9845. S • eclfication General - . ... Air Velocity Range (liner ft/min) 300 to 4000 ftlmin (91 to 1220 m /min) Sensor Sensitivity Range 0.2% to 3.7% per foot of obscuration, selectable at host control panel UL Listed Temperature Range 32° F to 100° F (0° C to 38° C) Operating Temperature Range 32° F to 122° F (0° C to 50° C) Storage Temperature Range 0° F to 140° F ( -18° C to 60° C) IP Humidity Range 10% to 95% RH, non - condensing Wiring Connections Terminal blocks, 18 to 12 AWG (0.82 mm to 3.31 mm ) Housing Color Black base with clear cover Remote Status /Alarm LED and Test Station. with" Remote` Status /Alarm;LED ; :- ; -; 1 -,< , , : ,:- , Remote Alarm LED Current 1.2 mA, no impact to alarm current (2098 -9808 or 2098 -9806) Test Station Keyswitch Current 3.3 mA, no impact to alarm current (2098 -9806) Remote Alarm LED and Test Station Distance 250 ft (76 m) maximum Addressable Operation - Data Communications MAPNET II or IDNet communications, auto - select, one address per housing; provides operating power to model 4098 -9755 Model 4098 -9756 w 'M ith Supervisedultiple .Relay Coritrol,_Requires SeparateFused 24VDC.from.Fire Alarm Power Supply Input Voltage 18 -32 VDC (24 VDC nominal) Standby Current 2.4 mA @ 24 VDC Alarm Current 15 mA @ 24 VDC; add 15 mA additional for each remote PAM -SD relay Supervised Remote Relay Control Output For use with PAM -SD relay only, quantity of 15 maximum; distance of 500 ft (152 m) maximum; requires 10 kf2,,1/2 W end -of -line resistor a PAM -SD Rel Output Ratings, 'Sin le Form C, use.wiith�Model 4098- 9756 =Onl . - Y p 9 ,9 Y: ° ' .se ,;: ; Coil Current 15 mA @ 24 VDC, up to 15 maximum per relay control output Relay Contacts, Resistive Ratings 7 A @ 28 VDC; 10 A @ 120 VAC; 250 ).lA @ 5 VDC Location Distance 500 ft (152 m) maximum to relay coils; relays must be within 3 ft (1 m) of device being controlled per NFPA 72 Tiro. Simplex, the Simplex logo, TrueAlarnr, MAPNET 11, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S and /or other countries NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA). Simplex Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA tv S4098- 0030 -4 10/2003 www.tycosafetyproducts-usa-wm.com corn ©2003 2003 Tyco Safety Products Westminster All rights reserved All specifications and other information shown were airrent as ofdocument revision date and are suhlect to change without notice. Simplex Multi- Application Peripherals UL, ULC Listed; FM, CSFM, MAPNET II and IDNetTM Communicating Devices, and MEA (NYC) Approved* Individual Addressable Modules (IAMs) Features; MAPNET II or IDNet addressable communications supply both data and power over a single wire pair SINPI[I LINE RE[pRI/i/S to provide * *: : x 409 900I(Th -b. • Supervised Class B monitoring of normally open, dry 1RS1, uslR 511-31 g contacts • Total wiring distance from IAM to supervision resistor(s) of up to 500 ft (152 m) i 00o000Ba , ,/ • Monitored connection is compatible with Simplex' dr 2081 -9044 Overvoltage Protectors for outdoor wiring or electrically noisy applications > 4090 -9001 Supervised IAM For use with following Simplex control panels: (shown approximately 3/4 size) • Model Series 4010/4100/4100U/4120/4020 fire alarm control panels equipped with either IDNet or MAPNET Il communications • Model Series 2120 communicating device transponders (CDTs) equipped with MAPNET II communications Model 4090 -9001: • Enclosed design minimizes dust infiltration ' • Mounts in standard single gang electrical box • Screw terminals for wiring connections S�GNq�, �5�1/E NO '" • Visible LED flashes to indicate communications • Optional covers are available to allow LED to be viewed after installation (requires mounting bracket, 4090 -9051 Supervised IAM ordered separately) (shown approximately 3/4 size) Model 4090 -9051: • Encapsulated design for extended exposure to high humidity (LED is not present on this model) �t1;011' • • Color coded 18 AWG leads for wiring Individual addressable modules (IAMs) receive IDNet communications provides current limited both power and communications from a two -wire monitoring: MAPNET II or IDNet circuit. They provide location • Provides monitoring of tamper switch (supervisory) and specific addressability to a single initiating device (such waterflow switch (alarm) on same circuit using one point as single station smoke detector alarm contacts or heat detector contacts) or multiple devices at the same location • Available with IDNet communications only by monitoring normally open dry contacts and the wiring Multiple operation modes are available and are to an end -of -line resistor. selectable at the control panel: Model 4090 -9001 is packaged in a thermoplastic • Contact closure status can be tracked housing and provides screw terminal connections and a • Momentary contact closure conditions can be selected at status indicating LED. the panel to be latched or tracked (not available with the Model 4090 -9051 is an encapsulated package with wire 2120 CDT) leads. It does not provide a status indicating LED. UL listed to Standard 864 • These products have been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300 - 0026:223 for allowable values and /or conditions concerning material presented in this document. It is subject to re- examination, revision, and possible cancellation. Accepted for .. MAPNET II and IDNet addressable communications designs are protected by U.S. use — City of New York Department of Buildings — MEA35 -93E. Additional listings may be Patent No 4,796 025 applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. S4090- 0001 -7 3/2004 'V T GY 1 4 O ecation;:` Cur e.r.WI imited;OperationtAPOptions` Contact Closure. Closure of the monitored contact(s) For use with IDNet communications only, these initiates an alarm or other response as programmed at the IAMs can sense normal, open circuit, short circuit, and fire alarm control panel. An open in the monitored circuit current limited conditions. With the proper end -of -line wiring will cause a trouble to be reported. and current limiting resistors, dual functions such as tamper switch and waterflow switch monitoring can be Panel Selections. Selections can be made at the control determined and communicated by a single addressable panel to maintain the alarm condition if the initiating point. device contacts are momentary, such as from a rate -of -rise heat detector, or to track the device contact status (not available with the 2120 CDT). 'IAMProduct Seiecti n Model Number ` °Description > 4090 -9001 Supervised IAM, mounted in thermoplastic housing with screw terminals; see applicable options below 4090 -9051 Supervised IAM, encapsulated with wire leads Optional Trim Plates and Mounting Bracket for Model 4090 - 9001 Model Number Description 4090 -9806 Trim plate with LED viewing window, requires For semi -flush mounted box 4090 -9810 mounting bracket, includes mounting 4090 -9807 screws; galvanized steel For surface mounted box 4090-9810 Mounting bracket, mounts IAM to electrical box and provides screw holes for trim plate, required for optional trim plates �S ecifications'<: Electrical • Power and Communications MAPNET II or IDNet, auto selected, 1 address per IAM Input Requirements Normally open, dry contacts 4090-9001 Screw terminals for in /out wiring, 18 to 14 AWG wire Wire Connections (0.82 mm to 2.08 mm 4090 -9051 Color coded wire leads, 18 AWG (0.82 mm 8" long (203 mm) Supervision Resistor 6.8 kf2, 1/2 W NOTE: Refer to installation instructions 574 -331 (- 9001), 574 -572 ( -9051) and Resistors for Current Limited Operation field wiring diagrams 841 -804 and 1.8kQ and 4.7kf2,1 /2W (for use with IDNet communications only) 842 -073 for additional information. Wiring Distances 500 ft (152 m) maximum without protectors Distance from IAM to Contacts 400 ft (122 m) maximum with 2081 -9044 Overvoltage Protectors Wiring Distance Reference per channel, 2500 ft (762 m) maximum from fire alarm control panel MAPNET II or IDNet Communications 10,000 ft (3048 m) maximum total wiring distance (including T -Taps) Mechanical 4090 -9001 1- 9/16" W x 1 -3/4" H x 1 -1/4" D (40 mm x 44 mm x 32 mm) Dimensions 4090 -9051 1- 9/16" W x 1- 9/16" H x 9/16" D (40 mm x 40 mm x 14 mm) Housing Material, 4090 -9001 Black thermoplastic Encapsulation Material, 4090 -9051 Epoxy, beige Temperature Range 32° to 120° F (0° to 49° C) intended for indoor operation Humidity Range Up to 93% RH at 100° F (38° C) 2 S4090- 0001 -7 3/2004 =Mo ntin.::Information; O — � 1 4090 -9001 IDNet !"..:,..0. �. _' % Field wiring shown supervised IAM for reference li 7 *i 1 COOL 10%/1 LED viewing port I Ooi`l000 .1: Single gang electrical �• � o box 2 -1/2" (64mm) minimum depth (supplied by others) Address setting under resealable label Single gang blank cover plate and mounting screws, for use when • LED is not required to be externally viewed (supplied by others) Mounting Reference, Single Gang Blank Cover Plate I 1 i ,---/— O © Light pipe for LED viewing 4 -1/4" ® } 4 -1/2" (108 mm) j (114 mm s „, _.. 1 1 HECK © © ° O • 2 -1/2" 2- 13/16" r © (64 mm) - ® (72 mm) 4090 -9806, Trim plate for 4090 -9807, Trim plate for 4090-9810 Mounting semi -flush mounted box surface mounted box bracket, ordered separately NOTE: These mounting plates require mounting bracket 4090 -9810. Optional Trim Plates and Mounting Bracket for Visible LED 3 S4090- 0001 -7 3/2004 0.9040.144,01, in o ;Information,;, Address setting is O �• at rear of housing = �:�', _' _ _ 4090 -9051 I Encapsulated �I 0 Supervised IAM �'_ � j A ' L I .."!......-.2.1. . 2ti C O Single gang electrical box 2 -1 /2" (64mm) minimum depth (supplied by others) _'` Single gang blank cover plate and mounting screws (supplied by others) Tyro, Simplex, the Simplex logo, MAPNET II. and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S and/or other countries. SI ' Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4090- 0001 -7 3/2004 ® www. tycosafetyproducts- usa -wm. com 2004 Tyco Safety Products Westmmmster. All nghts reserved All specifications and other information shown were cun'ent as ofdocument revision date and are suhject to change without notice � SIMPleX Multi- Application Peripherals UL, ULC Listed; FM, CSFM, IDNetTM Communicating Devices and MEA (NYC) Approved* Model 4090 -9002 Relay IAM Features:' • IDNet addressable interface modules** for use n Y with Simplex models 4010 and 4100U fire alarm , ^ , y control panels - � e � `r � , l: ; 4090 -9002, Individual Addressable Relay Module (Relay IAM): ' I • A single addressable point provides control and C ® ® ? -•OW status tracking of a Form "C" contact • Low power latching relay design allows 1DNet communications to supply both data and module power U © Compact, sealed construction: • Enclosed design minimizes dust infiltration 4090 Series IDNet Relay IAM Package (shown approximately 1/2 size) • Mounts in standard 4" square electrical box • Screw terminals for wiring connections • Visible LED flashes to indicate communications S a ecifications;Y • Optional covers are available to allow LED to be (Refer to Installation Instructions 574 -184 for additional viewed after installation information.) UL listed to Standard 864 Communications 4010 or 4100U IDNet, 1 address per device sc Relay IAM Power Supplied by IDNet communications Descri •tionr Y PP Y IDNet Relay IAMB allow fire alarm control panels to Type Form C, SPDT control a remotely located Form "C" contact using IDNet 2 A @ 24 VDC, for transient addressable communications for both data and module Contact Power - Limited suppressed loads power. Typical applications would be for switching local Ratings 1 A @ 24 VDC for inductive loads power for control functions such as elevator capture, or 1/2 A @ 120 VAC, for transient control of FIVAC components, pressurization fans, Nonpower- Limited suppressed loads dampers, etc. Relay status is also communicated requiring only one device address. Wire Connections Screw terminals for in /out wiring, 18 to 14 AWG wire (0.82 to 2.08 mm Product Selection; Up to 2500 ft ( 762 m) from fire alarm Model 'Description', r ` ',; "- control panel 4090 -9002 Relay IAM IDNet Wiring Reference Up to 10,000 ft ( 3048 m) total wiring distance (including T -Taps) Optional Trim Plates Compatible with Simplex 2081 - 9044 Model Description,?_,. Overvoltage Protectors 4090 -9801 Trim plate with LED For semi -flush 4 -1/8" H x 4 -1/8" W x 1 -3/8" D viewing window, includes mounted box Dimensions (105 mm x 105 mm x 35 mm) mounting screws; For surface 4090 -9802 galvanized steel mounted box Housing Material Black thermoplastic Mounting Plate Material Sheet metal, galvanized Temperature Range 32° to 120° F (0° to 49° C), * This product has been approved by the California State Fire Marshal (CSFM) pursuant to intended for indoor operation Section 13144.1 of the California Health and Safety Code. See CSFM Listing Humidity Range Up to 93% RH at 100° F (38° C) 7300 - 0026:223 for allowable values and/or conditions concerning material presented in this document. It is subject to re- examination, revision, and possible cancellation. Accepted for use — City of New York Department of Buildings — MEA35 -93E. Additional listings may be °° IDNet addressable communications are protected by U.S. Patent No. 4,796,025. applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. S4090- 0002 -6 2/2004 . 11 7 0 1 0 0 0 Address . setting resealable label , -'- III 0 -~. ~~ `n , -,,%)*LiN CD 0 � gm ' ^' 4^(1nzmm) sq"am�*.z'1ar ' r� ' � (sw mm) mm/mumuopm.RAcO , K�` \ zo2or equal �u»puou»ymm ~' ~ ~. ' ~ ~ .~ 400n'snou Relay /Am ; - ooumoo vnomaoxnove,p/otoonumovnunonn,owo.mr uoewx*nLsoiv"ut,onu/,^u 11 <nunpoouuvnmnm> K8ountingRefnvence.Double Gang Blank CoverP|atm ^ © © pouxLED w*�^o | *-�e^ (4-5/16" �ac��� (109 mm) 's�E '-':',1t;^ ' ( l 0 0 , ' —_-�' 6^(116 mm)------44.- �w �a1er(1mymm) w' / / 4090-9801, Trim plate for 4090-9802, Trim plate for semi-flush mounted box surface mounted box Optional Trim Plates for Visible LED Tyco, Simpler, the Simplex logo, and m*' are trademarks o/ Tyco International ^cor its affiliates '" the U.S andlo, other countries. A����������0���� Tyco oo��pm�mmwwoun/cmmr'wexm,maro�ww'o14w1'nnu/'USA a40e0'0002'6 2/2004 ~~ www.tycosafetyproducts m 2004 Tvco Safer' Products Westminster. All rights ""en`a All specifications and other information date and are subject ° change without notice. Simplex Multi-Application Peripherals and Accessories Fire Alarm Control Relays, UL Listed* Track Mounted and Encapsulated, (Air Products) 4098 -9843 and 2088 Series FEATURES sWaxv +" i`a�•s w«�� rcea �sv<w ,12.4 3;;s M,S ;;'.�'.« " «�,c" i. -o- rzr^, ��." ;:� - ,- �;tay^ ��.«,t"-"�,>`,. • UL listed as Control Unit Accessory (UOXX) °max' ^ "� • R • Track mount package availability: o 6o.o 63z� ©' ©3�d o.o oxo o`o e:o a p o �; FIMV'M — Single or four relay module, with or without 1 ° o O ,No enclosure, with SPDT or DPDT contacts 9 ; 6 ° ®z� Q= a: -� o „ f. 6 7. 1Ef4 .13, R 4,4 Fy te r, — LED indicates relay coil status � 6:15!) or © ©io r , o © 6 ©4j o — Enclosures provide status LED viewing ports x„ 4 "\ ,,�; — 1..f£' ' .: t.: ;.,pa i' •t »�'. N ^t :;:.... E Multiple coil voltage inputs, diode polarized � � • °`����- _�••n�� ° ='��� b•,x„=�,F =W`�� =,.; — Modules are track mounted with "Snap- Apart" feature design 2088 -9020, MR204 /C, Four DPDT Relay Package with Enclosure (shown with cover removed) • Single encapsulated SPDT relay package with color coded 18 AWG wire leads, available in two versions: — 2088 -9021 (PAM -1) Provides diode polarized multiple input voltage ability and LED indication — 4098 -9843 (PAM -SD) Provides a diode polarized 24 VDC coil with in /out wiring '11.) 1 SPECIFICATIONS (refer to page 2 for dimensions) Ava ., w so 3 f Track Mount Relays HT FLU oc RED Contact Ratings 10 A @ 115 VAC, resistive Coil Voltage 18 -35 VACNDC, 115, or 230 VAC Encapsulated Relay Package Coil Current • SPDT models = 15 mA (typical of 2088 -9021, PAM -1 and 4098 -9843, PAM -SD) • DPDT models = 35 mA Terminal Block Ratings up to 14 AWG DESCRIPTION Encapsulated Relays . These multi - purpose control relays offer SPDT or Connections 18 AWG color - coded wire leads DPDT, 10 Amp contacts in a variety of mechanical 2088 9021 packages. Models are available for coil operation by one of four input voltages allowing a single relay to be Contact Ratings 10 A @ 115 VAC, resistive energized from a voltage source of 18 -35 VDC or VAC, Voltage 18 VACNDC, 115, or 230 VAC 115 VAC, or 230 VAC (not available with 4098 - 9843). Coil Ratings Voltage selection is made by wiring to the appropriate Current 15 mA @ 24 VACNDC, 115, or 230 VAC input terminals. 4098 -9843 Each relay model (except model 4098 -9843) contains a Coil Ratings 18 - 35 VDC input, 15 mA @ 24 VDC red LED which indicates that the relay coil is energized. • 10 A @ 115 VAC Mounting options are varied for application flexibility. Contact Ratings • 7 A@ 28 VDC Track mounted relays may be "snapped apart" from a • 250 p.A @ 5 VDC standard four - module assembly and used General 5pecifications_(all models);' ; independently if desired. Temperature Range -58° F to 185° F ( -50° C to 85° C) * Product listings are by Air Products & Controls, Ltd. per model numbers shown on page 2. © 2001 Simplex Time Recorder Co. All rights reserved. S2088 0010 - 4/01 RELAY SELECTION CHART Reference`, . AWProducts 'Relay ,`','Relay, Packaging Di Number.` ' ` Model ` Type Quantity 2088 -9007 MR -101/T SPDT 3" H x 2 1/8" W x 1 1/2" D Track mount, without enclosure (76 mm x 54 mm x 38 mm) 2088 -9009 MR -201/T DPDT Single 2088 -9008 MR -101/C SPDT Track mount with enclosure 6 1/8" H x 3 1/4" W x 2 1/2" D 2088 -9010 MR -201/C DPDT (156 mm x 83 mm x 64 mm) 2088 -9017 MR -104/T SPDT 3" H x 8 1/2" W x 1 1/2" D Track mount, without enclosure 2088 -9019 MR -204/T DPDT (76 mm x 216 mm x 38 mm) Four 2088 -9018 MR -104/C SPDT Track mount with enclosure 6 1/8" H x 9 1/2" W x 2 1/2" D 2088 -9020 MR -204/C DPDT (156 mm x 241 mm x 64 mm) Encapsulated, multi - voltage coil, color 1 1/2" H x 1" W x 7/8" D 2088 -9021 PAM -1 coded 18 AWG wire leads, with coil (38 mm x 25.4 mm x 22 mm) SPDT Single status LED 4098 -9843 PAM SD Encapsulated, 24 VDC coil, color 1 1/2" H x 1 3/16" W x 13/16" D coded 18 AWG wire leads (no LED) (38 mm x 30 mm x 21 mm) TRACK MOUNT RELAY WIRING REFERENCE SPDT contacts rated DPDT contacts rated 10 A @ 115 VAC, resistive / 10 A @ 115 VAC, resistive ® NC C NO ® ® ® NC C NO NC C NO ®®® ®®®®® - Relay energized LED 1 ® ® ®® ®@ ® ® 0 18/24 115 230 ® 0 0 18/24 115 230 I I I I I I I I (18-35) VDC ( -) ( +) ;; (18 -35) VDC ( -) ( +) ?" :,, ; - Coil voltage Coil voltage _ . (note polarity (18 -35) VAC AC AC _ (note po (18 -35) VAC AC AC for DC) 115 VAC N •> V for DC) 115 VAC N . V 230 VAC V V 230 VAC V V Terminal strip connections Terminal strip connections SPDT models DPDT models Simplex and the Simplex logo are either trademarks or registered trademarks of Simplex Time Recorder Co. in the U.S. and /or other countries. S2088 0010 - 4/01 e Westminster, Massachusetts 01441 -0001 U. S. A. 'Z Offices and Representatives Throughout the World Visit us on the world wide web at www.simplexnet.com. All specifications and other information shown were current as of printing and are subject to change without notice ® Simplex Releasing System Peripherals • UL, ULC Listed; FM Non -Coded Manual Stations and CSFM Approved* for Releasing Applications Features Manual fire alarm stations for releasing applications:. , • Double action push and pull operation with a [ , A\ e`_!„ ° ` A:.0chngi normally open (N.O.) contact • Current limited model is available with series PUSH 4,4 connected 560 S2 resistor for Style C operation, ^ ;, (current limited = alarm; open or short = trouble) DO It ' • Operation complies with ADA requirements • Pull lever protrudes when alarmed _,..:_ -, ` •�x�s - • Break -rod is supplied (use is optiona' y • Label kit provides six varieties of releasing ,..... ; ... T. applications (ordered separately) „1 • Screw terminals for wiring connections °`' =.r3 V41:0,.M Tamper resistant reset key lock (keyed same as Simplex fire alarm cabinets) Double Action Push Type Manual Release Station (shown with sample release label) Multiple mounting options: • Surface or semi -flush with standard boxes or matching Simplex boxes�r tug, • Flush mount adapter kit • Adapters are available for retrofitting to cormmonly!�' available existing boxes g '" UL listed to Standard 38 o. eration: 3� t� Double Action Push Type Manual Release ZANY , , % -� • `�^, I` t, Stations require that a spring loaded interference plate 'Y z (marked PUSH be pushed back to access the pull lever of �, • the single action station, reducing the possibility of an accidental activation. A firm downward pull of the lever Label Kit 4099 - 9802 then activates the alarm switch, breaking an internal plastic break -rod, visible below the pull lever. Break -rod use is optional. Use of a break -rod can provide an additional reduction of the possibility of an accidental Label Selection' activation without interfering with the minimum pull requirements needed for easy activation. A blank area on the front of the station allows the selection of a label to match the specific release When activated, the pull lever latches into the alarm application (label kit is ordered separately). position and remains extended out of the housing to provide a visible indication. (Refer to data sheet S2099 -0007 for standard Simplex Station reset requires the use of a key to reset the manual stations.) manual station lever and deactivate the alarm switch. (If the break -rod is used it must be replaced.) ' This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing Station testing is performed by physical activation of 7150- 0026:175 for allowable values and/or conditions conceming material presented in this document. It is subject to re- examination, revision, and possible cancellation. This the pull lever. Electrical testing can be also performed by product was not MEA (NYC) approved as of document revision date. Additional listings unlocking the station housing t0 activate the alarm switch. maybe applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster S2099-0010-1 6/2003 ma x. . u�Ra�x Product Selection. . Double Action, Push Operation, Manual Release Stations Model,' ^ - Description 2099 -9149 Standard operation, N.O. contact Manual release station, red housing with white letters and white 2099 -9152 For Style C operation, N.O. contact pull lever; requires label kit 4099 -9802 with series connected 560 0 resistor 4099 -9802 Label kit; select the label required for the specific release application; types include: Clean Agent, Extinguishing, Carbon Dioxide, Foam System, Sprinkler, and Manual Accessories Model*-,',, ;. \,_., y ,',.:,Description: ``,_ . Reference 2975 -9178 Surface mount Steel red box Refer to page 3 for dimensions 2975 -9022 Cast aluminum 2099 -9813 Semi -flush trim plate for double gang switch box, red Typically for retrofit, refer to 2099 -9814 Surface trim plate for Wiremold box V5744 -2, red page 4 for details 2099 -9819 Flush mount Black Refer to page 4 for details 2099 -9820 adapter kit Beige 2099 -9804 Replacement break -rod S : ecificationsl; Wire Connections Screw terminal for in /out wiring, for 18 to 14 AWG wire (0.82 mm to 2.08 mm Temperature Range 32° to 140° F (0° to 60° C) intended for indoor operation Humidity Range Up to 90% RH at 90° F (38° F) Housing Color Red with white raised lettering Material Housing and pull lever are Lexan polycarbonate or equal Pull Lever Color White with red raised lettering Housing Dimensions 5" H x 3 -3/4" W x 1" D (127 mm x 95 mm x 25 mm) - 0em4lushMl untln•` Reference Single Gang Box Mount 4" Square Box Mount Single gang box, 2 -1/2" deep 4" (102 mm) square box, 2 -1/8" (54 mm) minimum (64 mm), RACO #500 or equal dept RACO #231 or equal (supplied by others) (supplied by others) \ re \} Mount flush or with /�ra - 1 / 1/16" (2 mm) maximum extension I C n DO NOT R ECESS ' 4" Square box o with cover plate Station FIRE ® ALARM sid view PUSH Single gang cover plate, 3/4" IIII (19 mm) extension, RACO #773 PULL DOWN I or equal (supplied by others) ` - Single gang 1 Wall surface box outline Semi -Flush Mount Side View e sim x xnxuAL RELEASE 2 S2099- 0010 -1 6/2003 S.urface:Mountin; Reference 2975 -9178 Box 2975 -9022 Cast Box Preferred Mounting. For surface 5- 3/16" H x 4" W x 2- 3/16" D 5" H x 3 -7/8" W x 2- 3/16" D mounting, the preferred electrical (132 mm x 102 mm x 56 mm) (127 mm x 98 mm x 56 mm) (ordered separately) (ordered separately) boxes are shown in the illustration . r to the right. Additional Mounting i 0 Refer to page 4 for Wiremold box �' mounting compatibility. Knockouts located top and bottom I FIRE ® ALARM PUSH o t� - I PULL DOWN ■ i' Access for 3/4" threaded 5 " conduit located top and bottom (127 mm) £iSim ex MANUAL i� RELEASE 1" (25.4 mm) 3 -3/4" (95 mm) --'—.1 2099 Series Manual Release Station • . SurfaccMountSide, Viet Simplex 2975 -9178 box (shown for reference) i , .�a.::, �.. ev; y ,r,� a. Station cover , 411,0 `"°< hinges open for s� i i :; installation access , 01* WM ` .rte "��� � �.. �::— 3 S2099- 0010 -1 6/2003 Additiiiiii Mountin: Information;; / / For retrofit and new installations, additional compatible mounting boxes and the required o • O W iremold adapter plates are shown in the illustration to ®o CIO receptacle box 2099 -9814 Surface trim model V5744 -2 • the right. for Wiremold box (supplied by 5 -1 /8" H x 5" W others) (130 mm x 127 mm) O O ;/ O ® 'O Two gang switch box, each 3 "Hx2 "Wx2 -3 /4 "D .044.44 O VAT 1 (76 mm x 51 mm x 70 mm) ,n >.� ,K,t.,'_ , =,r°.. ; - (supplied by others) PUSH ' li 6 Q ale ) ri 4 . O ® Ez - .D �—LJ 2099 -9813 Semi -flush trim for 2 -gang switch box, 6" H x 4 -1/2" W , (152 mm x 114 mm) Flush Moutm6Ailti rmat>on Flush mount adapter kit 2099 -9819, Black 2099 -9820, Beige ��� z . ; ter t 1 Box must be recessed into wall `` v y � 0 � `— 1" to 1 -1/8" (25.4 mm to 29 mm) * MatataatfiatiriraPaltaitaial '4,1* '' 1 1 14 ` t �� i '`% ' � ,f ' 4 6 , 0ily - Ei 0 °' P USH x '' ° s. 0 (203 mm) ,, _ , ',, ! - -, , .' Hole cutout must be a 4.11,' £ A^ , PULL DOWN . � minimum of 6" H by 5" W 6' 1 M - , (152mmby127mm) (152 \ t �" ge , 0 mm) ai 44."?' s r X�eg T ' 0 vT4ifi.„) raggiriv Of0"T ' V ROA it bz Ee z% s , 4- 11/16" (119 mm) =41 �� 37„ square box, 2-1/8" *f; "` r i � ,,,'„ *;. 4 i,,.. , {apt (54 mm) minimum ',''''',,4=14: =10-'", , ' '` ;. :5,4aiaski? =4A -':. a y„ Wall depth (by others) 4 -3/4" (121 mm) I surface 6 -3/4" (171 mm) 11 Front View Side View Tyco, Simplex. and the Simplex logo are trademarks of Tyco Services AG or its affiliates in the U S. and /or other countries. Lexan is a trademark of the General Electric Co. YVirenold is a trademark of the Wiremold Company. Si' r � ) • a Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S2099- 0010 -1 6/2003 0 . ; t i s �� www .tycosafetyproducts- usa- wm.com 0 2003 Tyco Safety Products Westminster All rights reserved All specifications and other mfrirmation shmir were current at ofdocument revision date and are subject to change irit/rout notice Simplex TrueAlarm Smoke Detectors UL, ULC Listed; FM, CSFM, TrueAlarm Photoelectric Smoke Detectors and MEA (NYC) Approved* for Two -Wire and Four -Wire Bases Features; R:: ' �,� Photoelectric smoke detector with on -board ��:,� „���Y <.,.� ",.. : «- ����, = � • �_� TrueAlarm sensitivity drift compensation u - - UL listed to Standard 268 Functional chamber enclosure: I -` I : :1 , • Louvered design enhances smoke capture by directing flow to chamber • Entrance areas are minimally visible when ceiling mounted > 4098 -9601 TrueAlarm Photoelectric Detector Mounted in Base Multi- function indicator LED indicates normal and alarm conditions Magnetically operated functional test: • Initiates alarm and verifies performance • Identifies general sensitivity status using detector S eCifiCatIons LED Voltage 15 to 32 VDC from Fire Alarm Control Models available in two sensitivity settings: Panel IDC • 4098 -9601, Standard Sensitivity, nominal 2.8 % /ft Standby Current 100 1uA @ 24 VDC obscuration Up to 86 mA maximum, exact current is • 4098 -9605, Special Application Sensitivity, Alarm Current, 2-Wire determined by alarm current limiting of o Operation connected IDC • nominal 3.5 /o /ft obscuration Available base options: Alarm Current 4-Wire 24 mA typical @ 24 VDC Operation • Bases for 2 -wire or 4 -wire operation Auxiliary Relay Ratings Refer to page 2 under Product Selection • Auxiliary alarm relay output Air Velocity Range 0 -2000 ft/min (0-610 m /min) Optional remote alarm indicating LED UL Listed Temp. Range 32° to 100° F (0° to 38° C) Operating Temp. Range 15° to 122° F ( -9° to + 50° C) Humidity Ran e 10% to 95% RH from 32° to 122° F Descri 11011 y g (0° to 50° C) non - condensing Simplex TrueAlarm photoelectric detectors Color Frost White provide many of the proven TrueAlarm analog sensing 4 -7/8” Dia. x 1 -7/8" H, mounted in base features for applications where detectors are connected to Dimensions (124 mm x 48 mm); refer to page 3 for conventional 2 -wire or 4 -wire initiating device circuits detail (IDCs). Each TrueAlarm detector has an on -board microprocessor that evaluates its photoelectric light scattering chamber activity and makes an intelligent decision based on light obscuration history as to whether an alarm condition is present. TrueAlarm detectors are packaged in a patented ULC listed models are designated with a "C" suffix such as 4098- 9601C. This product has p 9 p been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of housing that minimizes the visibility of the air intake the California Health and Safety Code. See CSFM Listing 7272- 0026:219 for allowable louvers from the normal viewing locations while values and/or conditions concerning matenal presented in this document. It is subject to re examination, revision, and possible cancellation. Accepted for use — City of New York maintaining a high performance smoke capture ability Department of Buildings — MEA35 -93E. Additional listings may be applicable; contact your Bases are available for remote alarm LED indicator local Simplex product supplier for the latest status. connections and auxiliary relay outputs. t TrueAlarm smoke detector operation is protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683; 5,400,014; 5,543,777; 5,710,541; D383,407; 0388,352; D392,573. S4098- 0015 -5 10/02 AeAlarm Smoke.Detector-FeatUIPP., Intelligent Data Evaluation. Conventional smoke directly into alarm with the magnetic test. If there is an detectors will typically drift toward being too sensitive off - normal condition, the LED pulses first to indicate the due to the accumulation of dust and dirt. With TrueAlarm condition and then goes into alarm. (See page 3.) analog detection, data from the photoelectric chamber is gppllcaton Referen monitored and analyzed at the detector to provide a continuously shifting reference point. Detector Locations. Locations should be determined only after careful consideration of the physical layout and Drift Compensation. The data evaluation and its contents of the area to be protected. Refer to NFPA 72, shifting reference point provide a software filtering the National Fire Alarm Code. On smooth ceilings, process that compensates for environmental factors (dust, smoke detector spacing of 30 ft (9.1 m) may be used as a dirt, etc.) and component aging, establishing an accurate guide. For detailed installation information, refer to 4098 reference for evaluating new activity. With this filtering, Detectors, Sensors, and Bases Application Manual the resulting drift compensation provides a significant (574 -709). reduction in the probability of false or nuisance alarms caused by shifts in sensitivity — either up or down. Sensitivity Selection. The 4098 -9601 standard Magnetic Test Information. Status information is sensitivity detector is recommended for most applications. When a special application for a reduced sensitivity available by performing the magnetic test and observing detector is required, the 4098-9605 should be considered. the detector LED pulses. The LED will normally go Consult your local Simplex product supplier for assistance in determining the proper selection. ��roduct Se IpOtloni : Smoke Detectors • Model Description ;` Nominal Sensitivity ;Compatibility. > 4098 -9601 2.8 %/ft (standard) Compatible with bases: 4098 -9788, 4098 -9682, and TrueAlarm Photoelectric Detector ° 4098 -9683 4098 -9605 3.5%/ft Compatible Bases Model . -Descriptions. , • . . Details * 4098 9788 2-Wire Base with connections for IDC and LED connections are screw terminals for in /out wiring, > Remote Alarm LED Indicator 18 to 14 AWG 4 -Wire Base with Auxiliary Alarm Relay Ratings, Single Form "C ", For Suppressed Loads: Relay Contacts and connections for Power limited, 3 A @ 28 VDC; Non -power limited, 3 A @ 120 VAC 4098-9682 Remote LED Alarm Indicator Wiring Connections (In /Out where required): NOTE: Requires external 24 VDC for Relay contacts and IDC wiring, color coded 18 AWG leads; operation LED wiring, screw terminals for 18 to 14 AWG 2 -Wire Base with Auxiliary Alarm Relay Ratings, Dual Form "C ", For Suppressed Loads: Relay & connections for Remote LED Power limited, 1 A @ 28 VDC; Non -power limited, 1/2 A @ 120 VAC Indicator 4098 -9683 Wiring Connections (In /Out where required): NOTE: Must be connected as the only device on the IDC to ensure relay Relay contacts and IDC ( -), color coded 18 AWG leads; operation. IDC ( +) and LED wiring, screw terminals for 18 to 14 AWG Detector Accessories Model Description' . .Details* . ., Required for mounting to surface mounted 4" (102 mm) square or 4" octagonal boxes, and to 4" square flush mounted boxes 4098 -9832 Adapter Plate May be used when retrofitting existing bases Compatible with detector bases 4098 -9788, -9682, & -9683 4098 -9830 Remote LED Indicator Mounted on single gang stainless steel plate 2098 -9739 Encapsulated Dimensions: 2 -1/2" x 1 -1/2" x 1" Required for 4 -wire circuits using 24 VDC (64 mm x 38 mm x 25.4 mm) 4098 -9682 base, one per circuit; select End -of -Line Relay Mounted on single gang mounting type as required; wiring is 2098 -9735 Plate Mounted stainless steel plate color coded 18 AWG wire leads * Refer to pages 3 and 4 for dimensions and additional mounting details; 18 AWG = 0.82 mm 14 AWG = 2.08 mm 2 S4098- 0015 -5 10/02 hector Status LEDAi d lcations LED Indication Status Pulses approximately every 4 seconds Normal Steady On Alarm LED Response to Magnetic Test * LED Indication Followed By Status Action LED turns ON Alarm is initiated Normal sensitivity is within None compensation range LED pulses quickly, 6 times in 3 seconds, Alarm is initiated More sensitive, out of normal then turns ON compensation range Cleaning or other service is required LED pulses slowly, Alarm is initiated Less sensitive, out of normal 4 times in 8 seconds, compensation range then turns ON Does not initiate Alarm Detector is malfunctioning Service is required * Testing requires placing a magnet at the designated location on the detector cover for 4 seconds. Refer to Application Manual 574 -709 for further test and maintenance information. Dtinenslo =Referene Id folrmaaio:Ii 1/4" (6.4 m l m) 6 - 3/8" (162 mm) e.l 4 4098 -9832 Adapter Plate F 'I 4 - 7/8" (124 mm) P Base height 1 - 7/8" 11/16" (48 mm) (17 mm) i ®niii® r's: - ^,ax< � ;„',_,e;;?;,::�f R ®111 ` LED Status Indicator (with clear lens) 4098 -9601 & -9605 Dimensions Mounted on Base ALARM 0 Ei simplex 4098 - 9830 Remote LED Indicator (not to scale) 3 S4098- 0015 -5 10/02 Mountln • Information;' (Electrical boxes are supplied by others.) . Electrical Box Requirements: Without relay (base 4098 - 9788): 4" octagonal or 4" square, 1 -1/2" deep Single gang, 2" deep With relay (bases 4098 -9682 and 4098 - 9683): 4" octagonal, 1 -1/2" deep, with 1 -1/2" extension ring 4" square, 1 -1/2" deep, with 1 -1/2" extension ring Surface mount reference 4" (102 mm) Ate"- 4" (102 mm) square box octagonal box 4 1 1 -1/2" (38 mm) Flush mount reference, mount even with final minimum box depth surface, or with up to 1/4" (6.4 mm) maximum recess 4098 -9832 Adapter Plate, required for mounting i to surface mounted boxes and to 4" square flush mount boxes t.______ i 4098 -9682 and 4098 -9683 include a relay module that fi mounts in base electrical box r' I Smoke Detector Bases 4098 -9788, 9682, & -9683 IMM MIMIIIIMIIMI ylllmo 1 imes■IIImi 4098-9601, -9605 Smoke Detector Tyco. Simplex, the Simplex logo, and TrueAlarnt are trademark, of Tyco International Services' AG or its affiliates in the U.S. and /or other countries NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA). e S IeX TEPG - US • 91 Technology Drive • Westminster, Massachusetts • 01441 - 0001 • USA S4098 0015 - 5 10/02 2002 TEPG -US (a Tvco company) All rights reserved. All specifications and other information www. tepg. corn shown were current as of document revision date and are subject to change without notice • 5 t. { ® 2081 -9046 Coil kr Supervision Module Wiring Instructions Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex. ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs. Servicing should be performed by qualified Simplex Representatives. STATIC HAZARD - Static electricity can damage components. Therefore, P1 handle as follows: `) 1. Ground yourself before opening or installing components (use the 553 -484 Static Control Kit). 2. Keep uninstalled component wrapped in anti - static material at all times. Overview This publication shows how to connect the 2081 -9046 Coil Supervision Module to a Fire Alarm Control Panel (FACP). Refer to the 4010 Fire Alarm — Front Panel Installing, Operating, and Programming Instructions (574 -052) for configuration information. Refer to the 842 -058 Field Wiring Diagram for additional 4010 wiring information. For other FACPs see Field Wiring Drawings 841 -669 for the 4002, 841 -984 for the 4002 non -power limited, 841 -940 for the 4020, and 841 -941 for the 4100. Overview of 2081 -9046 Coil The 2081 -9046 Coil Supervision Module (shown in Figure 1) supervises and Supervision Module provides power for an electrically compatible suppression release solenoid coil, when connected to a 24 VDC Notification Appliance Circuit (NAC). The input voltage from the NAC must be connected between the Red and Black wires of the module. The output control voltage to the solenoid is taken from the Yellow and Black wires of the module. The output control voltage to the suppression solenoid is activated when the NAC is activated, alarm state (i.e., +24 VDC to the Red wire and 0 VDC to the Black wire). The output control voltage to the suppression solenoid is non - active when the NAC is non - active in a supervisory state (i.e. negative to the Red wire and positive to the Black wire). The module allows for supervision of the connection to the solenoid coil. Diode suppression is also provided for overvoltage inductive spikes. BLK RED BLK YEL Figure 1. Coil Supervision Module C 2000 Simplex Time Recorder Co., Westminster. MA 01441 -0001 USA 574 -437 All Specifications and information shown were current as of publication and are subject to change without notice. Rev. B 2081 -9046 Coil Supervision Module Electrical Specifications The lists below show the input power requirements and the output specifications for the 2081 -9046 Coil Supervision Module. Input Power Requirements • Nominal Voltage 24 VDC Output Specifications • Nominal Voltage 24 VDC • Maximum Current 2 A G 24 VDC • Stand By Current 2.2 mA (Maximum) Wiring IMPORTANT: Yellow and Black wires connected to the solenoid are non -power limited (indicated by shaded area in Figure 2). ! You must maintain 1/4" separation between the Yellow and Black wires and the two input Black and Red power limited wires. WIRING SUPERVISED FOR OPENS AND GROUND FAULTS NOTE 1 RED YEL r TO REVERSE i POLARITY NAC, � RED= +ALARM /- SUPERVISION NAC+ NAC+ tr XI +ALARM — i BLACK= - ALARM/ +SUPERVISION NAC- NAC- - AIARM — I I / L BLK BLK NOTE 1 / COIL SUPERVISION MODULE SOLENOID 2081.9046 LOCATED IN (1 PER CIRCUIT) JUNCTION VALVE CONNECTION BOX JUNCTION BOX Note 1: Separate conduit entrances are required for power limited (Red and Black) and non -power limited (Yellow and Black) wire pairs. Note 2: Power limited cabling must be either FPL, FPLR, FPLP, or equivalent type cable per the NEC. Figure 2. Wiring Connections for Coil Supervision Module ta 574 -437 X Rev. B 1� � Simplex Releasing System Peripherals UL, ULC Listed; Fire Suppression System Abort Switches and Releasing CSFM Approved* Appliance Circuit (RAC) Maintenance Switches Features; Abort switches provide a manual Fire Suppression System release abort request: FIRE SUPPRESSION • Pushbutton momentary switch is mounted on a stainless SYSTEM ABORT, steel single -gang plate • A protruding collar protects the switch from accidental 1 contact (collar is removable if required) • Models are available for flush or surface mount; flush mount is on standard single -gang box; surface mount includes a red mounting box PUSH AND HOLDV • Available with internal 1.2 kS2 resistor for current limited operation _; fiSimpleic.; Maintenance switches with indicator provide a secure and visible disconnect means for servicing Abort Switch (shown 1/2 size) Fire Suppression System Releasing Appliance Circuits (RACs): • Maintained position keyswitch is mounted on a stainless steel double -gang plate • Key is removable in either normal or disabled position Disconnect /Disable status indicator is a bright • NORMAL incandescent bulb with red lens, powered from separate 24 VDC �,::.. , , Dlsc� ,.., - _. • Models are available for flush or surface mount; flush 4,0 DISABLE mount is on standard two -gang ang box; surface mount : ; includes a red mounting box � {q � � AFIRE SUPPRESSION � � UL listed to Standard 864 Descriptiori' � s �" Releasing systems typically require maintenance Maintenance Switch with Disconnect Indicator Lamp disconnect switches and often require abort switches. (shown 1/2 size) These abort and maintenance switches are clearly labeled and combine easy operation with rugged construction for high integrity operation. S � sCIfIGat10 11S Prod'u& Select on: Abort Switch Silver contacts; 1 N.O. & 1 N.C.; Abort Switches rated 2 A resistive © 30 VDC Model`; Description, r`, Silver contacts; 1 N.O. & 1 N.C.; 2080 -9056 Flush mount Maintenance Switch rated 2 A resistive © 30 VDC fflmste 2080 -9057 Surface mount; includes mounting box Replaceable 2 W incandescent bulb; 2080 -9067 Flush mount; current limited with 1.2 kS2, 1W resistor Maintenance Switch 24 to 30 VDC typical; 83 mA @ 24 VDC; Indicator Light requires separate 24 VDC 2080 -9068 Surface mount, current limited with 1.2 kS2 resistor; includes mounting box Wire connections Terminal blocks for in /out wiring; 18 to Maintenance Switches with Disconnect Indicator Lamp 14 AWG wire (0.82 mm to 2.08 mm ) Model Description Temperature Range 32° F to 120° F (0° C to 49° C) 2080-9059 Flush mount Humidity Range Up to 93% at 90 °F (32° C) 2080 -9060 Surface mount; includes mounting box Accessories for Field Installation • These products has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code See CSFM Listing 7300 -0026:313 Model . 'Description - for allowable values and /or conditions concerning material presented in this document. See Additional Contact Block for Abort or Maintenance Switch; product selection for listing exception. This product was not approved by FM, or MEA (NYC) 2080 -9061 1 N.O. & 1 N.C.; UL recognized component for use with as of document revision date. Additional listings may be applicable, contact your local Simplex@ product supplier for the latest status. Listings and approvals under Simplex Time these switches; listings and approvals are not applicable Recorder Co. are the property of Tyco Safety Products Westminster. S2080- 0010 -1 5/2003 About Swifddiistallation Reference„ Red box is supplied with surface mount Abort Switch 2080 -9057 or 2080 -9068 Box width J 3" (76 mm) r I 2 -1/4" (56 mm) into box . CD I T ,. FIRE 1 /2" IRE SUPPRESSION ( mm) SYSTEM ABORT Abort Switch height 4 -1/2" 3 '5:'= .t:_ • (114 mm) jf : �; Ate' +<.,; Box hei ht g h I 4- 13/16" - fi g g f _ -s a ��� L (122 mm) Switch recess I w u 4 i, ', -, . depth 5/32" t - 'i 4` i PUSH AND HOLD (4 mm) I: ® Removable f3 Simplex - collar r' • Abort 2 -3/4" width, 2 -3/4" (70 mm) I �(70 mm) .1 Supplied gasket attaches to box; NOTE: For flush mounting, use field installed for flush mount; a 2 -3/4" deep (70 mm) pre- attached for surface mount single -gang box Ntglitenance,SACliInstallation Reference Red box is supplied with surface mount Maintenance Switch 2080 -9060 Box dimensions r 4- 13/16" (122 mm) square 2 -1/4" (56 mm) into box , CD (11) T „ „, ,„ , ___ 4 -1/2” NORMAL (114 mm) 1 - t ie DISC./ , , i DISABLE �r ! i ', FIRE SUPPRESSION ,s o DISCONNECT I DISABLE CD aD gsimplex 4 % - - -- Maintenance Switch ' 2 -3/4" width 4- 9/16" (116 mm) ,.1 i I4 (70 mm) � Supplied gasket attaches to box; NOTE: For flush mounting, use field installed for flush mount; a 2 -3/4" deep (70 mm) pre- attached for surface mount double -gang box Tvco. Simplex, and the Simplex logo are trademarks of Tvco International Services AG or us affiliates in the U.S. and /or other countries Ei Tyco Safety Products Westminster • • Westminster, MA • • 01441 -0001 • USA S2080- 0010 -1 5/2003 ® " iex www .fycosafetyproducts- usa- wm.com © 2003 Two Safety Products Westminster. All rights reserved. All specifications and other information shown were current as ofdocument revision date and are subject 0 change without notice. ® Sim • lex Release Control Fire Alarm Systems UL, ULC, CSFM Listed; FM Approved; 4004R Suppression Releasing Panel for Automatic MEA (NYC) Acceptance* Extinguishing, Deluge and Preaction Sprinkler Control features,', Agent discharge path Fire alarm control panel designed specifically for suppression release operation with: Actuator Agent Actuator circuit • Four initiating device circuits (IDCs) • Two notification appliance circuits (NACs) Coil supervisory • Two releasing appliance circuits (RACs) module • Two special purpose monitor inputs (SPMs) that accept manual release request and manual abort request for • • I Agent Release systems, and waterflow and supervisory Maintenance Switch 0 =.0 for Preaction or Deluge systems • Three auxiliary relays with selectable functions RAC 1 RAC 2 • Easily selected activity timing options SPM t Suppression release operation includes: O !:ru?c t.r ril:ul:r.rfial,l: l ` • Automatic extinguishing release SPM 2 - , _cJ. NAC 1 • Deluge and preaction sprinkler system release =sal IDC • Dual or single hazard area protection • IDCs are selectable for cross - zoning or for activation J NAC 2 from a single detection input IDCs 2, 3, and 4 ulla +Rw` '•-• • '.G!GI :I Ili / "I ba�llaal[I LPI tart • Short circuit RAC supervision 4004R Suppression Release Panel Audible Escalation of Events: Temporal or 20 bpm March Time pattern for first 4004R Suppression Release Panel • • cross -zone alarm One -Line System Reference Drawing • 120 bpm March Time pattern to indicate release timer Infroduction (Continued) active On steady to indicate release timer expired and actuator Flexible I/O Capabilities. Four IDCs allow for either • is activated four separately monitored zones or two, cross -zoned connections. Two SPMs allow dedicated manual inputs for Operator interface provides: release or abort, or waterflow and supervisory, depending • Status LEDs per circuit for Alarm, Trouble, and on system type. Two releasing appliance circuits (RACs) Supervisory (where appropriate) supervise to the actuator coils and activate the actuators • Acknowledge, Alarm Silence, and System Reset when required. The two NACs and the three panel auxiliary • Operating mode selection and timer selections when in relays provide status condition information. programming mode Easy Program Selections. The operator panel has a Compatible with Listed /Approved 24 VDC or program mode that allows selection of panel operation 2, 12 VDC series connected actuators type and detailed operating selections using an easily Related system components: selected sequential programming operation. • Coil supervision module 2081 -9046, one per RAC History Log. The last 50 events are stored in • Maintenance Switch, one per RAC non- volatile memory. This information is accessed by • Abort Switch connecting a technician's computer to the service port Listed to: which is also used to set the date and time. • UL Standard 864 Panel,Featt re. Descri •tion • ULC Standard S527-99 Operator Panel. The operator panel has alarm and ' i1 trouble status indicating LEDs for each input and ntroduction'; g output, P visible through the locking cabinet door (refer to diagram Dedicated for Suppression Release. 4004R on page 4). Unlocking the door provides access to the Suppression Release Panels provide conventional fire Acknowledge, Alarm Silence, and System Reset alarm control circuits and are equipped with the features pushbutton switches. required for a wide variety of single or dual hazard • See product selection on page 2 for additional details. This product has been approved by suppression release applications. Capabilities include the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California automatic extinguishing agent release and deluge and Health and Safety Code. See CSFM Listing 7165 - 0026:314 for allowable values and/or conditions conceming material presented in this document It is subject to re- examination, preaction sprinkler control. revision, and possible cancellation. Additional listings may be applicable; contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co are the property of Tyco Safety Products Westminster S4004- 0002 -2 5/2006 .y 4 Two Class B Releasing Appliance Circuits (RACs). Panel Feafiure Description (Contrnued),t: Rated 2 A each, these circuits are dedicated to operating (NOTE: Refer to specifications on page 6 for more release control actuators. RAC cutout timing is selectable information.) as no cutout, 45 seconds, or 1, 3, 4, 5, 6, or 7 minutes. Four Class B IDCs provide coverage for either two Auxiliary Power Output. Two sets of output terminals cross -zoned areas or four separately zoned areas. IDCs are are provided, one for continuous operation and the other capable of supporting up to 30 Simplex current- limited for resettable operation, rated for 750 mA combined. smoke detectors or electronic heat detectors (see list on Resettable terminals are provided for 4 -wire smoke page 2) as well as manual stations and other compatible detector power. contact closure initiating devices. IDCs are capable of Standard Auxiliary Relay Outputs. Three relay Class A operation with an optional adapter module and can outputs are available, selectable as normally open or be programmed as Style C (short or open initiates a trouble) normally closed, rated 2 A @ 30 VDC, 0.35 p.f. inductive: for use with current limited devices only. Single hazard agent Aux Relay 1 (Trouble) is energized when Normal and is release applications monitor pressure switches with IDC 3 de- energized with a common Trouble condition. and tamper switches with IDC 4. Aux Relays 2 and 3 respond differently depending on the Two Class B Special Purpose Monitoring Circuits system type and whether single or dual hazard. Typical (SPMs) are dedicated for manual release or abort, or functions are: waterflow and supervisory, depending on system type. Inputs For Single Hazard Operation, Aux Relay 2 is the are normally open switches. An abort switch stops release common Alarm relay. Aux Relay 3 can be selected to while activated and upon deactivation, the release operation indicate pre- discharge (release time delay started), occurs after a selectable time delay. Manual release inputs common supervisory, waterflow, or pressure switch relay, override abort switches and activate the release after depending on the system type. selectable delays of from 0 to 30 seconds in 5 second For Dual Hazard Operation, Aux Relay 2 is for Hazard increments. For Dual Hazard applications, current limited Area 1 common Alarm; Aux Relay 3 is for Hazard Area 2 abort operation is required. SPMs are programmable as common Alarm. Style C and capable of Class A operation with the optional Power Supply and Battery Charger. During alarm, adapter module. the power supply provides 3 A at 25.5 VDC, filtered and Two Class B NACs are provided for reverse polarity regulated. The temperature compensated battery charger notification appliance operation, each rated 2 A. Class A provides 27.5 VDC for charging batteries suitable for up to operation is available with the optional adapter module. NAC 90 hour standby and 10 minutes of alarm. External battery operation is selectable per application. chargers and cabinets can be used for more battery backup. Pr *pduct Selections Release Control Panels .Model':, „ Color. :Listings,.: - Description 4004 -9301 Beige UL, ULC, CSFM, & FM Basic Releasing Panel; operates with AC input of: 120/220/230/240 VAC, UL, ULC, CSFM, FM, & 50/60 Hz (auto - select); includes: four IDCs, two NACs, two SPMs, two RACs, 4004 -9302 Red MEA (NYC) 3 auxiliary relays, and 3 A power supply with battery charger, cabinet and door 4004- 9301CAF Beige ULC only Basic Releasing Panel, same as above, but French for Canada; ULC listed only Expansion Modules Model "Description'=��. _ Reference 4004 9860 Auxiliary Relay Module; four dual contact relays selectable as N.O. or N.C.; rated 7 A Select Two maximum @ 120 VAC resistive, 5 A @ 30 VDC, 0.35 p.f. inductive; unsupervised contacts as 4004 -9864 Two Circuit Class A Adapter Module for IDCs, SPMs, or NACs Four maximum required Panel Accessories (See data sheet S4081 - 0001 for external battery cabinets with chargers and for larger battery sizes) Model ` • `Descriptiori Reference 4001 -9811 Remote Battery Meter Module, 0 -50 VDC voltmeter and Mounting requires a four -gang box, 1 -3/4" (45 mm) 5 -0 -5 A ammeter with beige four :gang cover plate minimum depth 2081 -9272 6.2 Ah battery, 12 V 2081 -9288 12.7 Ah battery, 12 V Select one battery model per system standby 2081 -9274 10 Ah battery, 12 V '='' °'' °> requirements; two batteries are required Release Control Systems Accessories (refer to additional information listed on page 3) Model:, Description _.. ;• 2081 -9046 Coil Supervision Module, one required per RAC; refer to pages 6 and 7 for detail 2081 9048 Abort Supervision Module; encapsulated 56052, 1/2 W resistor; for Dual Hazard SPM; allows non - current limited Abort and Manual Release stations to be on same circuit refer to pages 6 and 7 for detail 4081 Series End -of -Line Resistor Harnesses; refer to data sheet S4081 -0003 2099 Series Manual Stations for Releasing Applications; refer to data sheet S2099 -0010 4905 Series Strobe synchronization modules; 4905 -9914 for Class B, 4905 -9922 for Class A; see data sheet S4905 -0003 for details 2 S4004- 0002 -2 5/2006 Reference Information CempatibikSimplexkDetectors #and other 50160Components . Model Type Data Sheet 4098 -9601 Standard detector S4098 -0015 4098 -9605 Reduced sensitivity detector Photoelectric smoke detectors for 2 -wire and 4 -wire bases 4098 -9602 Combination smoke and heat detector S4098 -0017 4098 Series Ionization Smoke Detectors; 2 -wire and 4 -wire models S4098 -0018 4098 -9612 135° F (57 °C) Fixed heat detector 4098 -9614 200° F (93 °C) Electronic heat detectors for 2 -wire and 4 -wire bases S4098 -0014 4098 -9613 135° F (57 °C) Fixed with rate -of -rise 4098 -9615 200° F (93 °C) heat detector 2099 -9149 Standard Manual Release Station with selectable release labels; S2099 -0010 2099 -9152 Style C, with 560 4 internal resistor double action push, N.O. contact Maintenance Switches, flush or surface mount; indicatorlamps require 24 VDC wiring 2080 - Series S2081 -0010 Abort Switches, surface or flush mount; available standard or with 1.2 kS2, 1 W resistor Expansion`Modlyles Accessorie Auxiliary Relay Module 4004 -9860 provides four Maintenance Switch. Proper service of release additional relays. Dual hazard applications will require appliance circuits requires the ability to securely two modules for auxiliary relay operation. Each relay disconnect the release . i module has a manual disconnect switch that controls circuit during °` ','' .'. relays 2 through 4. (Trouble Relay 1 is not controlled.) installation and - m: �� Y outputs are re Rela out uts required to be connected to a 15 A maintenance. Simplex NORMAL � q x =� maximum circuit breaker. (Relay specifications are maintenance switches` '', detailed on page 6.) are controlled by i Am , msc.). < i keyswitch and initiate a ,,e, . Auxiliary Relay Module Operation is per the following: supervisory condition '° :'''t` "� §� w .'=t ° ° ;`,:i :r. EIRE StR1 ,'; ; <u,= ' Relay 1 activates on any common trouble associated with when in °-- DISCON itetriI its hazard or any system trouble `' ''`' �' ,- , ": discomiect /disable �"�`_':`' ;:x Relay 2 activates on any common alarm associated with its position. Models with / -''. >,, ,, : : : :,,,, :,,_ , , ms's,:`: ,' ;�`` = ti hazard lamp are on a Relay 3 activates for pressure switch, waterflow switch, or double gang plate and are powered from separate 24 VDC release timer as required per application type (hazard wiring. Mounting is on stainless steel plates and models specific), or activates with the second zone for cross -zoned are available as either surface or flush mount. systems (hazard specific) For additional Maintenance and Abort Switch information Relay 4 activates when the hazard specific RAC activates refer to data sheet 52080 -0010. Dual Circuit Class A Adapter Module 4004 -9864. Remote Battery Meter Module 4001 -9811 provides This module converts two Class B circuits to Class A a display of battery voltage and battery charge and operation. It consumes no additional current and is discharge current. This module mounts within 3 ft (1 m) compatible with IDCs, SPMs, and NACs. Up to four of the 4004R cabinet using a four -gang electrical box with modules may be mounted within the 1 -3/4" (45 mm) minimum depth. (See illustration below.) : ..,.:!:<.:',:‘ 4004 R cabinet. V'-. i FIRE ALARM SYSTEM FIRE SUPPrzESSioN;_ °._ Abort Switches. For manual abort ���. •= � - SYSTEM ABORT " "''.' - ' ', -' requests, these abort switches are -=-- -':?As _ s ' available with or without a built -in e I,_ 1.2 kQ 1 W resistor and are i oc vows °y. t oc PERESt I mounted on single -gang stainless ° ".. %4 e ."..v.:.: a 1 0� sxa i�wl�o�e9 38:.25 26 �'F6 #„ 0° ,, : steel plates. Abort switches are PUSH ANDiHOCDf, , ::, .., -;' ,.,: :, -.4i, _ connected to the SPM inputs per . 41-;,: : 4 , rl°> .' system requirements. Activity abort occurs while the • . - • . switch is pushed and continues after releasing the switch for the selected Abort Release Time Delay. (See illustration to the left.) 3 S4004- 0002 -2 5/2006 z � -xi :° .� �a - .�. �, i . :aro.:.. P�rogram�mtng Modes and $.04 ion C6404' Sequence Programming Mode Description Choices Cross -Zoned Combined Release Single Hazard Either Zone (RACs activate together) Agent Release Dual Hazard Cross -Zoned Independent Release . Either Zone (RACs are separate) 1 Application Mode (9 choices) Single Hazard Cross -Zoned Combined Release Either Zone (RACs activate together) Preaction /Deluge Dual Hazard Cross -Zoned Independent Release Either Zone (RACs are separate) Agent Release Single Hazard Cross - Zoned, NYC Abort (not UL listed) 2 IDC and SPM Circuit Style Class B /Class A or Style C 3 Automatic Release Time Delay 0, 10, 20, 30, 40, 50, or 60 seconds 4 RAC Cutout Timer No cutout, 45 seconds, or 1, 3, 4, 5, 6, or 7 minutes 5 Manual Release Time Delay 0, 5, 10, 15, 20, 25, or 30 seconds UL Standard 864 listed Immediate or 10 seconds remaining 6 Abort Release Time Delay Not:UL Standard 864` IRI abort (cross -zoned systems only), NYC abort, or listed : , original,release.delay•: 7 NAC Coding (where selectable) Temporal pattern or 20 beats per minute (first cross -zone alarm) Standard No inhibit or one minute inhibit selected as: both on until silence, NAC 1 on until Operation reset and NAC 2 on until silence, or both on until reset; 8 NAC Operation NOTE: For Halon 1301, Halon 1211, or clean agent release, a pre- discharge NAC Pre Discharge must be configured to warn of impending discharge, the release timer selects the Operation duration of the pre- discharged signal 9 Supervisory Latching Latching or non - latching 10 Supervisory Notification LED and tone -alert only, or with: NAC 2 also on; Aux Relay 3 also on; or both NAC 2 and Aux Relay 3 also on °Operator,, 00.F. u'Ii ion, 00,0 4 LABEL INSERT selectable for Preaction /Deluge or Agent Release, UL or ULC versions (UL Agent Release version shown for reference) RUN MODE: red LEDs I I indicate Manual Release RUN MODE: LEDs provide ,- r y' '• -;� -� activated (for Agent 7 Alarm Release Applications); - A t PP ) Alarm (red) and Trouble Zone 1 4 (yellow) status per I DC � ; ;: '''', . §, ; ' a , yellow LEDs indicate (Y ) yellow LED Troub ' Zone 5 Trouble zone; Zone 4 yello `l ; ,,,,,,,. ,:,. ., ,,,, ,,.....:� .� „r =a,,q'°" � Trouble for SPMs (Zones 5 >- , (' and 6) and NACs, for indicates supervisory status , k ,Q' Al arm , Manual Release =0 , ' ; ) if still flashing after ACK '" Zone 2i ° - N, ., RACs, yellow LED indicates f - : T rouble , ' Zone 6 Trouble t, I ,= supervisory if still flashing 4 ,:.A4, .:. IY7 'C. ` i after ACK l:r`' ; Alarm NA 1 Trouble ,. A . ;. Zone 3 —.� , P ROGRAM MODE: ;y'* tt,, ■ Trouble g "; NAC 2Trouble ,,° -1 PROGRAM MODE: Top ten LEDs indicate ;fir'- f:,? =r N: p # -s �, , _: .,,,, . _ •.> ,,, ._,,:� . , E Top nine LEDs provide Programming Mode Category Alarm RAC 1_' :� _ Programming Selection Zone 4 y Alarm Silenced yellow LED . " RAC ; " e'4 ` indicates that audible z .(r ~ r �, " �"' , . ?.Q` A l i , Alarm A gent Released notification appliances are i X ; ;c � r Agent Released red LED i , " " a r indicates RACs are activated silenced prior to system reset 4 4 Supervisory . Earth F au l t e' • = '. , — ro e T <" Y Earth Fault yellow LED Supervisory and System i a';rv,C r System Abort d � r indicates presence of an earth Trouble yellow LEDs; for UL ' ` "' s stems, indication of disabled rig` ` AC Power ° Relay Disconnect x i, ; fault Y a " { - or disconnected RAC , :�, , :, ; e 'x � Abort Active yellow LED i A LARM i � r SYS7EM � , ; tracks state of Abort Switch _ AC Power reen LED is on „ ` sE t ® ' NC SILEE `4 RESET 1 4 # 1 9 t ,' Relay Disconnect yellow LED with normal power status t( � �� y . indicates that expansion relays ^* a t A,ta' : 4P . „�s» i » ` t,.> . MajtNO have been disabled for service r ACK acknowledges status during RUN mode , , SYSTEM RESET restores the system to ■ and accepts selection during PROGRAM mode; ALARM SILENCE normal during RUN mode and toggles press and hold for 5 sec to perform LAMP TEST silences audible alarms the selection during PROGRAM mode i . i J 4 S4004- 0002 -2 5/2006 Release Confkit0 stem :Reference;? Requirements (Continued);. Automatic Extinguishing Release Systems. 4. For FM Approved Automatic Extinguishing Release, These systems automatically activate actuators for the secondary standby must be a minimum of 24 hours release of a fire extinguishing agent (such as dry with 5 minutes of alarm. Actuators must be chemical, water spray, foam, CO or Halon) in response electrically compatible. to fire detection device input. 5. For FM Approved Deluge and Preaction Sprinkler UL and FM Extinguishing Release System Panels operation: IDCs must be Class A, wired to must have a minimum of 24 hours of standby power. Listed/Approved devices; secondary standby capacity Initiating devices must be Listed /Approved for the must be a minimum of 90 hours with 10 minutes of application, and may be wired either Class A or B. alarm; and the specified compatible Automatic Water Actuators must be electrically compatible with the control Control Valves /Actuator must be used. (Refer to list panel circuits and power supplies, and are wired Class B on page 8.) to provide coil supervision (refer to additional 6. Power supply loading and wiring distances must be information in Requirements section below). per Installation, Programming, and Operating Deluge and Preaction Sprinkler Systems Instructions 579-354. automatically activate water control valves in response to 7. Battery standby must be selected for proper actuator fire detection device input. operation and may require a minimum voltage of Deluge Sprinkler Systems employ open sprinkler 23 VDC depending on the actuator. Detailed battery heads and provide water flow when the fire detection calculation reference information is contained in system activates a common automatic water control valve. Installation Instructions 579-354. They are used to deliver water simultaneously through all 8. Maintenance Switches, one per RAC, are required per of the system sprinkler heads. This type of system is NFPA 72 the National Fire Alarm Code' (2002 applicable where the immediate application of large Edition, Chapter 6) to allow the system to be tested or quantities of water over large areas is the proper fire serviced without actuating the fire suppression systems. response. Their use may not be allowed in same jurisdictions, always confirm local requirements. When used, Preaction Sprinkler Systems are similar to deluge Simplex Maintenance Switches are required to ensure systems except that normally closed sprinkler heads are that operation initiates a supervisory condition. used and supervisory air pressure is maintained in the pipe. Operation requires both an activated sprinkler head Aldrtlonal System Devlee Infgrmatlon?' and an activated fire alarm initiating device. 1. Simplex Abort Switches are available when abort UL requirements for Fire Alarm Systems Listed for operation is required. When used, wire on Special Automatic Release or Deluge and Preaction Sprinkler Purpose Monitoring Circuits (SPMs) as Class A or Systems are the same as described above for Automatic Class B; Simplex model Abort Switches are required. Extinguishing Release Systems. 2. Manual Release Stations are used for direct activation FM Approved requirements for Fire Alarm Systems of the release actuators with the appropriate time delay for Automatic Release of Deluge and Preaction Sprinkler implemented by the fire alarm control panel. Systems require operation of specific compatible FM 3. Reference for additional information is listed on pages 2 Approved Automatic Water Control Valves, a minimum and 3. secondary power capacity of 90 hours, and all circuits for the automatic release initiating devices must be capable of Addltional,lnfoemation operation during a single open circuit fault condition This data sheet is a summary of the extensive operating (Class A). features and options available with the 4004R Release Rele_aSe Control SyStemA3egU Control Panel. Complete details are covered in the 4004R Installation, Programming, and Operating Instructions 1. Actuators are connected as two -wire, Class B manual (publication 579 -354) shipped with each 4004R. notification/releasing circuits with only one 24 VDC Compatible system devices are listed on page 3. actuator per circuit to ensure supervision. Where applicable, two, 12 VDC actuators in series or one For general information, refer to Factory Mutual Research 12 VDC actuator and a manufacturer supplied series Corporation (FMRC) "FMRC Approval Guide," FM resistor may be used. Approval standard "Deluge Systems and Preaction Systems." 2. Coil Supervision Module, model 2081 -9046, must be wired electrically before the actuator and located in PLEASE NOTE: Proper operation of release control the actuator wiring junction box. (Refer to System systems requires that the system design, installation, and Connection Reference on page 7.) maintenance be peifomed correctly and in accordance with all applicable local and national codes, and 3. For UL Listed Automatic Extinguishing Release valves and actuators, refer to list on page 7. equipment manufacturer's instructions. No liability for total system operation is assumed or implied. 5 S4004- 0002 -2 5/2006 • Specifications (,Ofer„to diagrantongpage andpInstruetionssb79.354 for additional tiformatiori)LL Power Ratings .. Voltage Ratings 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto - select AC Input Current Ratings 2 A maximum @ 120 VAC input; 1 A maximum @ 240 VAC input Power Supply Output 3 A maximum available for external loads Battery Charger Temperature compensated, capable of recharging batteries required for 90 hour standby and 10 minute alarm (contingent on auxiliary power load) Standby Current 100 mA; with IDCs fully loaded, tone -alert silenced, trouble LED on, charger off Alarm Current 264 mA + external loads; (2 zones in alarm & 2 internal relays, NACs and RACs on) Standard Circuit Ratings (NOTE: Total.DC current = 3 A maximum; see NAC ratings for details) Supervisory 3 mA maximum; 3.3 kQ end -of -line resistor per circuit Alarm Current 75 mA maximum Initiating Device Output Voltage 28 VDC maximum Circuits (IDCs) Capacity Each IDC supports up to 30 detectors (smoke or electronic heat) and manual stations as required; wiring distance is limited to 50 S2 maximum Application For Manual Release, Abort Switches, or Supervisory functions only; not for detectors; wiring distance is limited to 50 0 maximum Special Purpose For Dual Hazard Dual Hazard Application Abort Switches require a current limiting resistor of 1.2 kf2, Monitoring Circuits Applications 1 W, or an external Abort Supervision Module per SPM (SPMs) Supervisory 6 mA; 3.3 kQ end -of -line resistor per circuit Activated 75 mA maximum Output Voltage 28 VDC maximum Special Application appliance rating = 2 A maximum on a NAC NOTE: Special Application appliance rating = full 3 A power supply rating Alarm Current Notification Regulated 24 DC appliance power = 1.5 A maximum on a circuit Appliance Circuits NOTE: Regulated 24 DC strobe load = 1.35 A maximum total for power supply (NACs) Output Voltage Alarm = 26 VDC max.; supervisory = 29 VDC maximum; 10 kQ end -of -line resistor Synchronized Requires NAC dedicated to strobe control with non -coded output; use an external Strobe Operation Synch Module (4905 -9914, Class A, or 4905 -9922, Class B, see data sheet S4905 -0003 for details); up to 33 strobes can be synchronized per 4004R Notification Special Application Simplex 4901, 4903, and 4904 Series horns, strobes, and 4 -wire horn /strobes; Appliance Appliances (contact your Simplex product representative for compatible appliances) Reference Regulated 24 DC Power for other appliances listed to UL Standard 1971 or UL Standard 464; use Appliances associated external synchronization modules where required Release Appliance Output Current 2 A maximum per circuit Circuits (RACs) Output Voltage Activated = 26 VDC maximum; non -alarm = 29 VDC maximum; 10 kL end -of -line resistor Auxiliary Power Output; for Special Two outputs are available, continuous operation or resettable operation; combined Application loads only output is 750 mA maximum; output voltage = 19.25 to 27 VDC Auxiliary Relay Outputs Contacts rated 2 A @ 30 VDC, 0.35 p.f., inductive, selectable as N.O. or N.C. by (Trouble, Aux Relay 2, Aux Relay 3) jumper Wiring Connections for Above Circuits and Terminals rated for 18 AWG to 12 AWG (0.82 mm to 3.31 mm ) AC Input Auxiliary:Module .Ratings Class A Adapter Module 4004 -9684 Two circuits per module, rated same as circuits; not applicable to RACs (no additional current required) Relay Type Four relays with two outputs per relay; individually selectable as N.O. or N.C. AC Ratings 7 A @ 120 VAC, resistive Auxiliary Relay Module DC Ratings 5 A @ 30 VDC, 0.35 power factor, inductive 4004 -9860 Module Current 12 mA standby; 70 mA with all four relays energized; @ 24 VDC Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm to 3.31 mm ) 2081 - 9046 -Coil Supervision.Module'and -9048 Abort. Supervision'Module ;(see - page.? :for additional details) Construction Epoxy encapsulated Dimensions 1 -3/8" W x 2- 7/16" L x 1- 1/16" H (34 mm x 62 mm x 27 mm) Wiring 18 AWG (0.82 mm wire leads, color coded Coil Supervision Module Current Rating 2 A maximum; internally fused at 3 A, non - replaceable Abort Supervision Module Resistance 560 0, 1/2 W Environmental Ratings • . Operating Temperature Range 32° to 120 °F (0° to 49° C) Operating Humidity Range up to 93% RH, non - condensing @ 100.4° F (38° C) maximum 6 S4004- 0002 -2 5/2006 40413 SystemrC:01 eation :Reference O Listed /approved actuator or Deluge and Preaction Automatic Water Control Valve; one if 24 VDC (or 2 in series if 12 VDC) per RAC Actuator wiring -mss mill Coil Supervision Module junction box Yel Pi li Blk 2081 -9046 + Out - - + In - Abort Supervision Module 2081 -9048 Red Blk -° \, ^'p: (for dual hazard mode with non - current NI ■ limited devices on the SPM) - - - -- Maintenance Disconnect Switch ..- : I • • j- 24 VDC for Maintenance Disconnect 1 =- 1 , ' status indicator (if required) Optional 4905 -9914 or 4905 -9922 Synchronized Abort Switches Manual Release RAC 2 Flash Module (as required) Stations RAC 1 I- 11717 Wv__ 11111111111 llllliii 11111 11111ll11111 lfll Typical strobe only NAC NAC 1 SPM 1 SPM 2 , t _ .i'— IDC 1 Typical horn only NAC 7 „ ' Manual fire ` � NAC 2 - _. _ alarm station °a00 Ek, aekz,e rmt ii-i Compatible IDCs 2, 3, and 4 ` 1:11111{ li II,II 11.111111I1.ILi'•; detection devices 4004R Suppression Release Panel GENERAL WIRING NOTE: Optional 4001 -9811 - Wiring shown is for reference only, refer Meter Module • I Fes.: to specific installation instructions for detailed wiring information. NOTE: Locate within 3 ft Meter module cable (1 m) of 4004R cabinet (supplied with meter module) CompatibleULkListed5Valves and Actuators. : MFG: - M 'oBel'Number:_: <;; °," ' , , : _. , . , MFG: Model Number •° * AUTOMAN II -C Assembly (solenoid 17728; coil 25924) 8210A107 (097617 -005D coil) 1/2" NPS, 5/8" orifice, AUTOMAN II -C Explosion -Proof Releasing Device 24 VDC (solenoid 31492; coil 31438) 8210G207 (238310 coil) 1/2" NPS, 1/2" orifice * AUTOMAN II -C Assembly (solenoid 68739; coil 25924) ASCO 8211A107 (097617 -005D coil) 24VDC Solenoid Electric Actuator (solenoid 73111; coil 73097) HV2628571 (23810 coil) N.C. 1/2" NPS, 1/2" orifice ANSUL *CV90 HF Electric Actuator 73327 (may use 73606 in -line HV2648581 (23810 coil) N.O. 1/2" NPS, 1/2" orifice resistor) R8210A107 (097617 -005D coil) 1/2" NPS, 5/8" orifice LP CO2 w /ASCO solenoid 422934 T8210A107 (097617 -005D coil) 1/2" NPS, 5/8" orifice LP CO2 double action 24 VDC solenoid 430948 ECH Electrical Control Head (551201) Pyro- LP CO2 3 -way selector valve solenoid 433419 Chem Explosion -Proof Electric Actuator (570147) Electric Actuator 24 VDC solenoid 570537 Removable Electric Actuator (570209) 0.2 A 71395SN2ENJ1NOH111C2 (Skinner coil H111C2) 1/4 ", NPS, 1/16" 73212BN4TNOONOC111C2 (Skinner coil C111C2) 1/2 ", 5 -300 psi Skinner 73212BN4TNLVNOC322C2 (Skinner coil C322C2) 1/2 ", NPS, 0.92 A, 250 psi 73218BN4UNLVNOH111C2 (Skinner coil H111C2) 73218BN4UNLVNOC111C2 (Skinner coil C111C2) 1/2 ", NPS, 5/8 in. orifice Star Model D deluge valve, with solenoid 5550 Sprinkler * 12 VDC coils, either wire two in series for 24 VDC activation, or, if available from manufacturer, use series resistor 7 S4004- 0002 -2 5/2006 ,OV A'o ■rowed ; Water C,Qntr,O1 Values'; Group Manufacturer ModehNumber .. - Details A Skinner LV2LBX25* 24 VDC, 11 W, 458 mA. 1/2 inch NPS, 1/2 inch orifice T8210A107 B ASCO R8210A107 24 VDC, 16.8 W, 700 mA, 1/2 inch NPS, 5/8 inch orifice 8210A107 C Star Sprinkler 5550 24 VDC, part of Model D deluge valve D ASCO 8210G207 24 VDC, 10.6 W, 440 mA, 1/2 inch NPS, 1/2 inch orifice E Skinner 73218BN4UNLVNOC111C2* 24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice 73212BN4TNOONOC111C2 24 VDC, 10 W, 420 mA, 1/2 inch NPS. 5/8 inch orifice; 5 -300 psi F Skinner 73212BN4TNLVNOC322C2 24 VDC, 22 W, 1/2 inch NPS, 920 mA, 250 psi (1725 kPa), 1/2 inch orifice G Skinner 71395SN2ENJ1 NOH111C2 24 VDC, 10 W, 420 mA, 1/4 inch NPS, 1/16 inch orifice, 250 psi (1725 kPa) rated working pressure I Vitaulic Series 753 -E solenoid valve 24 VDC, 8.7 W, 12 inch NPS, 364 mA. 300 psi (2069 kPa), 12 inch orifice 11591 and 11592 Normally closed (NC) Explosion proof solenoid valves, 24 VDC, 10 W, J Viking 11595 and 11596 Normally open (NO) 12 inch NPS, 300 psi (2069 kPa), 4.1 Cv K Viking 11601 and 11602 NC solenoid valve, 24 VDC, 9 W, 12 inch NPS, 250 psi (1725 kPa), 6.2 Cv For new applications, LV2LBX25 has been replaced by model number 73218BN4UNLVNOC111 C2. 1Mountin. Referencelnformation k Box width 14 -5/8" (372 mm) vi (Top and side views are � Typical conduit entry area shown with door installed) l ;' ;���(cut holes as required) Box depth 4-1/4" (108 mm) It a 11 -1/4" (286 mm) I _- 1 l ® I8 8 8 0 Ec Class A adapter boards r aj Aux. relay 0 0 �• module t 0 a = a, a �IpMM M.,,Mq Door thickness ® all. r• 5/8" (16 mm) —j- m•'11 ' 0,11 Au r O M [ /� I?) 1 module 2 13 - 1/2" (Main board) ° = " ., 16" (343 mm) o'� _;�= � (406 mm) ^Io Ern .__CAC Input)4 o — -1 r Battery Area ® ` No conduit or wiring in this area, o l' `— ® 13-1/4" (337 mm) i (Front view module placement reference showing NOTE: For semi -flush mounting, cabinet mounting hole dimensions, optional Class A must extend 1 -1/2" (38 mm) adapter modules, and optional relay modules) minimum from wall surface . NOTE A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780. Tyco, Simplex, and the Simples logo are trademarks of Tyco International Services AG or its affiliates in the U.S and /or other countries. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA). �� Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4004- 0002 -2 5/2006 a www.tycosafetyproducts usa- wm.com ©2006 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shove were current as of document revision date and are subject to change without notice Simplex TrueMert Multi- Candela Notification Appliances UL, ULC Listed; FM Visible Notification Appliances with Horn and Synchronized and CSFM Approved* Flash; Non - Addressable, SmartSyncTM Operation Compatible Features =3 wl Audible /visible (AN) notification appliances with strobe, available for wall orc ceiling mount x enon t a F • Operation is compatible with ADA requirements (refers ; � to important installation information on page 3) b 1 VP, • Rugged, high impact, flame retardant thermoplastic" housings are available in red or white with clear lens Operates over a two -wire SmartSync circuit to provide: ua w - • Horns that are controlled separately from strobes on the same two wire circuit • "On until - silenced" and "on- until- reset" operation on ` i , ( the same two -wire pair • Horn control that can be selected to be temporal coded, _ march time coded, or on continuously _"I �= /f • Strobe appliances on the same circuit operating at a . 1/1 synchronized 1 Hz flash rate • Class B (Style Y) operation requires connection to a compatible SmartSync NAC or to SmartSync Control Wall and Ceiling Mount A/Vs • Module (SCM) 4905 -9938 Description' • Class A (Style Z) operation when connected to the 4905 -9938 SCM or with 4100U series fire alarm control Multi- Candela TrueAlert A/Vs with horn and panel NACs synchronized strobe provide convenient installation to standard electrical boxes. The enclosure designs are Wall mount A/Vs features: both impact and vandal resistant and provide a convenient • Wiring terminals are accessible from the front of the strobe intensity selection. Since each model can be housing providing easy access for installation, selected for strobe intensity output, on -site model inspection, and testing inventory is minimized and changes encountered during • Covers are available separately to convert housing color construction can be easily accommodated. Optional adapters and wire guards: Wall mount AN housings are a one -piece assembly (including lens) that mounts to a single or double gang, or • Wall mount AN adapters are available to cover surface 4" square standard electrical box. The cover can be mounted electrical boxes and to adapt to Simplex® quickly removed (a tool is required) and covers are 2975 -9145 boxes available separately for color conversion. • UL listed red wire guards are available for wall or ceiling mount ANs Ceiling mount ANs install using standard 4" electrical boxes. Color choice is determined by model number. Visible notification appliance (strobe): $trObeIntenSlty SeleCtlOn' • 24 VDC xenon strobe; intensity is selectable as 15, 30, 75, or 110 candela with visible selection jumper secured During installation, a selection plug at the back of the behind strobe housing housing determines the desired strobe intensity. An • UL. listed to Standard 1971 attached flag with black letters on a highly visible yellow background allows the selected intensity to be seen at the • Regulated circuit design ensures consistent flash output side of the strobe lens. and provides controlled inrush current * This product has been approved by the California State Fire Marshal (CSFM) pursuant to Audible notification appliance (horn): Section 13144.1 of the Califomia Health and Safety Code. See CSFM Listing 7125- 0026:317 for allowable values and /or conditions concerning material presented in this • Low current, 24 VDC electronic horn with harmonically document. It is subject to re- examination, revision, and possible cancellation. This product rich output sound suitable for either coded or steady was not approved by MEA (NYC) as of document revision date. Refer to page 2 for listing y status of wire guards. Additional listings may be applicable; contact your local Simplex operation product supplier for the latest status. Listings and approvals under Simplex Time Recorder • UL listed to Standard 464 Co. are the properly of Tyco Safety Products Westminster. " Simplex two -wire strobe synchronization operation is protected by U.S. patent No. 5,559,492 and SmartSync hom /strobe operation is protected under U.S. Patent No. 6281,789. S4906- 0002 -2 9/2004 Strobe.Application Selection4 SmartgynaT iiVireControl Proper selection of visible notification is dependent on SmartSync operation mode allows a two -wire circuit to occupancy, location, local codes, and proper applications provide the ability to activate both the horn and strobe on of: the National Fire Alarm Code (NFPA 72), ANSI the same NAC and then allow the horn to be silenced A117.1; the appropriate model building code: BOCA, while the strobe remains flashing. The horn operates as 1CBO, or SBCCI; and the application guidelines of the "on- until - silenced" while the strobe operation is Americans with Disabilities Act (ADA). "on- until - reset." Synchron,ized Strobes' SmartSyne Sources; Multiple Strobes. When multiple strobes and their • 4100U and 4010 Fire Alarm Control Panels (refer to reflections can be seen from one location, synchronized data sheet S4010 -0001 for details; refer to data sheet flashes reduce the probability of photo- sensitive reactions S4100 -0031 for basic 4100U information) as well as the annoyance and possible distraction of a 4009 IDNet NAC Extender (refer to data sheet random flashing.. The multi- candela strobes of these A/Vs S4009 -0002) are synchronized by the controlling SmartSync operation • SmartSync Control Module (SCM) 4905 -9938 (refer to NAC. data sheet S4905 -0003) Additional SmartSync compatible notification appliances include separate horns and combination { . horn/strobe notification appliances. ;Product Selectiont Multi- Candela ANs Model. Mounting Housing Color "FIRE "Lettering Description , 4906 -9127 Wall Red White 4906 -9129 White Red Horn with Multi - Candela Strobe; strobe intensity selectable as: 15, 30, 75, or 110 candela; operates with SmartSync two -wire 4906 -9128 Red White control Ceiling 4906 -9130 White Red Wall Mount AN Adapters Model;, _ " ' Description . . , . . . • • . -, Dimensions; , - 4905 -9937 Red Surface Mount Adapter Skirt; use to cover 1 -1/2" (38 mm) deep 5 -3/8" H x 5 -1/4" W x 1 -5/8" D - surface mounted boxes (136 mm x 133 mm x 41 mm) 4905 -9940 White depth with strobe = 4 -3/8" (111 mm) 4905-9931 Red Adapter Plate for mounting to Simplex 2975 -9145 box (typically for 8- 5/16" x 5 -3/4" x 0.060" Thick retrofit, may be mounted vertical or horizontal) (211 mm x 146 mm x 1.5 mm) 2975 -9145 Red Mounting Box, requires Adapter Plate 4905 -9931 7 -7/8" x 5 -1/8" x 2 -3/4" D (200 mm x 130 mm x 70 mm) SmartSync Control Module Modeb :.:Description '',, .., , , - "Dimensions 4905 9938 SmartSync Control Module with Class B or Class A output; mounts in 4" 4" x 4-1/8" x 1-1/4" D (102 mm) square box; refer to data sheet S4905 -0003 for details (102 mm x 105 mm x 32 mm) Replacement Covers for Wall Mount A/Vs Model ;, Description = Dimensions,. 4905 -9994 Red cover with white "FIRE" lettering 5 -1/8" H x 5" W x 1 -1/2" D 4905 -9995 White cover with red "FIRE" lettering (130 mm x 127 mm x 38 mm) Wire Guards and Ceiling Mount AN Adapter Model.' `D'escription _ .. ' - ;Dimen -• 4905 9961* Wall mount red wire guard with mounting plate, compatible with semi -flush 6- 1/16" H x 6- 1/16" W x 3 -1/8" D or surface mounted boxes (154 mm x 154 mm x 79 mm) 4905 -9927* Red Wire Guard for mounting to flush mounted electrical box 8-1/2" x 6-1/8" x 3" (216 mm x 156 mm x 76 mm) 4905 -9928" Ceiling Red Adapter Plate, required to mount guard to surface 9" x 7" Mount mounted electrical box (229 mm x 178 mm) 4905 -9915 White Surface Mount Adapter Box Extension, use to cover 4 -3/4" x 6 -7/8" x 1 -1/2" deep, 4905 -9916 Red 1 -1/2" deep surface mounted boxes (121 mm x 175 mm x 38 mm) * UL listed by Space Age Electronics Inc. 2 S4906- 0002 -2 9/2004 A/VIS'• ecificatlon s' Wall Mount or Ceiling Mount, Common Specifications Rated Voltage Range UL Listed Rating Regulated 24 VDC; see Note 1 below ULC Listed Rating 20 VDC to 30 VDC per ULC S526 -M878 Flash Rate and Synchronized NAC Loading 1 Hz; with up to 35 synchronized strobes maximum per NAC Environmental; Temperature and Humidity 32° to 122° F (0° to 50° C); 10% to 93 %, non - condensing at 100° F (38° C) Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm to 3.31 mm ; two wires per terminal for in /out wiring Horn Output Characteristics 2400 to 3700 Hz sweep, modulated at 120 Hz rate Voltage 16 VDC .24 VDC 33 VDC Sound Type (see Note 2) Steady Coded Steady Coded Steady Coded Horn Output Ratings @ 10 ft (3 m) Reverberant Chamber, 86 dBA 82 dBA 88 dBA 84 dBA 90 dBA 86 dBA UL 464 Test Anechoic Chamber 92 dBA 91 dBA 94 dBA 95 dBA 96 dBA 96 dBA Housing Dimensions (with lens) 5 -1/8" H x 5" W x 2 -3/4" D (130 mm x 127 mm x 70 mm) Wall Maximum RMS Current Rating per • 15 cd . . 30 cd - 75 cd 110.cd Strobe Setting (see Note 3 below) 75 mA 116 mA 221 mA 285 mA Mount Reference - RMS Currents "." ••.18 VDC. _70 mA - <' 101 mA ' 184'mA• 243.mA at other voltages:. , ,24 VDC ' 60 mA . . . 84 mA .143 mA ' . • 185,mA' Housing Dimensions (with lens) 4 -3/4 L" x 6 -7/8" W x 2 -5/8" D (121 mm x 175 mm x 67 mm) Maximum RMS Current Rating per 15 cd .- . - .30 cd' . -. - :. , 75'cd `..:. ' 110.cd ` ' " Ceiling Strobe Setting (see Note 3 below) 86 mA 132 mA 250 mA 320 mA Mount Reference'RM_ S'Currents : „. 18,VDC? ; :81 "mA'' a ., ""119mA'._ ' .216 :mA, 283 mA 6of her vol g ° ` to es�. ; .;:; .,: ` � . : .. 24 "VDC:' �. - ^� .70:mAr,_,. . : - 97 mA-) ° ' . '<_ °, '167 mk-^ ?;. : 21.7 mA 'Y-' NOTES: 1. "Regulated 24 VDC" refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices for the Hearing Impaired, changes effective May 1, 2004. This voltage range is the absolute operating range. Operation outside of this range may cause permanent damage to the appliance. Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on the NAC under worst case conditions. 2. Coded values are typical of the output measured with a Temporal coded or a March Time coded pulse and with a sound level meter reading on a "fast" setting. Under the same test conditions, coded horn output "peak" sound level readings are typically 4 dBA higher. 3. Currents are with horn on steady. The maximum RMS current listed is the device nameplate rating. Strobe designs are constant wattage and the maximum RMS current rating occurs at the lowest allowable operating voltage. (RMS is root mean square and refers to the effective value of a varying current waveform.) alnstaIIatikin Reference, - Surface or Semi,Flush Mounting O Mounting is compatible with ■ ( 1 0 ( 1 I IMPORTANT! WALL MOUNT single gang, double gang, and 4” (102 mm) square boxes, . INSTALLATION HEIGHT REFERENCE 1 -112" (38 mm) deep, by others _ X li _1 M I _I 7 _ • Bottom is of lens either even r 1T1 r with or slightly Electrical I 9 Y 0' ,� , ! E1D above bottom\ box outline Wiring access hole O � 5 i `' 1 • of compatible t ; ,_t boxes t ► Wiring terminals for I = a p , *� i I ; A y 1. S I martSync operation ii .• Mounting Holes. NFPA 72 requires 80" (2.03 m) 4" square (4) s -: = " I � that the entire lens minimum G " I ' Single gang (2) be not less than Vi � Double gang (3) 80" and not greater - 111110r than 96" above the finished floor Transparent housing and lens assembly • Intensity selection i r plug, accessible only + I from rear of housing; F 11 n E factory setting is 15 cd gal Removable cover Strobe intensity (tool required) viewing slot 3 S4906- 0002 -2 9/2004 1 Ce 11.66 6:40 N1and_ Guar 1- iiitallatW6,00erence1` Ceiling reference, 4" (102 mm) square box, Optional 4905 -9928 Adapter Plate, surface mounted box 1 -1/2" (38 mm) minimum depth required for surface mounted electrical box 1111/IMUll Four mounting clamps included, two each side \ 1 i ® :11-''''..." om X11 ■I ■MINI ■ ,® i■ It ,,7 eiling flush C mounted reference, box , I I_I�I�I■ r 1 . '',_ I_ Optional 4905 - 9915/ -9916 Adapter, recommended for surface mounted box – — , Optional 4905 -9927 4 t T r . ` Wiring terminals are ( located behind the housing Red Wire Guard 1 \ IF - J " End View I Strobe intensity viewing slot ME, ' – Intensity selection plug, accessible only from rear of lens housing; factory setting is 15 cd WON,741nt Installation Reference, giterRiatelpuarckand A da p ter Surface Mounting Reference /2975 - 9145 Box with Optional Adapter Skirt / ` <- ' / and Optional Wire Guard l 1 n Surface mount conduit and O ill box shown for reference ' '''''.. 1 . 1 LILI.M 4" (102 mm) square 11Il _1i , i ....mom ' box profile, 1 -1/2" ` ``7 II (38 mm) deep 7 I,F�® ■i = - - =: -1 I I• inn � 0 Optional 44 �� fi { . . 11 O O I 4905 -9961 D ON ■ 7, ,..../..„ AN Wire Guard Li I 0 �` 0 i�G3G _ _ T / 4905 -9931 Adapter Plate Optional Surface Mount Adapter Skirt, O ) 4905 -9961 Optional Wire Guard 1 -1/2" deep: 4905 -9937, Red; (shown here for reference only, 4905 -9940, White (conduit knockouts 4905 -9931 Adapter Plate can be used on other mounting options) are provided on all four sides) Tvco, Simplex. the Simplex logo, IDNet, TrueAlert. and SmartSvnc are trademarks of Tvco International AG or its affiliates in the U.S. and /or other countries NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA). Si PleX Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4906-0002-2 9/2004 www.tycosafetyproducts-usa-wm.com 2004 Tiro Safety Products Westminster All rights reserved All specifications and other infuriation shown were currtmt as ofdocument revision date and are subject to change litthout nonce � Simplex True /Wert Multi - Candela Notification Appliances UL, ULC Listed; FM Visible Notification Appliances with Synchronized Flash; and CSFM Approved* Non - Addressable, SmartSyncTM Operation Compatible Features,;; Visible only (V /O) 24 VDC notification appliances with high output xenon strobe, available for wall or ceiling mount: Ar :.;.. • UL listed to Standard 1971 6 77 acs. Y. « .. " ` t,v:'�,' ;zC.+.,'x• ,�.mJ'a:' _ • Intensity is selectable as 15, 30, 75, or 1 1 0 candela with visible selection jumper secured behind strobe housing 4 -- a • Operation is compatible with ADA requirements (refer :.`* f ' to important installation information on page 3) • Polarized input allows connection to compatible reverse polarity, supervised notification appliance circuit (NAC) Wall Mount Strobes • Regulated circuit design ensures consistent flash output 04 and provides controlled inrush current • Rugged, high impact, flame retardant thermoplastic i - - -• - -- -- - - -r housings are available in red or white with clear lens Strobes provide synchronized flash for use with: • 4010 Series and 4100U Series fire alarm control panels Ceiling Mount Strobes with NACs selected to provide strobe synchronization or SmartSync two -wire control ** ib.eSCIi .tlollfm • 4009 IDNetTM NAC Extenders Multi - Candela TrueAlert synchronized strobes • Separate strobe Synchronization Modules that are provide convenient installation to standard electrical available for Class B or Class A operation boxes. The enclosure designs are both impact and vandal • Separate SmartSync Control Modules (SCMs) that resistant and provide a convenient strobe intensity provide Class B or Class A output from conventional selection. Since each model can be selected for intensity NAC inputs output, on -site model inventory is minimized and changes encountered during construction can be easily Strobe housings provides flexible, easy, and accommodated. convenient semi -flush or surface wall mounting: Wall mount strobe housings are a one -piece assembly • Rear of housing does not extend into box (including lens) that mounts to a single or double gang, or • Wall mount strobes easily mount to single gang, double 4" square standard electrical box. The cover can be gang, or 4 -inch square outlet box quickly removed (a tool is required) and covers are • Ceiling mount strobes mount to single gang boxes available separately for color conversion. Wall mount strobe features: Ceiling mount strobes install using standard single gang electrical boxes. Color choice is determined by model • Wiring terminals are accessible from the front of the number. housing providing easy access for installation, inspection, and testing Strobe'Intenslty AeleCtlon • Covers are available separately to convert housing color During installation, a selection plug at the back of the Optional adapters and wire guards: housing determines the desired strobe intensity. An attached flag with black letters on a highly visible yellow • Wall mount strobe adapters are available to cover background allows the selected intensity to be seen at the surface mounted electrical boxes and to adapt to side of the strobe lens. Simplex 2975 -9145 boxes 5 ,� ,. , .0010. efer �en • UL listed red wire guards are available for wall or Strobe AppllCaee"- ceiling mount strobes Proper selection of visible notification is dependent on occupancy, location, local codes, and proper applications • This product has been approved by the California State Fire Marshal (CSFM) pursuant to of: the National Fire Alarm Code (NFPA 72), ANSI Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7125- 0026:316 for allowable values and /or conditions concerning material presented in A117.1; the appropriate model building code: BOCA, • this document. It is subject to re- examination, revision, and possible cancellation. This ICBO, or SBCCI; and the application guidelines of the , product was not approved by (NYC) as of document revision date Refer to page 2 for Americans with Disabilities Act (ADA). listing status of wire guards. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time ** Two-wire strobe synchronization operation is protected by U.S. Patent No 5,559,492; Recorder Co. are the property of Tyco Safety Products Westminster. SmartSync horn /strobe operation is protected under U.S. Patent No. 6,281,789; strobe designs are also protected under U.S Patent Nos. 5,886,620; 5,622,427; and 5,865,527. S4906- 0001 -1 8/2004 S richronied Strobes SmartSyncControl Sources Multiple Strobes. When multiple strobes and their Class B Smart Sync two -wire control is available reflections can be seen from one location, synchronized from: flashes reduce the probability of photo- sensitive reactions • 41000 and 4010 Fire Alarm Control Panels; 4010 as well as the annoyance and possible distraction of panels require operating software Revision 2.X or random flashing. These multi - candela strobes are higher (refer to data sheet S4010 -0001 for details; refer synchronized over a two -wire circuit when connected to to data sheet S4100 -0031 for basic 4] OOU information) compatible NACs, to compatible Synchronized Flash Modules, or to SmartSync Control Modules. • 4009 IDNet NAC Extender, models 4009 -9201 and 4009 -9301 (refer to data sheet S4009 -0002) SmaitSyricT - WIrB C011tr01 o SmartSync Control Module (SCM) 4905 converts separate conventional horn and strobe NAC Some applications desire the audible notification inputs into a SmartSync NAC output; up to eight SCMs appliances to be capable of being silenced before the can be synchronized to each other alarm condition is reset (on- until - silenced) while the visible notification appliances are kept activated until the Class A SmartSync two -wire control is available alarm condition is reset (on- until - reset). SmartSync from 4100U NACs and from the 4905 -9938 SCM. operation mode provides this function using a single Additional SmartSync compatible notification circuit (two -wire operation). appliances include separate horns and combination horn/strobe notification appliances. P Multi- Candela Visible Notification Appliances (Strobes) Model Mounting Housing Color "FIRE" Lettering Description 4906 -9101 Wall Red White 4906 -9103 White Red Multi- candela strobe with intensity selectable as: 15, 30, 75, or 110 candela; synchronized flash rate; 4906 -9102 Red White Ceiling SmartSync two wire control compatible 4906 -9104 . White Red Wall Mount Strobe Adapters Model -, .Description Dimensions 4905 -9937 Red Surface Mount Adapter Skirt; use to cover 1 -1/2" (38 mm) 5 -3/8" H x 5 -1/4" W x 1 -5/8" D (136 mm x 133 mm x 41 mm) 4905-9940 White deep surface mounted boxes Total depth with strobe = 4 -3/8" (111 mm) 4905-9931 Red Adapter Plate for mounting to Simplex 2975 -9145 box (typically for 8- 5/16" x 5 -3/4" x 0.060" Thick retrofit, may be mounted vertical or horizontal) (211 mm x 146 mm x 1.5 mm) 2975 -9145 Red Mounting Box, requires Adapter Plate 4905 -9931 7 -7/8" x 5-1/8" x 2 -3/4" D (200 mm x 130 mm x 70 mm) Ceiling Mount Strobe Adapter Model - • Description , Dimensions 4905-9910 Surface Mount Adapter Plate; zinc plated; required for mounting to 4 -7/8" x 3 -1/8" x 0.060" D handy box; not needed when using 4905 -9926 guard (124 mm x 79 mm x 1.5) Synchronization Modules (refer to data sheet S4905 -0003 for additional information) Model Description z i- ' ti • Dimensions - • 4905 -9914 Class B Synchronized Flash Module; epoxy encapsulated with 1 -3/8" x 2-7/16" x 13/16" in /out 18 AWG (0.82 mm) wire leads, rated for 2 A NAC, (35 mm x 62 mm x 20 mm) 4905 -9922 Class A requires 10 mA for power 4905 9938 SmartSync Control Module with Class B or Class A output; mounts in 4" x 4 -1/8" x 1 -1/4" D 4" (102 mm) square box (102 mm x 105 mm x 32 mm) Replacement Covers and Guards Model - Description , , Dimension 4905 -9992 Red cover with white "FIRE" lettering 5 -1/8" H x 5" W x 1 -1/2" D For Wall mount strobes 4905 -9993 White cover with red "FIRE" lettering ( 130 mm x 127 mm x 38 mm) 4905-9961* Wall mount 6- 1/16" H x 6- 1/16" W x 3 -1/8" D Red wire guard with mounting plate, compatible with (154 mm x 154 mm x 79 mm) semi -flush or surface mounted boxes 6 -1/8" x 4 -3/8" x 2 -7/8" deep 4905 -9926* Ceiling mount (156 mm x 111 mm x 73 mm) * UL listed by Space Age Electronics Inc. 2 S4906- 0001 -1 8/2004 • Strobe Specifications; Wall Mount or Ceiling Mount, Common Specifications Rated Voltage Range UL Listed Rating Regulated 24 VDC; see Note 1 below ULC Listed Rating 20 VDC to 30 VDC per ULC S526 -M878 Flash Rate 1 Hz Synchronized NAC Loading Up to 35 synchronized strobes maximum per NAC Temperature Range 32° to 122° F (0° to 50° C) Humidity Range 10% to 93 %, non - condensing at 100° F (38° C) Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm to 3.31 mm two wires per terminal for in /out wiring Housing Dimensions (with lens) 5 -1/8" H x 5" W x 2 -3/4" D (130 mm x 127 mm x 70 mm) Wall Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Strobe Setting (see Note 2 below) 60 mA 94 mA 186 mA 252 mA Mount . Reference RMS Currents 18 VDC 55.mA 85 mA 169 mA • 226 mA at other voltages 24.VDC 41 mA. 63 mA . '123 mA • . • 164 'MA Housing Dimensions (with lens) 4 -3/4" L x 2- 5/16" W x 2 -5/8" D (121 mm x 75 mm x 67 mm) Maximum RMS Current Rating per , • 15.cd ' 30 cd . 75 cd 110 cd ' Ceiling Strobe Setting (see Note 2 below) 75 mA 125 mA 233 mA 316 mA Mount Reference RMS Currents' ' 18'VDC , 64.mA: ..102 mA , • • 199.mA'7 : 266 mA .. . at other voltages , ,. : '. 24•VDC •.:: :. , 49.mA ".` 76 mA. • , ^ 146 mA 195 mA NOTES: 1. "Regulated 24 VDC" refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices for the Hearing Impaired, changes effective May 1, 2004. This voltage range is the absolute operating range. Operation outside of this range may cause permanent damage to the strobe. Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on the NAC under worst case conditions. 2. The maximum RMS current listed is the device nameplate rating. Strobe designs are constant wattage and the maximum RMS current rating occurs at the lowest allowable operating voltage. (RMS is root mean square and refers to the effective value of a varying current waveform.) . Installation Refetenee; *Surfacelor SemlFiushMall "Mounting; 0 7 Mounting is compatible with 91 0 ( 1 0 single gang, double gang, and 4" (102 mm) square boxes, r . T .A. 1 -1/2" (38 mm) deep, by others _ �1� _ ' ._ .�� _ IMPORTANT! WALL MOUNT IIIIIIPA • INSTALLATION HEIGHT REFERENCE r i Bottom of lens I O is either even Q lli ` ' with, or slightly Electrical Wiring access hole r � �� above bottom box outline � of compatible 1:'b i in � Wiring terminals I $ ° ® • � II boxes i, �� Mounting Holes: I ; ;' �., 4" square (4) NFPA 72 requires 80" (2.03 m) vrmmaoomPU onrosOma , �J?�n'� , ; .1. .:-' Single gang (2) that the entire lens minimum i, Double gang (3) be not less than I �/� 80" and not greater than 96" above the Transparent housing finished floor and lens assembly Intensity selection plug, accessible only frill ® . . from rear of housing; F 11 E factory setting is 15 cd Removable cover Strobe intensity (tool required) viewing slot 3 S4906- 0001 -1 8/2004 ite l n •` illit,St6obe lnstallafion Reference j Handy box, 1 -1/2" (38 mm) deep Single gang box (Wiremold (RACO 650 or equal) or single gang V5744S) 2-1/4" (57 mm) box, 2 -1/2" (64 mm) deep (RACO 519 deep, supplied by others or equal) supplied by others Also can be attached to boxes /'/ mounted to drop ceiling T -bar with clips (ERICO No, 512 or equal) 0 0 Q 4905 -9910 Adapter Plate, required for surface mount with handy box unless v o using the 4905 -9926 wire guard I - I I ° I -. -- -- - .. -- Ceiling mount strobe flat F Optional 4905 -9926 wire guard �i O �� ='�,i� ,I� with mounting plate - ► i. {., -�„ � Strobe i;urger ty , viewing of lens t housing; factory setting is 15 cd WallSMount4lnsta11ation ,Adapter Plate Guard,µand AdapterSkinrt Surface Mounting Reference 2975 - 9145 Box with Optional Adapter Skirt and Optional Wire Guard . Surface mount conduit and O 11111 . box shown for reference � 4" (102 mm) square ���I , , 1i7i1�I =ISIIM i II °-.-� 1 box profile, 1 -1/2" r -- ` (��11�1�1���1�11 , It I ii ' (38 mm) deep s illI= Optional t �' /I�I-1-I-� =� ' O O I 4905 -9961 —W ■ / i I • Wire Guard .1�u Strobe l� 4 FORE L �.� I, 4905 -9931 Adapter Plate �` �• — r =, Optional Surface Mount Adapter Skirt, O 4905 -9961 Optional Wire Guard 1 -1/2" deep: 4905 -9937, Red; (shown here for reference only, 4905 -9940, White (conduit knockouts 4905 -9931 Adapter Plate can be used on other mounting options) are provided on all four sides) Tyco. Simplex, the Simplex logo. IDNet. TrueAlert, and SmartSvnc are trademarks of Tyro International AG or its affiliates in the U.S. and /or other countries. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA) le Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4906- 0001 -1 8/2004 e www. tycosafetyproducts- usa -wm. coo O 2004 Two Safety Products Westminster All right, reserved. All specifications and other information shown were ci as of document revision date and are subject to change without notice aSiMpleX System Accessories UL Listed* 4081 Series End -of -Line Resistor Harnesses :Features For use as Class B end -of -line resistor:., , • Connect these resistor harnesses where end -of -line resistors are required at remote locations to monitor wiring continuity • Refer to specific circuit specifications for end -of -line resistor requirements UL Listed to Standard 864 Product ;Selection - 9 - 1/2" (241 mm) ko- 4 Model Reference Description** Number :YF ^ 4081 -9001 733 -892 2.2 kQ, 1/2 W 4081-9002 733-893 3.3 kS2, 1 W k; `f . „ 4081 -9003 733 -896 4.7 kt2, 1/2 W 4081 -9004 733 -886 6.8 kS2, 1/2 W 4081 -9005 733 -984 1.8 kS2, 1/2 W :j 4081 -9006 733 -890 560 S2, 1 W z =t 4081 -9007 733 -891 1.2 kS2, 1 W 4081 -9008 733 -894 10 kS2, 1/2 W 4081 -9009 733 -912 20 S2, 1 W 4081 -9010 733 -973 1 kQ, 1 W 4081 -9011 733 -974 100 S2, 1/2 W 4081 -9012 733 -985 22 kS2, 1/2 W Typical 4081 Series Resistor Harness Assembly 4081 -9013 734 -086 4.99 kS2, 1/2 W, ± 1% (full size except for lead length) 4081 -9014 734 -092 2.4 kO., 1/2 W 4081 -9015 734 -093 1.5 kt2, 1/2 W 4081 -9016 734 -149 150 kf2, 1/2 1/2W '" a e ` "' �� ,S • ecificationsx 4081 -9017 734 -171 3.9 kfl, 1 W 4081-9018 734-168 10 kS2, 1 W Overall Length Approximately 9 -1/2" (241 mm) Wire Length 7" (178 mm) ± 1" (25 mm) "* ± 5% tolerance except as noted. 2 Wire Size 18 AWG (0.82 mm 2 ) Insulation 600 V, black Leads Stripped 0.5" (13 mm); tinned Resistor Resistor leads are crimped to wires Attachment and covered with heat shrink tubing • This product was not approved by ULC, FM, MEA (NYC), or CSFM as of document revision date Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. S4081 -0003 7/2004 • Tyco, Simplex, and the Simplex logo are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries Simplex Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4081 -0003 7/2004 a www.tycosafetyproducts-usa-wm.com © 2004 Two Safety Products Westminster .411 rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without nonce