Loading...
Plans N . 4 ° 6 — cna78 / oao Sod GV nG. 140( 7• tqco / Fire & Building Products RECEIVED Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 JUL 0 6 MU n F CITY OF Series RFII — 5.6 K- factor BUILDING DIV IS ION "Royal Flush Il" Pendent Concealed Sprinklers Quick & Standard Response, Standard Coverage General Cap. The Protective Cap is temporarily removed for installation, and then it Description can be replaced to help protect the - sprinkler while the ceiling is being in „ stalled or finished. The tip of the Pro- f� _ s' The Series RFII Quick Response tective Cap can also be used to mark (3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently II” Concealed Pendent Sprinklers are pushing the ceiling product against the � t.,. decorative sprinklers featuring a flat Protective Cap. When the ceiling in : , c plate designed to conceal the stallation is complete the Protective t �� sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate 0,-: �` , W. `' Y Assembly installed 4'4 � ' ' ! ;', tecturally 1 sensitive areas such as hotel y 0 = „� lobbies, office buildings, churches, As an option, the Series RFII Standard and restaurants. Response (5 mm bulb) "Royal Flush II" Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175 erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM. The separable two -piece design of the intended for sensitive areas where it is Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical blies allows installation of the sprin- through the cover plate from the area klers and pressure testing of the fire above the ceiling. Data protection system prior to installation WARNINGS of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII of the finish coating to a fixed ceiling. PA They also permit removal of sus Sprinklers described herein must be UL and C -UL Listed. FM Approved. pended ceiling panels for access to installed and maintained in compli- NYC under MEA 353 -01 -E. LPCB (Ref. building service equipment without ance with this document, as well as No. 094a/09 for TY3551 & 094a/10 for having to first shut down the fire pro- with the applicable standards of the TY3531) Approved. tection system and remove sprinklers. National Fire Protection Association, The approvals apply only to the serv- Also, the se arable two iece desi n in addition to the standards of any ice conditions indicated in the Design of the the Sprink provides for g2 other authorities having jurisdiction. Criteria section and maximum pres- inch (12,7 mm) of vertical adjustment, Failure to do so may impair the per sure ratings indicated in the formance of these devices. Model/Sprinkler Identification Num- to reduce the accuracy to which the The owner is responsible for maintain- bers section. length of fixed pipe drops to the sprin- P klers must be cut. ing their fire protection system and de- Approvals for Air & Dust Seal vices in proper operating condition. Part #10908100 The Series RFII Sprinklers are The installing contractor or sprinkler U L and C -UL Lis for use with the shipped with a Disposable Protective manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re- with any questions. sponse Concealed Sprinkler. IMPORTANT Temperature Ratings Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate WARNING" that provides cautions Identification Discharge Coefficient with respect to handling and instal- K = 5.6 GPM /ps (80,6 LPM /bar lation of sprinkler systems and corn- Numbers Adjustment ponents. Improper handling and in- 1/2 inch (12,7 mm) stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm Plated, or White Painted (Custom paint it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by matches and colors other than white are available on request.) Page 1 of 4 JULY, 2004 TFP181