Correspondence September 21, 2006 ,1
��
CITY OF TIGARD
OREGON
Elite Care
Bill Reed
2300 SW 103
Portland, OR 97225
RE: GRANT STREET ELITE CARE— SITE REVIEW
Project Information
Building Permit SI T2006-00014 Construction Type: V -A
Tenant Name: Grant Street Elite Care Occupancy Type: SR-1
Address: 12353 SW Grant St. Occupant Load: 394
Area 31,72 9 sq ft Stories: 3
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition;
and the Tualatin Valley Fire & Rescue Fire & Life Safety Requirements based on the 2004 Oregon Fire
Code (OFC). The submitted plans are approved subject to the following.
1. Deferred submittals: Items which may be deferred include, but are not limited to, the following:
Raised floor systems, glazing systems, skylights wooden, steel, or composite floor or roof trusses,
suspended ceiling system, retaining walls, shelving systems and steel storage racks, stairway system etc,
will be charged a deferred submittal fee based on the valuation of the portion of the work being
deferred. The minimum fee shall be $200.00. This fee is in addition to the project plan review fee based
on the total project value. OAR 918- 050 -0150
Deferred Items: *Fire system design (FDC & riser line for sprinkler system)
Existing public fire service ends at property line. FDC line /valves shall be designed by NFPA
24 and NFPA 13. All piping shall be inspected prior to backfill.
* TVF&R FIRE FLOW and HYDRANT WORKSHEET- OFC Appendix B & TVF&R
• A. Approval of Fire Marshal John Dalby on following issues; All portions of the building are
required to be within 150 feet of Fire Apparatus Access Road. The new structure seem to
exceeds the distance. Clarify distance. OFC 503.1
• B. Information needed on the gates inclosing the access way from fire apparatus equipment and
clarify that gates meet the requirements of TVF&R and on the accessible rout to public way.
OFC 503.6 and OSSC 1008.2.
"Documents for deferred submittal items shall be submitted to the registered design professional in responsible charge who
shall review them and forward them to the building ofdal with a notation indicating that the deferred submittal documents
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
hate been reviewed and been found to be in general conformance to the design of the building. The deferred submittal items
the not be installed until the design and submittal documents have been approved by the building official OSSC Section
106.3.4.2"
EROSION
2. Erosion control measures shall be in place prior to excavation or grading.
ACCESSIBILITY
3. Accessible walkways and routes shall not exceed a running slope of 1 unit vertical in 20 units horizontal
(5% slope). Cross slopes shall not exceed 1 unit vertical in 50 units horizontal (2% slope).
4. Accessible parking spaces and access aisles shall be located on a surface with a slope not to exceed 1 unit
vertical in 50 units horizontal in all directions. 1104.43 OSSC
5. The accessible parking sign is required to be 84 inches to the bottom of the sign.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained
on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of
construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such
a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed City of
Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and
processing the documents.
Respectfully, ... i..,c.„." ,
Val Henzel,
Senior Plans Examiner
■
: . •
TIGARD
September 12, 2006
Elite Care
2300 SW 103`
Portland, OR 97225
RE: GRANT STREET F.LI'1'E CARE— SITE REVIEW #1
Project Information
Building Permit: SIT2006 -00014 Construction Type: V -A
Tenant Name: Grant Street Elite Care Occupancy Type: SR -1
Address: 12353 SW Grant St. Occupant Load: 394
Area: 31,279 ft Stories: 3
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition
and the Tualatin Valley Fire & Rescue Fire & Life Safety Requirements (TVF &R) based on the 2004
Oregon Fire Code (OFC). The following information is required in order to complete the review.
GENERAL. �O p
Z�
1. Provide the valuation for the site work portion of the project. Subtract the valuation of the site
plumbing work from the valuation for the applicable amount.
FIRE REVIEW
2. Complete the enclosed "TVF&R FIRE FLOW and HYDRANT WORKSHEET ". The allowable area
permitted and the number of hydrants required will be based on the worksheet. OFC Appendix B &
TVF &R # 19
3. Underground Fire Fighting Water Supply. Provide thrust blocking details including cut sheets
0 and installation instructions for any mechanical joint connections. Provide supply pipe burial depth,
piping sizes and materials, valve equipment cut sheets, vault details, equipment in vaults, details
t t J for hydrants and Fire Department Connection (FDC) location that are necessary for the installation
0 of the fire service. All valves shall be listed for use in a fire service application.
NFPA 24 section 4.1.3 for the items necessary for a plan review.
114 a
TIGARD
4.1.3 (13:8- 1.1.1) Working plans shall be drawn to an indicated scale on sheets of uniform size, with a
plan of each floor, and shall include the following items that pertain to the design of the system:
(1) The size and location of all water supplies
P i (2) The size and location of standpipe risers, hose outlets, hand hose, monitor nozzles, and related
1 equipment
�(3) The following items that pertain to private fire service mains:
1 a. Size
b � b. Length
el c. Location
V l� d. Weight
�+ e. Material
f. Point of connection to city main
g. Sizes, types, and locations of valves, valve indicators, regulators, meters, and valve pits
h. Depth at which the top of the pipe is laid below grade
(4) The following items that pertain to hydrants:
a. Size and location, including size and number of outlets and whether outlets are to be equipped
with independent gate valves.
b. Whether hose houses and equipment are to be provided, and by whom
c. Static and residual hydrants used in flow
(5) Size, location, and piping arrangement of fire department connections
4. Provide information on whether or not there is a fire department connection along with a fire line
located on property. OFC 503
Q All portions of the building are required to be within 150 feet of Fire Apparatus Access Road. The
south (the back of the building) side of the structure exceeds the distance. The Chief may modify
the distance when the building is provided with an Automatic Sprinkler System. I will be in contact
with John Dalby @ 503- 356 -4700 to discuss the issue. Call John if you have any questions.
OFC 503.1
0 Provide information on the gates inclosing the access way from fire apparatus equipment and clarify
that gates meet the requirements of TVF &R # 18 and for the gate across the accessible rout to public
way per OSSC 1008.2.
RETAINING WALLS / WALLS OSSC chapter 18
(7)Sheet C2A references a future perimeter wall and sends you to building plans for details. The building
' plans give no reference to this wall. Please provide perimeter wall information and details to be part of
the site plan this item can be a deferred item if stated as such.
0 Sheet C2A number 6 and 8 references 4 foot high walls please provide information and details on type
of walls.
Drainage for retaining walls shall be shown on the plans including the connection to an approved
point of discharge. Indicate piping slope, size, material and backwater valves if required by code.
1 , 4
TIGARD
ACCESSIBILITY
1 .-
Accessible parking sign shown on sheet C2A is required to be 84 inches to the bottom of the
sign. Please revise the detail.
Please provide an item - by - item response.
Deferred submittals such as Truss Joist Shop Drawings, Suspended ceiling system, Retaining wall design,
etc. will be charged a deferred submittal fee based on the valuation of the portion of the work being
deferred. The minimum fee shall be $200.00. This fee is in addition to the project plan review fee based on
the total project value. OAR 918- 050 -0150
"Documents for deferred submittal items shall be submitted to the registered design professional in responsible charge who
shall review them and forward them to the building official with a notation indicating that the deferred submittal documents
have been reviewed and been found to be in general conformance to the design of the building. The deferred submittal items
shall not be installed until the design and submittal documents have been approved by the building officiaL OSSC Section
106.3.4.2" Deferred Items: None Listed
When submitting revised drawings or additional information, please attach a copy of the enclosed City of
Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing
the documents.
Respectfully,
Val Henzel,
Senior Plans Examiner
Page 1 of 1
Val Henzel - TVF &R worksheets
From: "scoff" <palmhil12@mindspring.com>
To: "'Val Henzel"' <Val @tigard- or.gov>
Date: 9/21/2006 3:59 PM
Subject: TVF &R worksheets
CC: "'Mark Reed" <reed @stdairy.com >, "'Bill Reed ' <breed @oatfieldestates.com >,
<emily @stdairy.com >, <CPMARCH @aol.com >, "Scott Churchill"
<palmhi1l2 @mindspring.com>
Val,
I received a call from Bill Reed of WCR Company that the
TVF &R worksheet could not be found. Here are scanned copies of the
filed worksheets which I saved to my project file. I will send them as
.jpg files so that they can be easier to read.
Please feel free to contact me if you have any questions.
Regards,
Scott Churchill
file: / /C:\Documents and Settings \val.000\Local Settings \Temp \GW }00002.HTM 9/21/2006
Page 1 of 1
Val,
I received a call from Bill Reed of WCR Company that the
TVF &R worksheet could not be found. Here are scanned copies of the
filed worksheets which I saved to my project file. I will send them as
.jpg files so that they can be easier to read.
Please feel free to contact me if you have any questions.
Regards,
Scott Churchill