Specifications March 30, 2004 0f CITY OF TIGARD Clair Simmons Shaw West Company OREGON PO Box 1427 Tualatin, OR 97062 RE: SMOKE DETECTION/FIRE ALARM SYSTEM / s5 .s Building Permit: BUP2004 -00055 Construction Type: 11 -1HR Tenant Name: CFT Elementary Occupancy Type: E -1 Address: I - • _ • • - Occupant Load: 2480 Area: 67,749 Sq Ft Stories: 2 Sprinklers: In lieu of 1 HR Hazard: Ordinary Group The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. General requirements 1. A key box shall be installed within 20 feet of the main entrance. The bottom of the key box shall be not less than 8 feet nor more than 10 feet above the walking surface unless approved by the Fire Chief. 902.4.2 TVFR99 -01 An existing key box at the main building entrance is acceptable. 2. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the Fire Chief All functions of the system or alteration shall be tested. 1007.3.4.1 TVFR99 -01 3. The permittee shall provide written certification to the Fire Chief that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. 1007.3.4.2 TVFR99 -01. 4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL. Standard 10 -2, Section 1- 5.2.8.2, TVFR99 -01 Manual Fire Alarm activation devices shall be mounted in the following reach ranges: • Forward Reach - 15 inches to 48 inches above the floor. 1109.2.3.5 OSSC • Side Reach — 9 inches to 54 inches above the floor. 1109.2.3.6 OSSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Visuals (Section 1109.14 OSSC) 1. Visual signal appliances shall be provided in the building in each of the following areas: • Restrooms and any other general use area (e.g., meeting rooms) • Hallways • Lobbies • Common use areas. 2. Visual alarms shall be located not less than 80 inches and not more than 96 inches above the floor level. When a low ceiling exists, the visual alarm shall be mounted at least 6 inches below the ceiling. 3. Visual alarms shall have a minimum candela rating of 75 candelas. 4. No place in a room shall be more than 50 feet from a visual signal. 5. No place in a common corridors or hallways shall be more than 50 feet from a visual signal. 6. In large rooms exceeding 100 feet across and without obstructions 6 feet or more above the floor, devices may be placed around the perimeter spaced at a maximum of 100 feet apart. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing .•' Respectfully, / ian la Senior ' ans Examiner .. : , , , ... , ` Analog/Addressable Fire Alarm Control System IFP -1000 Intelligent - > Fire Panel The IFP-1000 is an intelligent analog/addressable fire control p an The 1. e M - basic IFP -1000 system has a single SLC loop, which can support 127 SLC APPROVED MAR 2004 2 4 devices, and can be expanded to 1016 points by adding 5815XL (127 �' (ITY F TIGARD points each) Signalling Line Circuit Expanders. The IFP -1000 has six on- . it Bl 1 IVISI()IV board FlexputTM circuits that can be configured for notification outputs, or '. N for conventional smoke detector (either Class A or Class B) inputs. The -,...:-4:',-7•i ,�® 429 - Vol. 9 control panel also has a built -in dual tine digital fire communicator, Form C _ __,,„:.:7 trouble rely ,. and two programmable Form C relays. firmware has - r •. relay, prig ys '`� ; it - _ -- werful features such as detector sensitivity, daylnight thresholds, drift t ,a °° ,,,. - _ r; ,.,�, ry compensation and pre- trouble maintenance alert. x k ' ' n i 7 'o-9- 9 9- 5 Other devices that can be added to the system are the RA -1000 Remote r : ' r .. ,, Annunciator, the Model 5824 SeriaUParallel Interface (for printing system 1 w° reports), and the RPS -1000 Intelligent Power Module. t !':,,:,:::f,,,;:.:,,-4, L A t y Features �` °. • Built -in support for 127 analog addressable points, expandable to 1016 r : analog addressable p mts. s m • Uses standard wire —no shielded or twisted pair required. , t � x • Built -in UL listed digital communicator for remote reporting of system f r ' r activity and system programming. _ %" -- i' • Central station reporting by Point or by Zone. • Supports Class B (Style 4) and Class A (Style 6) configuration for SLC and SBUS. • Distributed, intelligent power. yiett • Sensor sensitivity settings. : f r • Day /Night sensitivity setting. • Automatic drift compensation. 4 4fi, a ' s� . ` ` , s ' • FlexputTM I/O circuits_ Flexput circuits can be configured for notification = . , } outputs, or conventional smoke detector inputs. Notification circuits can . be configured as Class A (Style Z) or Class B (Style Y). 2- and 4 -wire r smoke detectors can be configured as Class A (Style D) or Class B • Acknowledge function allows operator to (Style B). keep track of event status. • Built -in annunciator with a backlit 80-character LCD display. • Jumpstart® auto - programming. • RS-485 bus provides communication to system accessories. • • Modular design. • Built -in RS -232 interface for programming via PC. • System can be uploaded or downloaded on • Built -in Form C trouble relay rated at 2.5 amps at 24 VDC. ` site or from a remote location with a PC - • Two built -in Form C programmable relays rated at 2.5 amps at 24 • Non volatile event history stores up to 1000 VDC. events. • Individual addressable devices can be tested. • 125 Software zones. • SLC device locator can be used to locate a single or multiple devices ' ^ 250 output groups. on a SLC loop. • 5 amp power supply and maximum • System automatically tests the addressable devices. charging capacity of 33 amp hours. (An • 13 preset notification cadence patterns including ANSI 3.41 and four additional cabinet enclosure is required for user programmable patterns. ( batteries in excess of 17 amp hours ) • Programmable to automatically display initial event first or display tally SLC Supports multiple Device types (See of system events. compatible addressable devices.) Any • Built -in synchronization for appliances from AMSECO,Gentexe. combination of addressable devices can be Faraday, and Wtleelock® used on a single SLC loop (up to a 127 devices) 7550 Meridian Curie PIN 350093E, 04/02 i -c SILENT b 753 49 6455 55369 -4927 Copyright ®2002 Silent Knight KNIGHT 1- 800 - 328 -0103 Flexput is a Trademark of Silent Knight y a Fax 763 -493 -7475 Jumpstart' is a Register Trademark of ,�' . k., . a hitp: //wnwafarenhytaom Silent Knight 4 , I See Cundiff Engineering's shop drawing review comments and l corrections noted on the enclosed documents. r t IF P-1000 FACP RPS -1000 +s 1 PA -1000 Mode15824 Model 5815XL r ro c r n ,w } e h £.a r:. RS -485 System a. i, 1 s t ti �jjJ - - =5 m , W ut `d. 3 v l Conventional r S v ? Bea pull Mayon Y l ,.a •x-- ti > Y ; r t 7 u �, a 4 ._: SLC Lapp � . °' '`' ' *r m . (2wxesl a t _ i Y ° ' x y�' SDdco -AS SD500 -A M SD500 -PMVfM S6500 -ARM t ^ i '`,,� . "?` ° .,(*w SO400•ANM _ .t # s "' :',, S s Max. I 27 dances pet SLC km, SD505- jock IF P-1000 supports up to 8 SLC loops ADH R or ADH SDSOS.APS SD505-AIS 80505-Al-IS Specifications System Troubles Electrical (Yellow) On when a trouble lectrical Specifications condition exists Primary AC: 230* / 120 VRMS CO System Silenced On when an alarm, 50 / 60 hz, 2.5A (Yellow) trouble or supervisory Total Accessory Load: 5 A@ 24 VDC condition has been 5 Amps Q 24 VDC of power - limited notification power silenced but not yet Standby Current: 140 mA cleared Alarm Current: 260 mA System Power (Green) On when power Battery Charging Capacity Up to 33 Ah systems are normal: "Order high voltage power supply version IFP- 1000HV flashes for AC or DC FlexputF Circuits failure Six programmable circuits which can be programmed Mechanical Specification individually as: Flush Mount 9 Notification Circuits: 3 amps of power- limited power per Dimensions: 14 -1/2 - W x 24-3/4 3 -7/8 "D circuit at 24 VDC. (36.8 W x 62.9 H x 9.8 D cm) Auxiliary Power Circuits: 3 amps of power- limited power Overall Dimensions: 16 -1/8"W x 26 -3/8 "H x 4 -1 /8 "D per circuit at 24 VDC. (40 -6 W x 67 H x 11.8 D cm) Initiation Circuit: 100 mA of power - limited power per Weight 28 lbs. (12.8 kg) circuit at 24 VDC. Color: Red Approvals Telephone Requirements: FCC Part 15 and UL Listing Part 68 approved NFPA 72 Central Station Remote Signalling Type of Jack: RJ31X (two required) Local Protective Signalling Systems Auxiliary Protected Premises Unit Water Deluge Releasing Service CSFM 7165-0559: 135 MEA 429 -92-E Vol. 9 FM Approved Indicator Lights General Alarm (Red) On for alarms Supervisory (Yellow) On when a supervisory condition exists SILENT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 1- 800 - 446 -6444 or in Minnesota 763-493-6435 - .,....._ . . iiireMSWASOKOMPISMAIWO s KNIGHT l ,. � M . F AX: 763 -493 -6475 - e World Wide Web: http:Nwww.farenhyt.com made in the USA i are, mom„ Two Form C contacts, 2.0A © 30 VDC or .6A @ 120 VAC y The SD500-ARM is an addressable device that adds two Form C contacts to the Farenhyt system. The contacts are ' - rated at 2.0 amps @ 30 VDC or .6 amp @ 120 VAC. The 429 - 92 - E, Vol_ 9 S0500 -ARM allows you to control a wide variety of normally APPROVED open and normally closed applications, including elevator recall, door closing, fan operation, and auxiliary notification. And, because the relay module is addressable, these applica- ,;" tions can be located at any point in the signaling line circuit. ; :r ' " • Two sets of Form C contacts. (Double pull/Double Throw relays) • Contacts are rated at 2A @ 30 VDC or .6A @ 120 VAC. • Up to 127 relays can be used on each SLC loop. • Relay programming is completely flexible —can be mapped to , zone conditions. j • Polling LED visible through cover plate. - \ • UL listed, complies with NFPA 72. I ., 6:1= to. }' • CSFM approved l - . 1 • MEA approved k .,. - • FM approved 1 `' J` `\\ Contact Rating: Form C 2A @ 30 VDC or .6A @ 120 VAC Standby Current: .55 mA Alarm Current: .55 mA Operating Temperature: 32°F to 120 °F (0 °C to 49 °C) - °° °� 4- 718 "H x 4- 718°�l x 1 °D ! See G Undit1" E=ryc- )- 19Cr1f 2 hop Dimensions: C rc'J4ti -i rc,v<if.:w ` r'`5t!1? ?rlt.., and 1 Mounting: 4 - square I con ec ran 5 :))pied nil the , en -,-, docuiTlent > 1 FP -1000 )FP -100 }� � g 7550 Meridian Circle ` -73,6,:i SILENT Maple Grove, MN 55369 -4927 1 L `t KNIGHT � 763 4936455 ( in Mfnneaota) PM 350219, 12/01 j ` u Fax 763 - 493 - 8475 ° : s a Copyright 0 2001 Silent Knight http:thavov farenhyt.com o . , . , arer Detects product of combustion - In addition to accurately detecting a smoldering fire, each SD505- APS photoelectric detector has a unique address, which is recognized by the FACP. F NI The SD505 -APS compensates automatically for contamination in the environment. Detector calibration testing is simple —even from a 429 -92 -E, Vol 9 APPROVED remote site. The SD505 -APS offers a low profile installation and uses the Model SD505 -6AB base, compatible with other detectors in the series, allowing for complete application and placement flexibility, Like other Farenhyt smoke detectors, the SD505 -APS * = „ offers easy installation, stable operation, RF/transient protection, , ,$ and vandal - resistant locking. O l'i ' , ..,, 8 ' L ,...: f` i • Low profile, 2 inches, including base • Simple and reliable addressing without mechanical switches „. • Automatic compensation for sensor contamination - IA Y V7 • Built -in fire test feature : ' � � - 4 � t • Simple detector calibration testing through the control panel or d a , r .t` 'f, ? .,,,,,,,,,„_,,,,,,-7,--:,,, . remotely through a WindowsTr” based computer. (Windows _ ` : x software required for remote testing.) _ $ - • Vandal- resistance locking features w- , • Field cleanable • UL listed, meets NFPA 72 Ch 7 requirements • CSFM Approved • MEA Approved • FM Approved Operating Voltage: 17-41 VDC See Cund,if Engineering's shop 1 Current Consumption: Standby: .55 mA drawing i'evike-.^i :... onir Tents and I Alarm: .55 mA correct!onE, noted on the 1 6 enclosed documents. 1 Operating Temperature: 32°F to 120 °F (0 °C to 49°C) - Relative Humidity: 85% noncondensing Sensitivity: 0.88% - 3.56% FT - Air Velocity: 0 - 300 FPM I 7550 Meridian ctrcte *'*` * SILENT le Grove, MN 55369 -4927 ' .'` 1- 800325-0103 } I GHT 783-493.6435 o Minnesotai PIN 350226, 12101 , c _ .&. 7,t Fax 763 - 493 - 647 5 Copyright ® 2001 Silent Knight Mlp:l vAwr.farenhyt.carn . ; . , . Fa Monitors Dry Contacts andard size (SD500 -A1M) and miniature (SD500 -11A1M) ;',: /SIM r The S0500 -AIM and SD500 -MIM are addressable input modules for use with the Farenhyt fire control panels. The SD500 -AIM and SD500 -MIM are designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm 429 -92-E, Vol. 9 F DR initiation devices. APPROVED The SD500 -AIM addressable input module mounts to a 4"- square box. The SD500 -MIM mini input module fits inside a single gang s. box. The modules are supervised, single input contact monitors. Using an EOL resistor, they monitor for alarm contact closures and ';s :, ..,. for open circuit wiring fault conditions. w C+4Np r • Operates on Class A (Style 6 & Style 7) or Class B (Style 4)SLC - ;___ _ _ ` Loop. • Single contact monitor. • Up to 127 modules per SLC loop. i _ , • SD500 -MIM mounts in a single gang box. , • SD500 -AIM mounts in a 4 "- square or double gang electrical box, and has an attractive :- i a_ _ n -» 11 ivory cover plate. i. -, 0 --°- =. • SD500- AIM/MIM are DIP switch programmable. 1,- _ -- ' ; • Accepts up to 14 gauge wire. • Both modules UL 864 listed; comply with NFPA 72 I " • 2500 ft max. wiring distance from input module to contact. • CSFM listed. So500 AIM • MEA 429 -92 -E, Vol. 9 • FM approved Operating Voltage: 24 VDCr K, l Standby Current: 0.55 mA Alarm Current: 0.55 mA S8500 -ADM Ambient Temperature: 32 °F to 120°F ..-v717: t ' f :: ` ' F " (0°C to 49 °C) IFP-1000 Mounting: SD- 500 -AIM: IFP -100 �� - m -- yw double - gang box or xs i S CUPdifl crigirneea ingg's shop 1 4° square electrical box di awing review comments and SD 500 - MIM: corrections doted on the i single -gang box ! enclosed documents. f g 7550 Mendian Circle ' SILENT Maple Grove, MN 55369 -4927 { �Y � ,' KNIGHT 763-493-6435 On Minnesota) P/N 350232, 11!01 I "� q ' m Fax 763 493 - 8475 Copyright ® 2001 Silent Knight . htip:f/wwwfarenhytcom Faren Pull Addressable ul flan • The SD500-PS is a single action addressable fire pull station, and the SD500 —PSDA is a dual action addressable fire pull station. The SD500- PSIPSDA feature rugged metal construction. A terminal ��I 429_92-E vol. s strip on back of the pull station allows interconnection of the putt station to the SLC loop of a Silent Knight analogfaddressab Ere . f . alarm control panel. The S0500- PSIPSDA is designed for indoor is use in non - explosive environments. The normally open initiating point contacts are gold - plated to avoid risk of corrosion. T h e SD500- PSIPSDA has been tested by UL for compliance to the £ requirements of the Americans with Disabilities ACT (ADA). • UL Listed 4 ` � r • CSFM listed p • ADA compliant • Key reset (Same key as Silent Knight enclosures) Y Y 9 • Surface mount back box available • Terminals - accept up to 14 gauge wire . • Extremely easy to operate � ;_ i v ���� • Corrosion - resistant gold - plated contacts. • Reflective label makes it easier to locate in low light . L s t x r � The SD500 -PS single action pull stations are operated by a pull on � _ =k the front pull cover of the station. The SD500 -PSDA dual action pull stations are operated by lifting up an access plate and then pulling forward on the front cover of the pull station. A plunger switch, • l z • wired to a self contained addressable module, i released as the pull station opens to initiate the alarm. Once operated, the cover Operating Voltage: 24VDC hangs down and can be seen up to 100 feet away. The pull station Standby Current: .55mA is reset by returning the front cover to the normal upright position Alarm Current: .55mA and relocking the station with a reset key. The reset keys are the Ambient same keys used on Silent Knight enclosures. Temperature: 32 °F to 120 °F The SD500- PSIPSDA includes a status LED which blinks, indicating (0 °C to 49 °C) that the addressable module is communicating with the loop. The Mounting: Single gang box status LED lights continuously during an alarm. A dip switch on the Optional Red Surface addressable module is used to set the unique address. Mount Box PS -SMBB Q . SD500 -LK Included with SD500- PSDA or it can be ordered separately and used to convert SD500 -PS to SD500 -PSDAs (See illustration on 7550 Meridian Cirde back page.) SILENT nr Maple Grove, Mn 55369 -4927 763. 493 -6455 KNIGHT 1- 800 - 328 -0103 P/N 350254, 09/02 j s g Fax 763-493-7475 Copynght © 2002 Silent Knight z ? httpJlwww.fanmhyt.com Sl?e Cur l c'.lt Engineering's shop t drawing ; €Vli-,V comments and corrections noted on the enclosed documents. Fa re n yt Provides detection of heat. wkl k3• r 4 The SD505 -AHS is a heat detector suited to virtually any commer- cial setting. The SD505- AHS'is an absolute temperature device. This means that it generates an alarm if the temperature goes above the trip point (programmed at the panel). The S0505 -AHS provides accurate temperature measurement data 429 -92 -E, Vol 9 to the fire alarm control panel This heat detector is particularly APPROVED suited to environments where smoke detectors cannot be used because of the presence of steam or cooking fumes, such as in a kitchen. • Low profile, 2 inches, including base • Absolute temperature device . + I • Simple and reliable addressing • Uses digital communication protocol • The SD505 -AHS is UL Listed and meets the requirements out - + �;;. �; lined in NFPA 72 Inspection Testing and Maintenance, Chapter 7. ; max • CFSM listed WRg.1.;:"- .'# 0 - • MEA listed ,';> ; ter; . r .. " • FM approved , _ . _ Operating Voltage: 17 to 41 VDC EZi kr•AAIAt Current Consumption: Alarm: .55 mA Standby: .55 mA Detection Temperature Range: 135 °F to 150°F (57°C to 65°C) Ambient Temperature: 32°F to 120°F aee 1 ..21 ii L e e rit,g shop (0°Cto49 °C) draw�nt. rP� °�:if t. ^,'''.:;�r ?3;t'lent^ and Mounting: 4 SQR, 4 OCT Single gang corrections noted on the ,nci0seo documents, mud ring m- Rated Spacing: 70' between sensors on smooth ceilings 7550 Mend en Circle SILENT Maple Grove, MN 55389 -4927 1-800- 328-0103 KNIGHT n3-493-6435 (in Minnesota) P/N 350230, 11/01 Fax 763 483.6175 Copyright © 2001 Silent Knight http://ww•v.facerrhyt.com 'i € ; �`"��� Adds up to 127 addressable , devices to the FACP 5815n , ll O .4 ,, The Model 5815XL SLC Expander is a signaling line circuit MEA controller for the Farenhyt IFP -1000 analog /addressable fire control panel. It allows you to add 127 addressable devices to the IFP -1000 - 429-92-E Vol. s FACP. Seven 5815XLs can be added to the IFP -1000 for a T maximum of 1016 addressable devices per face 5815XL signaling circuits have the same functionality as the SLC that is built into the FACP and support the same addressable devices as the main panel. The 5815XL connects to the panel via L' the RS 485 bus and is housed in the IFP -1000 or RPS -1000 :,:. �f cabinet. 11 ® W,._ • Adds 127 analog/addressable to the Farenhyt IFP -1000 system • Seven 5815XLs per system • 5815XL SLCs have same functionality as built -in, including Style 6 and 7 (Class A) configuration. _ r� 1 . • Communicates with the FACP via RS 485 system bus , , f �� rl �° G L E "' '' • LED indicates good communication * cc' '' d ', ,�` -} f ` • Housed inside IFP -1000 cabinet or remotely mounted inside the - - $' ` h -z RPS -1000 cabinet. :'i' . � � " _ � . ' ? ma y .. - y 1 • UL 864 listed, complies with NFPA 72 and 101 ='` f' "` g. Y ; w: ° ; "' . n 4 • CSFM Listed 1 • Communicates on most standard wiring systems - =4 _ 7 * uR • FM approved r 1.'.y , -1,a�` f System Capacity: IFP -1000 FACP supports seven 5815XL SLC Expanders. Each expander supports 127 addressable devices; IFP -1000 system supports 1016 devices total. total. See Cundi$i l nain ;enng's sho i drawing an.vio, commen and 1 Operating Voltage: 24 VDC } corrections noted on the i Current Consumption: 55 mA min. - 125 mA max. I enclosed documents. (standby and alarm) (with 127 devices) Ambient Temperature: 32 ° F to 120 °F (0 °C to 49 °C) Mounting: Inside IFP -1000 FACP or - RPS -1000 cabinet 7550 Meridian Circle q SILENT Ar� Maple Grove, MN 55360.4927 i P , ` . 1- 800 - 328.0103 I KNIGHT 612493 -6455 (in Minnesota) P/N 350211, 01/01 Fax: 612.493-6475 '� , Copyright co 2001 Silent Knight http://www.tarenhyt.com t { , t , Fa re n yt For Remote Annunciation RA-1000 Remote Annunciator The RA -1000 Remote Annunciator can be used to operate and pro- gram Farenhyt Fire Control Panel. The RA- 1000's keypad and dis- play match the built-in annunciator of the IFP -1000 control panel. The remote annunciator connects to the control panel via the RS- 485 system bus. When the system is in normal operation and has AC power, the Power LED is tit and all other LEDs are off. The i t, other LEDs turn on as alarms, supervisories, troubles, system ` silenced and AC power losses occur. APPROVED Features �I • 80- character backlit LCD display (4 lines with 20 characters each) • EA Tactile/audible feedback • Accepts user codes or fire fighter's key 429 -92 -E Vol. 9 • Larger keypad buttons for system Reset and Silence _ • RS-485 interface to panel • Can be flush- or surface mounted. Trim ring available for sur- face mounting. • Operation and appearance is identical to IFP -1000 built -in ;, annunciator _ p • Supports simultaneous use by multiple users from up to 8 sepa- Pp; rate RA -1000s • on -board piezo sounder audibly indicates alarms, troubles, and - ,. supervisories = • r; 4' ; ,4 r • Five Status LEDs for, alarms, supervisory, trouble, silence and AC power indications. • UL listed, complies with NFPA 72 • - CSFM approved • MEA approved • FM approved • Wiring lengths up to 6000 ft. from the control panel Specifications Dimensions: Height 7-3/8" (18.73 cm) Width: 9-1/8° (23.18 cm) Operating Voltage: 24 VDC Depth: 1 -1/2° (3.81 cm) Standby Current: 20 mA Colors: Lt. Gray (RA -1000) Alarm Current 25 mA Red (RA-1000R) Maximum Per System: 8 Compatible Operating Temperature: 32° F to 120 F (0° C to 49° C) FACPs: IFP -1000 IFP -100 Mounting: Surface or Flush Wiring Distance: Up to 6,000 feet from control panel (depending on wiring method) � 7550 Meridian Circle z 80446 -6444 SILENT Maple Greve, Mn 55369 -4927 P/N 350071, 11/01 IGHT 76 -6435 Copyright ID 2001 Silent Knight http: //www.farenhyt.com Fax: 763-493-6475 I Sege Cundiff Erigineerinyc shop drawing review comments and corrections noted on the I enclosed documents. .9: :,,i527,:,:,,,::, rd: 4. ! S. b faz.,. &",' 7 3 i,� L;(;' -, � ,ma " 'r •u-'> { y, s . • '' -k '( n- -§.,.2 +. t'ti ,� r �: e •" �,y 't� a t ' b £ e - in .. ' + t xr; 4 w , S '.+# to ` '� a' i4 ;...'... " .:.�.i a ''' '' ' : i ` .. i� t! s;. a, 'A-2, :,, x Commander Series Selectable Candela Evacuation Signals Applications The Commander Series is a low the factory on the temporal lower profile strobe or horn /strobe frequency mode and it comes combination that offers dependable standard with a rugged cast metal audible and visual alarms and the mounting plate. lowest current available. The Commander has a minimal operation current and has a minimum �',, " . The GE3 Series offers field ; selectable candela options of 15, 30, flash rate of 1Hz regardless of input � ,�r Y *� , , , p voltage. . ` ti, =r = .:. �' . � 7 `` 60, 75, and 110 candela. The Commander Series comes t "''' * '4,S3; 3 €; :.‘4, r The Commander Series horns standard with the 4" mounting plate ° , F - ;' 3 . �, � t , offer a new synchable chime and which incorporates the popular �. Y ri : , i- ,, .( iii whoop tone and provide a selection "Supersliderw feature that allows you , r : ) I of high or low dBA as well as a to easily test for supervision. Also , r , ' _ _ � ' . selection of a 2400 Hz ( rem inclu is a locking mechanism .�k. �� - , ' �=_ ��� signaling) or a low frequency broad which secures the product to the band 1500- 3000Hz mechanical bracket without any crews showing GFS3 GEC3 sounding (evacuation) tone where The Commander (GE3 Series) doors could be a problem. appliances are UL 464 and UL 1971, The GE3 Series are easily field listed for use with fire protective changeable from temporal 3 to a systems and are warranted for three continuous tone by simply removing a years from date of purchase. jumper. The GEC3 is shipped from Standard Features • Field selectable candela options of 15, 30, 60, 75, • Wide Voltage Range 16 -33 VDC or FWR and 110 candela • Separate Horn and Strobe Functions • Prewire Entire System, Then Install Your Signals • Available in Red or Off -White • Ease of Supervision Testing (Super Slide - ) • Lower Installation and Operating Costs • Input Terminals 12 to 18 AWG • Switch Selection for High or Low dBA Approvals • Switch Selection for High or Low Frequency r x.-.11 (1500 -3000 Hz) _ *� - • Switch for Temporal 3, Chime, or Whoop Tones :.. } r ' ' • Tamperproof Re- entrant Grill + ®� tilt • Surface Mount with the GSB (Gentex Surface • Americans with Disabilities Act (ADA 4.28.3) Mount Box) • BFP (City of Chicago) • • Synchronize Strobe and /or Horn by Using the BS +A/MEA #285 -91 -E • CSFM 7135- 0569:122 (GEC3) AVS -44 Control Module 7125- 0569:123 (GES3) • Silence Horn While Strobes Remain Flashing • NFPA 72 - • Rugged Die Cast Metal Mounting Bracket UL ULC Dual Listed 464, 1971 • True Evacuation Tone S ,wee Cundi``t t: mlineer ina S ., l dr.. ^kuvir.,r, ;.r comments and Gorr ections noted on the I enc ",osed documents. Wiring Diagram GE3 Series with AVS44 Synchronization Module PAP. mop= r4 ., .. _ g � ��. I .NB AIM =LIM ea— per. � 4!i err tea B. ♦ [5;at- VarTO IPLEMEIRMATE OMIT QVIERIeglEt CRT •Ilittl• 03 MGM ESN 4 a) ork MILIELJ r T_Z7 MOW GAM er aim Architect & Engineering Specifications: The audible and/or visible signal shall be Gentex GE3 Series or approved equal and shall be listed by Underwriters Laboratories Inc. per UL 1971and /or UL 464. The notification appliance shall also be listed with the California State Fire Marshall (CSFM) and the Bureau of Standards and Appeals (NYC). The notification appliance (combination audible /visible) shall produce a peak sound output of 100dBA or greater at 24V as measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible /visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or greater regardless of power input voltage. The appliance shall have an operating current of 55mA or less at 24 VDC for the 15Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16 -33 volts with either direct current of full wave rectified power. The appliance shall be capable of testing supervision without disconnecting wires. Also the appliance shall be capable of mounting to a surface back box. EX 24 units per carton �'° 27 pounds per carton _ Fire Protedion Products: www.gentexcom 10985 Chicago Dr., Box 310, Zeeland, MI 49464 616/392 -7195 1- 800/436 -8391 FAX: 616/392-4219 j� Genies corporation reserves the right to make changes to the product data sheets at their drscrehon. $fir Printed on Recycled Paper GE30201 -3 ,": e � �e x8, x zsza ., 4 n • ?� r y ' , �� s 9 ,+ x s z . 4.`: � ,,ilk ,, ' „. : - €' a' • Weatherproof Commander Series Evacuation Signals Applications The Weatherproof Commander Series is a low profile Strobe, horn or horn /strobe combination that offers dependable visible and /or audible alarms. }MffAM.P:, The WGE Series horns offer a new synchable chime and whoop tone and pro- 7-` �',°, . "' vide a selection of high or low dBA as well as a selection of a 2400 Hz (remote i� k , :2 ' 3 si or a low frequency broad band 1500- 3000Hz mechanical sounding ,° (evacuation) tone. t - ' ) c ''. °e } � The WGE Series are easily field changeable from temporal 3 to a continuous . tone by simply removing a jumper. The WGE is shipped from the factory on the 4: , �' i temporal lower frequency mode and it comes standard with a rugged die cast '.- , ' :, metal mounting plate. _,' i`: `- .L . ", � � ' The WGE Series has a minimal operation current and has a minimum flash ¢ -4_ '. rate of 1 Hz regardless of input voltage. The Weatherproof Series is equipped with the Super Slide' feature to test , GE;S WGEC supervision. Included with the unit is the GOE weatherproof enclosure. The unit and GOE enclosure must be used together to meet the UL outdoor listing. Shown with the GOE The WGE Series appliances are UL 464, UL 1638 listed for use with fire pro- tective systems and are warranted for three years from date of purchase. weatherproof enclosure Standard Features Approvals • Prewire Entire System, Then Install • Synchronize Strobe and /or Horn by - , Your Signals Using the AVS -44 Control Module �z, - c ? ' S • • Ease of Supervision Testing (Super • Listed for outdoor use when used 4 r ), : - : M= Slide'") with the GOE enclosure - ) • True Evacuation Tone • Silence Horn While Strobes �' °"'a ._._ `r°ma • Jumper Selection for High or Low Remain Flashing • Americans with Disabilities Act (ADA 4.28.3) dBA • Lower Installation and Operating • BFP (City of Chicago) • Jumper Selection for High Costs • BS +AIMEA #285.91E-XVI or Low Fr uenc • Input Terminals 12 to 18 AWG • CSFM 7135. 0569:122 7125 0569.127 Y 7300 - 0569:124 • Jumper for Temporal 3 • Rugged Die Cast Metal Mounting . NFPA 72 • Tamperproof Re- entrant Grill Bracket • tit. 464, UL 1638 • Wide Voltage Range 16 -33 VDC or • Available in Red or Off -White FWR • 75 Candela Strobe Meets ADA • Separate Horn and Strobe Functions 4.28.3 Requirements • Model Number Part Number Nominal Voltage Candela Model designations: GEH24R 904- 1205 -2 24VDC -- "W" = Walt Mount GEH24W 904 - 1207 -2 24VDC ___ "R" = Red Faceplate WGES -75WR 904 - 1219 -2 24VDC 75 UL1638 W = Off White Faceplate WGES -75WW 904 - 1220 -2 24VDC 75 UL1638 "P =Plain (no lettering) WGEC -75WR 904- 1217 -2 24VDC 75 UL1638 Plain units are non returnable. WGEC - 75WW 904 - 1218 - 24VDC 75 UL1638 *Operating the horn in this mode at this voltage will result in not meeting the minimum UL Operating temperature: Indoor. 32 0 to 120°F 0 a to 49°C reverberant sound level required for public mode Outdoor 31 to 150 F -35 to 66 C fire protection service. These settings are per DC (mA) acceptable only for private mode fire alarm use. DBA Q 10 ft per DBA @ 10 ft Use the high dBA setting for public mode UL464 (High) UL464 (Low) - Horn Mode 16v 24v 33v 16v 24v 33v 16v 24v 33v application (not applicable when using the chime tone. The chime tone is always private mode). Tema 3 2400Hz 78 83 84 71* 75 77 13 19 24 Notes: The sound output for the temporal 3 tone Temp 3 Mechanical 76 81 82 70* 73* 76 11 16 22 is rated lower since the time the horn is off is Temp 3 Chime 70* 71* 71* 66* 68* 70* 9 12 15 averaged into the sound output rating. While the Continuous 2400Hz 81 86 87 74* 78 80 14 21 28 horn is producing a tone in the temporal 3 mode Continuous Mechanical 80 84 85 72* 76 78 13 18 25 its sound pressure is the same as the continuous Continuous Chime 70* 71* 73* 66* 68* 70* 10 12 15 mode. Gentex does not recommend using a Whoop 82 83 83 69* 72* 75 43 51 56 coded or pulsing signaling circuit with any of our p strobe products. I See Cur;r. off L._ngine 3i''n E 4 !lop drawing rovipw comments and corrections noted on the enclosed documents. ._ "" "w' SAC �vma +� o ''Y ?',. r r,:','.: P : '-`"1. �a s r Mounting Super Slide" ,' � ., Switch Locations ' °�+... • ii ; . swrrcH POSITION . + 3 4 5 j + t bfacharica4T•ny ON ON ON j l Mechanical QFF ON ON II r11 I (( r �i Ht7amp ON OFF ON s ,-,,, I t ( till. j f ; NFCant OFF OFF ON II k I �'1 1 rl ;l� t ChimeT•mp ON ON OFF l� i} !.;, II P u%- CMmrC••t OFF ON OFF a = •..,.. „` * t t I i -. • fl Whoop ON `1 ! I i 7 „- it Who OFF OFF OFF s ( Switch Position 8 . - -...... =! i .- ON > HIGH dB Illist*, OFF> LOW dB Die Cast Metal Mounting Plate: Mounts to etttei'prooftioz I switch po9Hl i and 2 I�� Qz to the at1 horn an n to salsa @9 isolated tmrn and strobe ' power inputs. !� " J a Q 2 s Q E RMS Current Draw @ 24VDC --- ON _ Horn Strobe ( y� I i It l,t, i ce; ■ ■■ ■ ■ 21mA 112mA 1iU l 11,11•••11 J r tL --JC 1 r ..c ; P Wiring Diagram WGE Series rte. lel= 1) — INSEXIIIIVAL ''' lei talTWOMMISPIALRO UMW usUlas. 0, a _ TainillirtillelltINIALERACIMUrr T ri r; 0 �i �}- utgeTs e �.ir1il•lt rl sear medusa NW sae esgai me. w,a.mar rmarna �,. fi f, f� f�i� ry ei , 7 , T ::—P it g " l'cl 1 "4"mi: , . _ 1 1 Architect & Engineering Specifications The audible and/or visible signal shall be Gentex WGE Series or approved equal and shall be listed by Underwriters Laboratories Inc. per UL 1638 and /or UL 464. The notification appliance shall also be listed with the California State Fire Marshall (CSFM) and the Bureau of Standards and Appeals (NYC). The notification appliance (combination audibleNisible and audible units only) shall produce a peak sound output of 100dBA or greater as measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or greater regardless of power input voltage. The appliance shall also be capable of meeting the candela requirements of the ADA (75Cd) . The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The unit shall have an input voltage range of 16-33 waits with utter direct current of foil wave rectified power. The appliance shall be capable of test supervssit without disconnecting wires. Also the appliance shall be capable of mounting to a surface back box. The WGE unit _ must be used with the GOE outdoor enclosure to meet UL outdoor listing. , GE , � a rc., w_ CORPCINAT'ION 24 units per carton 27 pounds per carton Fre Protection Products: www.gentexco ) 10985 Chicago Dr., Box 310, Zeeland, Ml 49464 ' 616/392 -7195 1- 800/436-8391 FAX 616/392 -4219 Gentex corporation reserves the right to make changes to the product data sheets at their discretion. 0 Pnnted on Recycled Paper WGEC0602 -