Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the �A
Description
standard corrosion tests of the appli -.,
cable approval agencies, the testing is e
The Series TY -FRB, 2.8, 4.2, 5.6, and not representative of all possible cor -_
8.0 K- factor, Upright and Pendent rosive atmospheres. Consequently, it
Sprinklers described in this data sheet is recommended that the end user be "*
are quick response - standard cover- consulted with respect to the suitability -
age, decorative 3 mm glass bulb type of these coatings for any given corro i._
spray sprinklers designed for use in sive environment. The effects of ambi- € - ��
light or ordinary hazard, commercial ent temperature, concentration of
occupancies such as banks, hotels, chemicals, and gas /chemical velocity,: =:a: -'
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be
plicable, is intended for use in areas exposed.
with a finished ceiling. It uses either a An intermediate level versions of the 7–
two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers < `„
Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet I`
cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de ''
recessed adjustment or up to 3/4 inch tailed in Technical Data SheetTFP780
(19,1 mm) of total adjustment from the ,
flush pendent position, or a two -piece • WARNINGS -=
Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de-
inch NPT) Recessed Escutcheon with
scribed herein must be installed and '•
1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen- ble standards of the National Fire Pro -
dent position. The adjustment pro- tection Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hav- Model /Sprinkler
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de- Identification
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain- Numbers
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition. TY11 1 Upright - 2.8K T 112 NPT- -
that which would otherwise be ob- The installing contractor or sprinkler TT1 — P ent 2.8K 1- I2"NPT
manufacturer should be contacted 2"NPT
with any questions. 72K; 172"NPT
IMPORTANT TY3131 - Upright 5.6K, 1/2"NPT refer to Technical Data TY3231 - Pendent 5.6K, 112 "NPT&
Sheet TFP700 for the "INSTALLER T
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and corn T
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 MARCH, 2007 TFP171
tijco Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -FRB — 5.6 K- factor
Horizontal and Vertical Sidewall Sprinklers
Quick Response, Standard Coverage
General ment provided by the Recessed Es-
cutcheon reduces the accuracy to
which the fixed pipe nipples to the
Description sprinklers must be cut.
The Series TY -FRB, 5.6 K- Factor, Corrosion resistant coatings, where
applicable, are utilized to extend the f t '
Horizontal and Vertical Sidewall Sprin- PP ,- tv
klers described in this data sheet are life of copper alloy sprinklers beyond
quick response standard coverage, that which would otherwise be ob- a . Y, ,
decorative 3 mm glass bulb type spray tamed when exposed to corrosive at �'.;*
sprinklers designed for use in light and mospheres. Although corrosion resis�
s
ordinary hazard, commercial occupan- tant coated sprinklers have passed the
standard corrosion tests of the appli
cies such as banks, hotels, shopping �_
malls, etc. They are designed for in- cable approval agencies, the testing is
stallation along a wall or the side of a not representative of all possible cor-
beam and just beneath a smooth cell- rosive atmospheres. Consequently, it
ing. Sidewall sprinklers are commonly is recommended that the end user be
used instead of pendent or upright consulted with respect to the suitability .. : •
sprinklers due to aesthetics or building of these coatings.for any given corro- ,u ..
construction considerations, where sive environment. The effects of ambi-
piping across the ceiling is not desir- ent temperature, concentration of;
able. chemicals, and gas /chemical velocity, :k
sho be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the �r
TY -FRB Horizontal Sidewall Sprinkler chemical to which the sprinklers will be
lf
is intended for use in areas with a exposed. `
finished wall. It uses a two -piece Style t
10 Recessed Escutcheon with 1/2 inch WARNINGS -,.
(12,7 mm) of recessed adjustment Or The ( ) 1 The Series TY -FRB Sprinklers de-
up to 3/4 inch (19,1 mm) of total adjust- scribed herein must be installed and
ment from the flush sidewall position, maintained in compliance with this
or a two -piece Style 20 Recessed Es- document, as'well as with the applica- Technical
cutcheon with 1/4 inch (6,4 mm) of ble standards of the National Fire Pro -
recessed adjustment or up to 1/2 inch tection Association, in addition to the Data
(12,7 mm) of total adjustment from the standards of any other authorities hav-
flush sidewall position. The adjust- ing jurisdiction. Failure to do so may Approvals
impair the performance of these de- UL and C -UL Listed.
vices. FM, LPCB, and NYC Approved.
The owner is responsible for maintain- (Refer to Table A for complete ap-
ing their fire protection system and de- proval information including corrosion
IMPORTANT vices in proper operating condition. resistant status.)
The installing contractor or sprinkler Max Workin g Pressure
Always refer to Technical Data manufacturer should be contacted Refer to Table B.
Sheet TFP700 for the "INSTALLER with any questions.
WARNING" that provides cautions Discharge Coefficient
with respect to handling and instal- Model/Sprinkler
K = 5.6 GPM /psi (80,6 LPM /bar
• lation of s rinkler s stems and corn- Temperature Ratings
ponents. Improper handling and in-
stallation can permanently damage Identification Refer Table A.
a sprinkler system or its compo= Finishes
nents and cause the sprinkler to fail Numbers Sprinkler: Refer to Table A.
to operate in a fire situation or cause Recessed Escutcheon: White Coated,
it to operate prematurely. TY3331 -. Horizontal Chrome Plated, or Brass Plated.
TY3431 - Vertical
Page 1 of 6 APRIL, 2006 TFP176
tqco ' Fire & Building
Products
rapid respons
HOME FIRE SPRINKLER SYSTEM
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series LFII Residential
Pendent Sprinklers
•
4.9 K- factor
General adjustment or up to 1/2 inch (12,7 mm)
of total adjustment from the flush ceil- =ON<
ing position. The adjustment provided
Description by the Recessed Escutcheon reduces
the accuracy to which the pipe nipples
The Series LFII (TY2234) Residential to the sprinklers must be cut. s
Pendent Sprinklers are decorative, 0
g The Series LFII (TY2234) has been �`
fast response, frangible bulb s p rin= ( )
- klers designed for use in residential designed with heat sensitivity and
occupancies such as homes, apart- water distribution characteristics
proven to help in the control of residen- ��
ments, dormitories, and hotels. When P P
tial fires and to improve the chance for
aesthetics end optimized flow charac- p� fic
teristics are the major consideration, occupants to escape or be evacuated.
the Series LFII (TY2234) hould be the���°
first choice. ) 4 ;-
WARNINGS
The Series LFII are to be used in wet
The Series LFII (TY2234) Residential
pipe residential sprinkler systems for Pendent Sprinklers described herein
one- and two - family dwellings and mo- must be installed and maintained in
bile homes per NFPA 13D; wet pipe compliance with this document, as <, ;.,
residential sprinkler systems for resi- well as with the applicable standards r s'
dential occupancies up to and includ- of the National Fire Protection Asso .
ing four stories in height per NFPA ciation, in addition to the standards of ,
13R; or, wet pipe sprinkler systems for any other authorities having jurisdic-
the residential portions of any occu- tion. Failure to do so may impair the : # '' r ,
pancy per NFPA 13. performance of these devices. � � � �`
The Series LFII (TY2234) has a 4.9 The owner is responsible for maintain -
(70,6) K- factor that provides the re- ing their fire protection system and de
quired residential flow rates at reduced vices in proper operating condition.
pressures, enabling smaller pipe sizes The installing contractor or sprinkler ' `
and water supply requirements. manufacturer should be contacted
with any questions.
hY
The recessed version of the Series y Q , . b
LFII (TY2234) is intended for use in �..,
areas with finished ceilings. It employs Sprinkler/IVlodel
a two -piece Style 20 Recessed Es-
cutcheon. The Recessed Escutcheon Identification
provides 1/4 inch (6,4 mm) of recessed
Number
SIN TY2234
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
• lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8 JANUARY, 2006 TFP400
tqCi / Fire & Building
Products
rapid response
HOME FIRE SPRINKLER SYSTEM
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
BlazeMaster
CPVC Fire Sprinkler Pipe & Fittings
Submittal Sheet
General Technical
t c i7
Description Data
Tyco Fire & Building Products (TFBP) Sizes
BlazeMaster CPVC Pipe and Fittings 3/4" to 3"
are designed exclusively for use in wet'
Maximum Working Pressure
pipe automatic fire sprinkler systems. 175 psi
They are made from a specially devel- p�� f "
oped thermoplastic compound com- Approvals
p osed of post
chlorinated , FM, CUL, NSF, Dade County, polyvinyl UL � � �-'� �° � `��
chloride (CPVC) resin and state of the LPCB, MEA, and the City of Los Ange ��`
art additives. TFBP BlazeMaster les. (Refer to IH -1 Rev. 0, Janu
CPVC products are easier to install ary 2005 "Installation Instruction &
than traditional steel pipe systems, Technical Handbook" for exact list m
and at the same time, provide superior ing /approval information.) _"
heat resistance and strength as corn-
Manufacture Source
pared to traditional CPVC and PVC U.S.A.
piping materials used in the plumbing
trade. Various' adapters are available Material
to connect CPVC pipe to metallic pip- .Pipe: ASTM F442, SDR 13.5
ing. All female pipe thread adapters
have brass inserts for durability. • Fittings: ASTM F438 (Sch. 40) and
Grooved adapters connect directly to ASTM F439 (Sch. 80), ASTM F1970
grooved end valves and metallic pipe,
with flexible grooved end couplings. Color
Orange
WARNING
Tyco Fire & Building Products (TFBP)
BlazeMaster CPVC Pipe and Fittings
described herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
.
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
BlazeMaste, is a registered trademark
of Noveon IP Holding Corp. •
Page 1 of 6 JANUARY, 2006 TFP1915
•
ES- A- C300a/C300Na
Colt Series C300a - C300 Na
AMES
FIRE & WATERWORKS
Double Check Detector Assemblies
Sizes: 21/2" - 6" (65 - 150mm)
¢ t o
- C300a0SY r
C300aBFG
•
• ',�t` '2L,
•
•
Features The Colt C300a, C300Na Double Check Detector Assemblies are used to
prevent backflow of pollutants, that are objectionable but not toxic, from
• Extremely Compact Design entering the potable water supply system. The Colt C300a, C300Na may
• 70% Lighter than Traditional , be installed under continuous pressure service and may be subjected to
Designs backpressure. The Colt C300a, C300Na are used primarily on fire line
• 304 (Schedule 40) Stainless Steel sprinkler systems when it is necessary to monitor unauthorized use
Housing & Sleeve of water. For use in non - health hazard applications.
• Groove Fittings Allow Integral
Pipeline Adjustment
Patented Bi -Link Check Provides Specifications
• Lowest Pressure Loss The Colt C300a, C300Na Double Check Detector Assemblies shall
Unmatched Ease of Serviceability consist of two independent Bi -Link Check modules within a single
• housing, sleeve access port, four test cocks and two drip tight shutoff
• Available with Grooved Butterfly valves. Bi -Link Checks may be removable and serviceable, without the
Valve Shutoffs use of special tools. The housing shall be constructed of 304 (Schedule
• May be Used for Horizontal, 40) stainless steel pipe with groove end connections. Bi -Link Checks
Vertical or N Pattern Installations shall have reversible elastomer discs and in operation shall produce drip
• Replaceable Check Disc Rubber tight closure against the reverse flow of liquid caused by backpressure or
backsiphonage. The bypass assembly consists of a meter which registers
in either gallon or cubic measurements, a double check valve assembly
and required test cocks. Assembly shall be a Colt C300a, C300Na as
manufactured by the Ames Company.
Job Name Contractor
Job Location Approval
Engineer Contractor's P.O. No. •
Approval Representative
Ames product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Ames Technical
Service. Ames reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make
such changes and modifications on Ames products previously or subsequently sold.
www.amesfirewater.com
Dyna-Flow®
High Strength Steel Pipe
The original high strength lightwall sprinkler pipe with hydraulics superior to Schedule -10.
Dyna -Flow pipe is the "original" high- • ,o P „_
, � -. K � Specifications �.. . � . ,.
strength lightwall sprinkler pipe. Dyna- -
Flow has outstanding hydraulic NPS Nominal I.D. Wt. Wt. (H20 Filled) Pcs/ Wt/Lift (21') WI/Litt (24') Wt/Lift (25') •
capabilities and is recognized as the In; mm In; mm Lbs/Ft; Kg /m Lbs/Ft; Kg /m Lift Lbs; Kg Lbs; Kg Lbs; Kg
most popular alternative to Schedule -10 1" 1.191 0.830 1.31 91 1,586 1,812 1,888
pipe. Lightweight, easy to cut and easy 25 30.3 1.2 1.95 91 719 822 856
to handle for installation. Dyna -Flow is a 1W 1.536 1.059 1.87 61 1,356 1,550 1,615
valuable addition to any fire protection 32 39.0 1.6 2.78 61 615 703 733
system. 1W 1.728 1.667 2.71 61 2,135 2,440 2,542
Superior Hydraulics 40 43.9 2.5 4.03 61 968 1107 1153
2" 2.203 2.104 3.79 37 1,634 1,868 1,946
With an inside diameter of up to 11% 50 56.0 3.1 5.64 37 741 847 883
larger than Schedule -40 and up -to 7% 2W 2.703 2.564 5.10 30 1,615 1,846 1,923
larger than Schedule -10, Dyna -Flow 65 68.7 3.8 . 7.59 30 733 837 872
pipe hydraulics are exceptional. Larger 3" 3.314 3.387 7.18 19 1,351 1,544 1,608
I.D.s enable Dyna -Flow, and related 80 84.2 5.0 10.69 19 613 700 729
components, to be down -sized within the 4" 4.310 4.473 10.86 19 1,784 2,039 2,124
system, thus increasing the potential for 90 109.5 6.7 16.16 19 809 925 963
job cost savings. For complete Hazen -
Williams charts, refer to "Dyna -Flow
Hydraulic Data Tables."
Coatings & Fabrication Specifications & Approvals Additional Benefits
Dyna -Flow products are coated with Dyna - Flow /Super Flo pipe is manufac- • Lightweight and easy to install,
an environmentally approved and tured to meet ASTM A -795 Type E, resulting in more efficient use of your
specially formulated modified - acrylic or Grade A and is in compliance with freight and labor dollars.
water -based coating. This durable coating NFPA -13 and NFPA -14. All sizes of
is paintable. The black coating acts,as Dyna Flow /Super Flo are UL Listed, FM 'Provides stability needed to comply
an excellent primer and is resistant to Approved and ULC Listed. with standard hanger spacing
(15 ft O.C.) per NFPA.
weathering and U.V. degradation from
outdoor storage. 0 ® ® • Available in Standard lengths for your
Metallurgical properties provide excellent Listed Approved Listed convenience, or can be ordered in
fabrication characteristics for end prep custom lengths upon approval.
Dyna - Flow /Super Flo is UL/ULC Listed
finishes, welding and roll grooving. • Fast cutting and welding as well as
for use with roll grooved, plain -end g g>
There is no special process or equipment couplings, and welded joints for wet, dry, easy roll grooving and end preparation.
needed for fabrication and installation. , preaction and deluge systems. It is FM
• Available in Factory roll grooved form
The internal surface of all black Allied Approved for roll grooved, plain -end, and for quicker shop turnaround.
Tube & Conduit Fire Sprinkler pipe welded joints for wet systems. Refer to
products up to 4.5000" in diameter is appropriate documentation for up-to -date • Clean, durable mill coating provides
coated with our new Antibacterial listing and approval information. Dyna- longer "shelf life" and acts as an
Formula, "ABF". In scientific laboratory Flow /Super Flo is now available "hot- excellent primer for custom paint
test, ABS proved to have superior dip" galvanized and has been specifically applications.
resistance to microbial colonization of approved by FM for dry systems uses.
• pipe walls, thereby delaying or possibly
preventing the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
tgco ^ l-J allied 16100 S. Lathrop • Harvey, IL Customer Service:
11350 Norcom Rd. • Philadelphia, hia, PA 19154 (800) 882 -5543
a vital part of your world TUBE 8 CONDUIT 2525 N. 27 th Ave. • Phoenix, AZ 85009 Fax 708- 339 -1806
S2 - 3
n
. ,,
f
Dyna-Thread®
.
Full Line Sch -40 Replacement
•
Dyna - Thread's offers the life expectancy of Sch-40 with superior hydraulics and greater value.
Dyna- Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
and longevity of traditional Sch -40 pipe with quality and superior hydraulic advantages.
Comparison to Schedule 40 .. Comparison to L.W.T. Pipes
• Dyna - Thread's inside diameter is up • With its increased strength and lighter • More wall thickness at the thread
to 3.6% larger than Sch -40 giving it weight, Dyna - Thread reduces (CRR =1.00) gives Dyna - Thread
superior hydraulics. And, when used installation fatigue and is ideal for better life expectancy than lightwall .
in combination with Dyna -Flow pipe, retro -fit applications. threadable pipe joints. .
down sizing often occurs.
Corrosion Resistance Ratio (CRR) is a • Unlike lightwall threadable pipe,
• Dyna - Thread is fully listed and UL (Underwriters Laboratory) term for Dyna - Thread has no thread gauge
approved by UL, ULC, and FM for the estimated life expectancy of a pipe warning.
fire sprinkler applications. joint. This is based on the calculated
wall thickness at the base of the first • Dyna-Thread is approved for
• The life expectancy of Dyna- Thread standard hanger spacing (15 ft.
equal based on the exposed thread, assumed to be the
and Sch-40 are e
q weakest point of the pipe length. Dyna- O.C.), can be used as earthquake
calculated wall thicknesses per UL. sway bracing, and is safe to use as
Thread and Sch -40 have the same
• The consistent quality of steel used to calculated wall thicknesses at this point drops.
make Dyna - Thread facilitates smooth and are both assigned the same CRR of • Dyna - Thread is safer to weld on.
threading and lower maintenance 1.00.
costs. • Dyna - Th is more widely
The internal surface of all black Allied accepted than lightwall threadable
• The exterior of Dyna - Thread is where Sch -40 is specified.
protected by a clean, durable mill Tube & Conduit Fire Sprinkler pipe
coating for extended shelf life and products up to 4.5000" in diameter is
easy paint application. coated with our new Antibacterial
Formula, "ABF'. In scientific laboratory
test, ABS proved to have superior : & Ap
resistance to microbial colonization of
® ® ® pipe walls, thereby delaying or possibly Super 40/Dyna- Thread pipe is
preventing the onset of manufactured to meet: ASTM A -135,
Microbiologically Influenced corrosion Grade A and is in compliance with
Listed Approved Listed NFPA -13. All sizes of Super 40/Dyna-
(MIC) when the First Sprinkler System
is first installed. Thread are rated at 300 psi working
pressure. Super 40/Dyna- Thread is UL
'• ' , Specifications and ULC Listed for wet, dry deluge and • •
NPS Nominal 1.1 Wt. Wt. (H20 Filled) Pcs/ Wt/Lift (21'). Wt/Lift (24') Wt/Lift (25') Pre action sprinkler systems and FM
Approved for use in wet systems. Super
In; mm In; mm Lbs/Ft; Kg/m Lbs/Ft; Kg /m Lift Lbs; Kg Lbs; Kg Lbs; Kg 40/Dyna Thread can be "hot -dip"
1" 1.080 1.330 1.75 70 1955 2234 2327 galvanized to meet FM requirement for
25 27.4 2.0 '2.60 70 887 1013 1056 dry systems. Super 40/Dyna- Thread is
- 1 1.408 1.870 2.54 51 2002 2288 2384 approved for all threaded couplings and
32 35.8 2.8 3.78 51 908 1038 1081 welded outlets and is suitable for all
1'A 1.639 2.290 3.22 44 2115 2418 2519 roll - grooved, and plain -end fittings.
40 41.6 3.4 4.79 44 959 1097 1143 (See listing information).
2" 2.104 3.050 4.57 30 1921 2196 2287
50 53.4 4.5 6.80 30 871 996 1037