Loading...
Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 July 12, 2007 14 r _ RE: FIRE SPRINKLER SYSTEM l- .,,'k ' -N t ' V _ i _ _ Project Information R i Building Permit: BUP2007 -00336 Construction Type: VA Tenant Name: Grant Street Elite Care Occupancy Type: SR -1 Address: 12353 SW Grant St. Occupant Load: 394 Area: 25272 Sq. Ft. Stories: 3 Hazard: Light Commodity: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; National Fire Protection Association, Standard 13 (NFPA 13)2002 edition and the State of Oregon Fire Code (OFC) 2004 edition. The following conditions must be completed prior to permit issuance. 1) Complete coverage shall be shown on the plans for the following areas; a) all attic spaces b) all closets c) below decks greater than 4 ft. wide d) porte cochere • - _ .. _ .. • . . • .:. • ade. . - a - - • . • a 2 inc un. ergroun • supp , . • A - "• - •• - • •ser. O ,fri - a 3) Show drawing of RP Device required by the City of Tigard for the anti- freeze loop. 4) Plans do not show all room partitions for complete coverage. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, i ,,� Sri Lean Nelson, Senior Plans Examiner Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard or.gov • TTY Relay: 503.684.2772 re on Department of Human Services Seniors and People with Disabilities 18.59 Theodore R. Kulongoski, Govern 500 Summer Street NE, E13 Salem, OR 97301 -1074 (503) 945 -5832 March 9, 2006 kig 1000 1- 800 - 232 -3020 � � G p,�D Fax (503) 378 -8966 cV OF p er s∎o- Val Henzel ' g ull -DIN CITY OF TIGARD BUILDING DEPARTMENT 13125 SW Hall Blvd. Tigard, Oregon 97223 RE: ELITE CARE EXTENDED FAMILY RESIDENCE (RCF) 12345 S.W. GRANT STREET TIGARD, OREGON 97223 Dear Ms. Henzel: As discussed with Mike McDernDtt, State of Oregon, Facilities Planning and Safety and as outlined in the State of Oregon 2004 Structural Specialty Code Amendments (based on the 2003 International Building Code), Appendix SR Section SR 101.3, we understand that the above facility willbe licensed for a maximum of 30 residents in an Occupancy Type SRI. As outlined in IBC SR 102.1 and Appendix Table SR 109.1, facilities with more than 16 residents are considered "assisted selfpreservation" and should have evacuation time under 13 minutes. Th you, Allison McKenzie SENIORS & PEOPLE WITH DISABILITIES OFFICE OF LICENSING & QUALITY OF CARE "Assisting People to Become Independent, Healthy and Safe" SPD 1350 (02/03) An Equal Opportunity Employer cc: Craig Monaghan, Architect (4522 Lower Drive, Lake Oswego OR 97035) Mike McDermott, FACILITIES PLANNING AND SAFETY Page 1 of 1 Val Henzel - FW: Engineering for the 6' high perimeter wall - CMU block From: scoff <palmhi112 @mindspring.com> To: "'Val Henzel "' <Val @tigard- or.gov >, "'Brian Blalock" <brianb @tigard- or.gov> Date: 9/18/2006 5:11 PM Subject: FW: Engineering for the 6' high perimeter wall - CMU block CC: "'Mark Reed" <reed @stdairy.com >, "'Scott Churchill (E- mail)" <monroestreetassociates@earthlink.net> Val and Brian, Per our previous discussions, here is the engineered 6' high CMU block wall With a footing that allows the wall to be built as close as possible to The property line. It has been fully engineered by Rowell Structural Engineers. The desire of Ownership is to file this electronically. Please let me know if this is acceptable given the urgency to begin the work. Regards, Scott Churchill Original Message From: Vicki Miller [mailto:vickim @rowelleng.com] Sent: Monday, September 18, 2006 3:13 PM To: palmhill2 @mindspring.com Subject: Scott Churchill 9- 18- 06.pdf file //C:\Documents and Settings \val.000\Local Settings \Temp \GW }00002.HTM 9/21/2006 City of Tigard, Oregon 0 13125 SW Hall Blvd. . Tigard, OR 97223 5 , December 20, 2007 ® RE: FIRE SPRINKLER SYSTEM Proiect Information Building Permit: BUP2007 -00336 Construction Type: 5 -A Tenant Name: Grant Street Elite Occupancy Type: SR -1 Address: 12353 SW Grant St. Occupant Load: 394 Area: NA Stories: 3 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; National Fire Protection Association, Standard 13 (NFPA 13) 2002 edition and the State of Oregon Fire Code (OFC) 2007edition. GENERAL 1. A key box shall be installed in a location approved by the Fire Chief. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Section 506.1 OFC. Please contact Tualatin Valley Fire & Rescue for key box information at 503 -612- 7010 2. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers on the property. Sections 6.2.9.1 & 6.2.9.2 NFPA 13. 3. The spare sprinklers shall be kept in a cabinet located where temperatures will not exceed 100 degrees "F" at any time. A special sprinkler wrench shall be provided and kept in the sprinkler cabinet to be used in the removal and installation of sprinklers. Sections 6.2.9.3 & 6.2.9.6 NFPA 13. 4. The clearance between the deflector and the top of storage shall be 18 inches or greater. Section 8.6.6.1 NFPA 13. The distance shall be increased to 36 inches for Large Drop sprinkler heads. Section 8.11.6 NFPA 13 5. Sprinklers shall be located a minimum of 4 inches from walls and spaced not less than 6 feet on center. Sections 8.6.3.3 & 8.6.3.4.1 NFPA 13. 6. Clearances shall be provided around all piping extending through platforms, foundations, walls and floors. The diameter of the hole shall be 2 inches larger than the penetrating pipe for pipe sizes 1 inch through 3 inches. The diameter of the hole shall be 4 inches larger than the penetrating pipe for pipe sizes 4 inches and larger. Sections 9.3.4.1 & 9.3.4.2 NFPA 13. Phone: 503.639.4171 0 Fax: 503.684.7297 ® www.tigard- or.gov • TTY Relay: 503.684.2772 7. All valves controlling the water supply for automatic sprinkler systems and all water flow monitoring devices shall be electrically monitored when the system serves more than 20 heads. Section 903.4 OFC 8. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. Such sprinkler water -flow devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Section 903.4.2 OFC 9. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads to prevent vertical motion resulting from seismic loads. The structural components to which bracing is attached shall be determined to be capable of carrying the added applied seismic loads. Sway braces shall be designed to withstand forces in tension and compression. Bracing shall be attached directly to feed and cross mains. 10. The end sprinkler on a line shall be restrained against excessive vertical and lateral movement. 11. New sprinkler system piping shall be hydrostatically tested at 200 psi and shall maintain that pressure without loss for two hours. NFPA13 16.2.1.1 12. All concealed spaces enclosed wholly or partly by exposed combustible construction shall be protected by sprinklers. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, v300, Dan Nelson, Senior Plans Examiner (503) 718 -2436 dann @ tgard - or.gov