Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
August 3, 2009 I1
S
• s •
RE: SITE PERMIT FOR NATIONAL SAFETY COMPANY
T I GARD
Project Information
Building Permit: SIT2009 -00006 Construction Type: 5 -B
Address: 7105 SW Gonzaga Occupancy Type: B
Area: 10,400 Sq. Ft. Stories: 2
Name: National Safety Co. Sprinkled: Yes
The plan review was performed under the State of Oregon Structural Specialty
Code (OSSC) 2007 edition; 2007 Oregon Fire Code and NFPA 13. Please
provide the following conditions prior to issuance of the permit.
1) Please complete page 2 of the site permit application. Response
accepted.
2) Show all underground fire lines and location of double check device.
Provide details and drawings. Response denied. Please provide
TVW approval for locating double check in building.
3) Show locations of fire hydrants. Response accepted
4) Please submit completed TVFR fire flow worksheet from TVFR
website. Response accepted
5) Please provide flow test results from closest fire hydrant. Response
denied — Fire flow shall be done within 5 years and done on the
closest hydrant.
6) Provide Geo Tech Soils Report. Response denied — Geo Tech report
required for this building because it is being built over a removed
house.
7) Footings for building are not allowed to be in the street right of way.
Response denied. Encroachment permit shall be taken out
through Mike McCarthy, Senior Project Engineer.
8) Show finish grade elevation for accessible routes. Response
accepted
9) Show detectable warnings where accessible ways cross traffic lanes.
Response accepted. Will red line plans
10)Plans show ramp up from access stall from accessible parking space.
Response accepted.
11)Please provide complete site erosion control plan showing all erosion
control measures. Response accepted.
12)Provide demo permit for removal of house and final inspections for
both demo permits. Response denied — Pease provide final
inspection for demo permit No. BUP2008- 00304.
13)Provide completed 1200C and PFI Permits. Response accepted
14)Plans indicate a 11,160 sq. ft. building. Original building was
approved as a 10,416 sq. ft. by the planning department. This
increase in size would have to be approved with a new minor
modification.
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard - or.gov • TTY Relay: 503.684.2772
When responding, provide an itemized letter stating in what way each
numbered issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy
of the City of Tigard, Letter of Transmittal. The letter of transmittal assists the
City of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson
Senior Plans Examiner
(503)718 -2436
dann @tigard- or.gov
08/03/2009 10:17 5636243681 Tir RD BLIILDI NIG DEPT FA _1 02
Poet -it`A Fax Note 7671 i oa page
City of Tigard, Oregon T° '4& Fns
c„.109 00.
August 3, 2009 +Tone" Phone, '7t 2 _, €%; "
iM
RE: SITE PERMIT FOR NATIONAL SAFETY COMPANY
TIGARI)
Project information
Building Permit S1T2009 -00006 Construction Type: 5 -B
Address: 7105 SW Gonzaga Occupancy Type: B t
Area: 10,400 Sq. Ft. Stories: 2 jl7
Name: National Safety Co. Sprinkled: Yes d p Cry
zo
The plan review was performed under the State of Oregon Structural Specialty n
Code (OSSC) 2007 edition; 2007 Oregon Fire Code and NFPA 13. Please
provide the following conditions prior to issuance of the permit. 1"r�
1) Please complete page 2 of the site permit application. Response
accepted.
2) Show all underground fire lines and location of double check device.
Provide details and d- awings. Response denied. Please provide
TVW approval for locating double check in building.
3) Show locations of fire hydrants. Response accepted
4) Please submit completed TVFR fire flow worksheet from TVFR
website. Response accepted
_5) Tease provide flow test results from closest fire hydrant. Response
denied -- Fire flow shall be done within 5 years and done on the
closest hydrant.
i�i)rovide Geo Tech Soils Report. Response denied -- Geo Tech report
required for this building because it is being built over a removed
house.
7) � tings for building are not allowed to be in the street right of way.
esponse denied. Encroachment permit shall be taken out
through Mike McCarthy, Senior Project Engineer.
8) Show finish grade elevation for accessible routes. Response
accepted
9) Show detectable warnings where accessible ways cross traffic lanes.
Response accepted. Will red line plans
l0)Plans show ramp up from access stall from accessible parking space.
WED ham, Response accepted.
1 oc �� 11) Please provide complete site erosion control plan showing all erosion
control measures. Response accepted.
12)Provide demo permit for removal of house and final inspections for
/I/0c A both demo permits. Response denied -- Pease provide final
SSS4� inspection for demo permit No. BUP2008- 00304.
13 Provide completed 1200C and PFI Permits. Response accepted
C O L.c9 IA/6 nS indicate a 11,160 sq. ft. building. Original building was
v proved as a 10,416 sq. ft. by the planning department. This
ID PP � increase in size would have to be approved with a new minor
cG O ;C6 2_ modification.
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard-or.gov • TTY Relay: 503.684.2772
A
TRANSMISSION VERIFICATION REPORT
TIME : 08/03/2009 10:14
NAME : TIGARD BUILDING DEPT
FAX : 5036243681
TEL .
SER.# : BROD4J479592
DATE,TIME 08/03 10:14
FAX NO. /NAME 5032245936
DURATION 00:00:21
PAGE(S) 02
RESULT OK
MODE STANDARD
ECM
(1$9
Post-if Fax Note 7671 Da e pages
City of Tigard, Oregon ' . Ta.. - M 'hi ► +'
Co. /Dept. Ca. 1
August 3, 2009 Prone# Phone ",ice (• 2# Ii
Fax A'S07:J 22 C ,. Fax *
el
RE: SITE PERMIT FOR NATIONAL SAFETY COMPANY
TIGARD
Project Information
Building Permit: SIT2009 -00006 Construction Type: 5 -B
Address: 7105 SW Gonzaga Occupancy Type: B
Area: 10,400 Sq. Ft. Stories: 2
Name: National Safety Co. Sprinkled: Yes
The plan review was performed underthe State of Oregon Structural Specialty
Code (OSSC) 2007 edition; 2007 Oregon Fire Code and NFPA 13. Please
provide the following conditions prior to issuance of the permit.
1) Please complete page 2 of the site permit application. Response
accepted.
2) Show all underground fire lines and location of double check device.
Provide details and drawings. Response denied. Please provide
TVW approval for locating double check in building.
3) Show locations of fire hydrants. Response accepted
4) Please submit completed TVFR fire flow worksheet from TVFR
website. Response accepted
5) Please provide flow test results from closest fire hydrant. Response
denied — Fire flow shall be done within 5 years and done on the
closest hydrant.
6) Provide Geo Tech Soils Report. Response denied — Geo Tech report
required for this building because it is being built over a removed
house.
7) Footings for building are not allowed to be in the street right of way.
Response denied. Encroachment Hermit slhall be taken out
TRANSMISSION VERIFICATION REPORT
TIME : 08/0312009 10:18
NAME : TIGARD BUILDING DEPT
FAX : 5036243681
TEL .
SER.# : BROD4J479592
DATE,TIME 08/03 10:17
FAX NO. /NAME 5036205338
DURATION 00:01:06
PAGE(S) 02
RESULT OK
MODE STANDARD
2
Poet -it Fax Note 767 1 Da l = _ P 9 S
City of Tigard, Oregon , .► From ( GA. . e ..�
Co, /Dept. Co .
August 3, 2009 Pnona # Phan 07.y 7t
Fax # 43.13 6s Fax #,� ,-y ,7 •
RE: SITE PERMIT FOR NATIONAL SAFETY COMPANY
TIGARD
Project Information
Building Permit: SIT2009 -00006 Construction Type: 5 -B
Address: 7105 SW Gonzaga Occupancy Type: B
Area: 10,400 Sq. Ft. Stories: 2
Name: National Safety Co. Sprinkled: Yes
The plan review was performed under the State of Oregon Structural Specialty
Code (OSSC) 2007 edition; 2007 Oregon Fire Code arid NFPA 13. Please
provide the following conditions prior to issuance of the permit.
1) Please complete page 2 of the site permit application. Response
accepted.
2) Show all underground fire lines and location of double check device.
Provide details and drawings. Response denied. Please provide
TVW approval for locating double check in building.
3) Show locations of fire hydrants. Response accepted
4) Please submit completed TVFR fire flow worksheet from TVFR
website. Response accepted
5) Please provide flow test results from closest fire hydrant. Response
denied -- Fire flow shall be done within 5 years and done on the
closest hydrant.
6) Provide Geo Tech Soils Report. Response denied -- Geo Tech report
required for this building because it is being built over a removed
house.
7) Footings for building are not allowed to be in the street right of way.
Response denied. Encroachment permit shall be taken out
City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
June 3, 2009
•
RE: SITE PERMIT FOR NATIONAL SAFETY COMPANY
T I GARD
Project Information
Building Permit: SIT2009 -00006 Construction Type: 5 -B
Address: 7105 SW Gonzaga Occupancy Type: B
Area: 10,400 Sq. Ft. Stories: 2
Name: National Safety Co. Sprinkled: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; 2007 Oregon Fire Code and NFPA 13. Please provide the
following conditions prior to issuance of the permit.
1) Please complete page 2 of the site permit application. , "i° r"--
2) Show all underground fire lines and location of double check device. Provide
details and drawings. -v) &pencitiAL of ✓✓ sN TL° stis,
3) Show locations of fire hydrants.
4) Please submit completed TVFR fire flow worksheet from TVFR website.
5) Please provide flow test results from closest fire hydrant.
6) Provide Geo Tech Soils Report.
7) Footings for building are not allowed to be in the street right of way = JC tjsC
8 • • - •• _ - _ . • - r Sy -; K-(6.4.71—
9) Show finish grade elevation for accessible routes. 1 i�
10)Show detectable warnings where accessible ways cross traffic lanes.
11) Plans show ramp up from access stall from accessible parking space. 7
12)Please provide complete site erosion control plan showing all erosion control
measures.
13)Provide demo permit for removal of house and final inspections for both demo
permits.
14)Provide completed 4.2006.esd.PFI Permits.
This plan review is as complete as possible with the preliminary plans.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard
in tracking and processing the documents.
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
Respectfully,
an Nelson
Senior Plans Examiner
(503)718 -2436
dann @tigard - or.gov
1 r
Fire Marshal's Division Offices
Tualatin Valley North - 14480 SW Jenkins Rd., Beaverton, OR 97005, (503) 356 -4700
Fire & Rescue South - 7401 SW Wash Ct., Tualatin, OR 97062, (503) 612 -7010
Fire Flow and Hydrant Worksheet
This worksheet is required to be submitted to and approved by the Authority Having Jurisdiction
(AHJ) before any permits for new building construction, building expansion or fire hydrants will be
issued by any building department within the TVF &R District. See the instructions for assistance
completing this form or call one of the above numbers.
Preparer Information
Preparer Name:
Phone: I Fax:I I
Architect / Engineer of Record: I
Phone: I Fax:I
General Building Information
Project Name:
Project Address: I
City: I County:I I Zip:I
Construction Type(s): Type V -B
Total Bldg Area: I 0 sgft
Total Fire Area: I 0 sqft
Bldg Fire Flow: I 0 Gallons Per Minute (Light Hazard)
Describe Fire Area: (if more than one fire area, include an 8 112 x 11 or 11 x 17 drawing indicating the various fire areas)
Type of Occupancy or Use of Building:
_
A. Occupancy Hazard
Al Determine percent of each occupancy hazard in the fire area.
Occupancy Hazard Class Fire Area I Total Fire Area Percent of Fire Area
Light Hazard 0 SF / 1 SF x 100 = 0 %
Ordinary Hazard Grp 1 0 SF / 1 SF x 100 = 0 %
Ordinary Hazard Grp 2 0 SF / 1 SF x 100 = 0 %
Extra Hazard Grp 1 0 SF / 1 SF x 100 = 0 %
Extra Hazard Grp 2 0 SF I 1 SF x 100 = 0 %
Total Must equal 100% [ 0 %
A2 Calculate Fire Flow
Occupancy Hazard Class Factor Fire Area Fire Flow Bldg Fire Flow
Light Hazard 1.0 x 0 % x 0 GPM = 0 GPM
Ordinary Hazard Grp 1 1.2 x 0 % x 0 GPM = 0 GPM
Ordinary Hazard Grp 2 1.3 x 0 % x 0 GPM = 0 GPM
Extra Hazard Grp 1 1.4 x 0 % x 0 GPM = 0 GPM
Extra Hazard Grp 2 1.5 x 0 % x 0 GPM = 0 GPM
A3 Required Fire Flow 0 GPM
B. Minimum Number of Fire Hydrants Required
Required Fire Flow 0 = I 0 No. of Hydrants Required
C. Reduction of Fire Flow - Reductions are based on the following:
Cl - Reduced by 25% for all Group R Occupancies without fire sprinklers (multiply by .75)
C2 - Reduced by 25% for a NFPA 72 Fire Alarm System (multiply by .75)
C3 - Reduced by 75% for NFPA 13 Automatic Sprinklers (multiply by .25)
D. Required Fire Flow
D1 - Group R occupancy I No IX I 1 I = I 0 GPM (Max. 3000 - Min. 1500 gpm)
D2 - Fire Flow 0 GPM X I 1 = 1500 GPM (Max. 3000 - Min. 1500 gpm) I
E. Available Fire Flow to the Building Test Results: GPM
Manually enter available fire flow here. Please attach documentation of the flow test that was
made. It shall include date, time, location of static /residual and flow hydrants, and the tester's
name, phone number and address.