Loading...
Correspondence City of Tigard, Oregon 13125 SW Hall Blvd. • Tigard, OR 97223 April 19, 2007'.,. 1� �T RE: REPLACING, INSTALLING AND RELOCATING ROOF TOP UNITS ?� �s GA Project Information Building Permit: MEC2007 -00225 Construction Type: NA Tenant Name: Gohman Mechanical Occupancy Type: NA Address: 12006 SW Garden Pl. Occupant Load: NA Area NA Stories: NA The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. • espectfully, ) 0 4111111.... , D an Nelson, Senior Plans Examiner Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772