Tigard Assembly of God
FIRE ALARM DESCRIPTION
DESCRIPTION
An automatic fire protection system will be installed
utilizing a multi -zone control panel and providing for
monitoring of Pull Stations and Smoke Detectors.
The interior horn/strobe will be mounted at 84" to the bottom of the device.
The pull station will be mounted at 48" to the center of the device.
All audible devices will sound in the ANSI temporal pattern.
All strobe flashes will be synchronized where applicable.
Primary power to the panel shall be 110 vac power with a 24vdc 7ah battery back -up.
All fire alarm circuits will be wired with 16 gauge FPLR/CMR red cable with the
exception of NAC circuits, which will be wired with 14 gauge FPLR/CMR red cable.
Monitoring will be provided through Alarm Central Station, a U.L. listed monitoring company
(503.641.6761)
All installation will be done according to N.F.P.A. 72 standard.
Work will be performed in a neat and professional manner. All work will
be performed according to the timeline set.
All equipment will be UL listed and approved for the application.
SYSTEM COMPONENTS
Bosch D7024 24v Fire Control /Communicator FACP
System Sensor i3 Series 2 -wire Smoke Detector
Gentex Commander 3 CEG24 Horn/ Strobes
Fire -Lite BG -12L Pull Station
Wheelock 6" bell
D7024 24V Fire Control /Communicator
Specifications
Features t
Conventional Features
• Four conventional zone (expandable to eight) Fire
Alarm Control Panel (FACP) 1
• Built -in Digital Alarm Communicator Transmitter “'"'' "'"
(DACT)
• 4 Programmable authority levels
• Each detector zone supports up to 20 two -wire
smoke detectors
• Up to 18 programmable relay outputs
• 32 character backlit LCD display
• Supports up to four D7033 Fire System Controllers
and eight D7030X Series LED Annunciators
• Two Notification Appliance Circuits (NAC) on board D7024 Fire Control /Communicator
• Internal 24VDC, 4 amp NAC power supply
Programmable through front panel interface or A viewing port in the keyed panel enclosure door leaves
• remote D7033 Fire System Controller the system status LEDs and LCD display visible while
maintaining system control key security.
• 99 event history buffer Unlocking the enclosure door provides access to the
• Option Bus provides serial data interface for fire system keys for silencing alarm and trouble conditions,
alarm accessories zone bypassing, detector resetting, testing, and other
• UL Listed for fire applications fire functions as well as programming. These functions
• Compatible with RAM IV are also available on all D7033 Controllers connected to
• WheelockTM Signal Sync the system.
Multiplex Features D7039 All system controllers provide custom text annunciation
p ( ) on a 32 character, backlit, two -line LCD display. All
• Expandable to 255 addresses using multiplex system controllers also have built -in sounders. Back -
technology light intensity and sounder volume are programmable.
• Relay outputs expandable to 58 16 Personal Identification Numbers (PIN) are available
• 499 event history buffer for access to system control. Each number can be
PINs available for up to 100 system users assigned an authority level to limit system control
• functions that may be accessed.
• Compatible with RAM IV The system stores events in a 99 -event memory log.
Description The D7024 Communicator reports to two telephone
numbers with full single, double, and backup reporting
Conventional D7024 FACP and communicates in BFSK, SIA, Contact ID, Modem
The Radionics D7024 is a fully integrated FACP that IIIa and 4/2 and 3/1 Tone Bursts.
provides four zones and is capable of supporting both The D7024 enclosure has space for additional
two -wire and four -wire detectors. Each zone can accessory modules and two D1218 12V, 17 Ah batteries
support up to 20 two -wire detectors, or any number of or two D126 12V, 7 Ah batteries.
four -wire detectors (depending on available power). Multiplex Technology (D7039)
Two Notification Appliance Circuits (NAC) provides up The D7024 conventional system features can be
to 4 amps of 24 -volt power to operate horns, strobes, enhanced, when running version 2.02 or higher
bells, and other notification appliances. Each NAC can firmware with the addition of a D7039 Multiplex
be programmed to provide the WheelockTM Expansion Module. The D7039 expands the base
Synchronized Output. system up to 255 addressable points, increases the
System control can be accessed through a built -in user number of relay outputs to 58 and adds an additional
interface in the panel, or through the remote D7033 Fire 400 events to the history buffer for a total of 499 events.
System Controllers connected to the system. The D7039 also allows for up to 100 system users (an
addition of 84 PINs from the base system).
r:9 A member of the
r adionics Bosch Group
C O N V E N T I O N A L D E T E C T I O N
JI
Se Photoelectric SYSTE
Smoke Detectors SENSOR'
Models Available
Two-Wire Models
;4 ti
2W -B 2 -wire standard
2WT -B 2 -wire standard with thermal
Four -Wire Models ..
4W -B 4 -wire standard
4WT -B 4 -wire standard with thermal ;,•°
Accessories
2W -MOD2 2 -wire loop test /maintenance module
SENS -RDR Sensitivity reader fit • RT Removal /replacement tool,__
A77 -AB2 Retrofit adapter bracket -
�'
5
Product Overview
Plug -in detector line — mounting base System Sensor's i series smoke detectors represent a significant advancement in
included conventional detection. The 0 family is founded on three principles: Installation ease,
Intelligence, and Instant inspection.
Large wire entry port
Installation ease. The i line redefines installation ease with its plug -in design.
In -line terminals with SEMS screws This allows an installer to pre -wire the bases included with the heads. The large
Mounts to octagonal and single -gang wire entry port and in -line terminals provide ample room for neatly routing the
backboxes, 4-square backboxes, or wiring inside the base. The base accommodates a variety of back box mount -
direct to ceiling ing methods as well as direct mounting with drywall anchors. To complete
the installation, i heads plug -in to the base with a simple Stop -Drop 'N Lock
Stop -Drop 'N Lock'" attachment to base action.
Removable detector cover and chamber Intelligence. i detectors offer a number of intelligent features to simplify
for easy cleaning testing and maintenance. Drift compensation and smoothing algorithms are
standard with the i line, to minimize nuisance alarms. When connected to the
Built -in remote maintenance signaling 2W -MOD2 loop test/maintenance module, or a panel equipped with the i
protocol, 2 -wire i detectors are capable of generating a remote maintenance
Drift compensation and smoothing signal when they are in need of cleaning. This signal is indicated via an LED
algorithms located at the module and the panel. To read the sensitivity of i detectors, the
Simplified sensitivity measurement SENS -RDR is a wireless device that displays the sensitivity in terms of percent
per foot obscuration.
Wide angle, dual color LED indication Instant inspection. The i series provides wide angle red and green LED indica-
tors for instant inspection of the detector condition, indicating: normal standby,
Loop testing via EZ Walk feature
out -of- sensitivity, alarm, or freeze trouble conditions. When connected to the
Built -in test switch 2W -MOD2 loop test /maintenance module or a panel with the i protocol,
the EZ Walk loop test feature is available on 2 -wire i detectors. This feature
MEA MSFM verifies the initiating loop wiring by providing LED status indication at each
LISTED NSW approved approved d etector.
S911 3011446 7272- 1209:210 290-01 -E 2093
November 20, 2001 DF -52004 F -050
-12 FI re•LITee ALarms Manual A arm Stations
www.firelite.com Section: Conventional Initiating Devices
GENERAL California
M = State Fire
The Fire•Lite BG -12 Series is a cost - effective, feature- UL Marshal
packed, non -coded series of manual fire alarm pull sta- r ' US ^ �_ •
tions. It was designed to meet multiple applications with •,� 7150- 0075:184
the installer and end -user in mind. The BG -12 Series fea- LISTED eivicu
tures a variety of models including single- and dual- action S711
versions.
The BG -12 Series provides Fire•Lite Fire Alarm Control 4jr;
Panels (FACPs), as well as other manufacturers' controls,
with a manual alarm initiating input signal. Its innovative (except BG - 12LPS
design, durable construction, and multiple mounting op- 12LPSP)
tions make the BG -12 Series simple to install, maintain,
and operate.
FEATURES
• Aesthetically pleasing, highly visible design /color. F R
• Attractive contoured shape with light textured finish.
• Meets ADA 5 lb. maximum pull- force.
• Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
• Easily operated (single- or dual- action), yet designed to PUSH IN
prevent false alarms when bumped, shaken, or jarred.
• PUSH IN /PULL DOWN handle latches in the down po-
sition to clearly indicate the station has been operated.
• The word "ACTIVATED" appears on the top of the handle
in bright yellow, further indicating operation of the sta-
tion.
• Operation handle features white arrows showing basic
operation direction, for non - English- speaking persons.
• Braille text included in finger -hold area of operation
handle and across top of handle. Flreirm
• Multiple hex- and key -lock models available.
• U.S. patent - pending hex -lock needs only a quarter -turn
to lock/unlock.
• Station can be opened for inspection and maintenance
without initiating an alarm. • Switch contacts are normally open.
• Product ID label viewable by simply opening the cover; • Can be surface (with SB -10) or semi -flush mounted.
label is made of a durable long -life material. Semi -flush mount to a standard single -gang, double-
• The words "NORMAL" and "ACTIVATED" are molded gang, or 4" (10.16 cm) square electrical box.
into the plastic adjacent to the alarm switch (located in- • Backplate is large enough to overlap a single -gang
side). backbox cutout by up to 1/2" (12.7 mm).
• Four - position terminal strip molded into backplate. • Optional trim ring (BG -TR).
• Terminal strip includes Phillips combination -head cap- • Spanish version (FUEGO) available (BG- 12LSP).
tive 8/32 screws for easy connection to Initiating Device • Designed to replace the popular BG -10 Series.
Circuit (IDC). • Models packaged in attractive, clear plastic (PVC),
• Terminal screws backed -out at factory and shipped ready clamshell - style, Point -of- Purchase packages. Packag-
to accept field wiring (up to 12 AWG /3.25 mm ing includes a cutaway dust /paint cover in shape of pull
• Terminal numbers are molded into the backplate, elimi- station.
nating the need for labels.
This document is not intended to be used for installation purposes. We try to keep our O 9001
product information up -to -date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact Fire•Lite Alarms, One Fire -Lite Place, Northford, Connecticut C E R T I F I E o
06472. Phone: (800) 627 -3473, Toll Free FAX: (877) 699 -4105, FAX Back:(888) 388- ENGINEERING &MANUFACTURING
3299. Made in the U.S.A.
DF -52004 — Page 1 of 2
•
e.�
GENTS C
CORPORATION
!Barter
y
Commander Series Selectable GEC3 /GES3
Candela Evacuation Signals 12 & 24 VDC
Applications S E R I E S
The Commander Series is a low profile strobe or horn /strobe combination that
offers dependable audible and visual alarms and the lowest current available.
The GE3 Series 24VDC offers tamperproof field selectable candela options of
15, 30, 60, 75, and 110 candela. The 12VDC offers tamperproof field selectable
candela options of 15, 30, 60, and 75 candela. (`` l
The Commander Series horn offers a continuous or synchable temporal three in
2400Hz and mechanical tone, a chime and whoop tone. All tones are easy for i f.
the professional to change in the field by using switches.
The GE3 Series has a minimal operation current and has a minimum flash rate
of 1Hz regardless of input voltage.
Product Listings
The Commander Series is shipped with the standard 4" mounting plate which
incorporates the popular Super- Slide feature that allows the installer to easily
test for supervision. The product also features a locking mechanism which *; C US
secures the product to the bracket without any screws showing.
APPROVED
,_..�__.� (t` lg x910 {Y :fl'!Y s oar w t.Tl6 fikLXlx a 1
The Commander also features the Checkmate - Instant Voltage Verification `� °`° " "`i`'a5 "•"� "T�
feature which allows the installer to check the voltage drop draw and match it to BFP (City of Chicago)
the blueprint. • CSF�E35 0569:122 (GEC3 -24 & GEH -24)
7125 - 0569:123 (GES3 -24)
The GE3 Series appliances are UL 464 and UL 1971, listed for use with fire pro- 7125 - 0569:129 (GES3 -12)
tective systems and are warranted for three years from date of purchase. 7135- 0569:130 (GEC3 -12 & GEH -12)
Standard Features • FM Approved
• UL 464 & UL 1971 Listed
• Nominal Voltage 12 & 24 VDC • CAN /ULC S526 -M87 Listed
• 24 VDC units have field selectable candela options of ULSZ7.S3406 Listed (GEC3 -24,
15, 30, 60, 75, and 110 candela GEH24 & GEH12)
• 12 VDC units have field selectable candela options of Product Compliance
15, 30, 60, and 75 candela • NFPA 72
• GEH horn is available in 12 or 24 Volt • Americans with Disabilities Act (ADA)
• Super- Slide Bracket - Ease of Supervision Testing
• Checkmate - Instant Voltage Verification
• Unit Dimensions: 5" high x 4.5" wide x 2.5" deep MEMBER ,w
A„4fiEM92.EC M
• Synchronize Strobe and /or Horn with Gentex Series The USA
Control Module (12 Volt product must use the AVSM • Switch for Continuous or Temporal 3 (not available on
Module) whoop tone)
• Prewire Entire System, Then Install Your Signals • Surface Mount with the GSB (Gentex Surface
• Lower Installation and Operating Costs Mount Box)
• Input Terminals 12 to 18 AWG • Silence Horn While Strobes Remain Flashing
• Switch Selection for High or Low dBA • Wide Voltage Range 8 -17.5 VDC (12 Volt Models)
• Switch for Chime, Whoop, Mechanical and 2400Hz Tone 16 -33 VDC or FWR (24 Volt Models)
• Tamperproof Re- entrant Grill • Faceplate Available in Red or Off -White
Mounting Super- SlideTM Switch Locations
SWITCH POSITION
ti��. ..�- -- " 3 4 5
� y h9oMmlwbTerry. ON ON ON
j ;I rt M echanirt4Cont OFF ON ON
HsTCmp pN OFF ON
�% F 'y ow HTCont OFF OFF ON
I Ch in*Cont me Temp ON ON OFF
►t Ch OFF ON OFF
�� Y` ;� .� 1 rli tI L so 9 Wfi000 OFF OFF OFF
1 w �� Svdtoh Position 6
� tt ON > HIGH dB
LL r
� � i ((` X'1 ' ) �.. OFF> LOW d8
flT[ll[ ' iI?� t r 1 � ' Swi tch positions 1 and 2
/ In the off posltlon to select
\ \\ (f430 � P ±, ��" =`I r�-A isolated horn and strobe
-s
- "melt , .
t l=' �4 power inputs 1. umi y • It' 1 t r kl
Die Cast Metal Mounting Plate: Mounts to single gang, ° . 1' , R Q
double gang 4" square boxes or GSB box. 'fir' lira ON � 11
�' :i ?�
ChCheckmate' - Instant Voltage Verification et� .I
r
-,,, „, 1 2 3 4 5 6
7 . ' — '
r ^,
_ ,,,,,,,,,,„,_„\,
liti Candela Selection
ir I t. I
., ,
+ .........,
s. .
,,,..... -
!L 1
1 Candela selection sli fllffl sw itch Depress center
c � � `' ', a sli 9 switch doslrod ✓ -
L ' brl hfness level. !' °��
111 t.�l! � j 11 i~_�. ��
ur
p* /
The access holes are provided in the back of the terminal Break off pin and insert into A KA
hole at t bottom of the ■ ,r1 { ,
block to allow the voltage to be measured directly without selector to lock candela setting. 101
removing the device. Typically this would be done at the Signal must be removed from 1yi I
bracket and pin pushed forward .+ \� II II '
I 0
end of the line to confirm design criteria. Most measure- from backside «n of hole s 1 .�
.
ments will be taken using the S+ and S- locations lo change canders. 5i 1" J�1,
although access is provided to other locations. NOTE: ° ^
0') ., 1
Care should be taken to not short the test probes, I r .
Conventional GES3 /GEC3 Series Wiring Diagrams
UL Listed UL Listed
Control Control Signal Signal
Signal Signal Panel
S+ S+ S H+ H S+ S+ S H+ H-
S+ S+ S - H+ H- S+ S+ S- H+ H-
Supervised j kS ° 8 E Ea
- Supervised IS S S ® ® 0.%. O O. 0 B Signal Circuit „I;" „I"'
Signal Circuit " END OF LINE \ O I"' II END LINE
O / IS OR
RES STOR
\ RESISTOR 0 II '1
END Of LINE
RESISTOR
0
Wiring Diagram GE3 Series with Gentex Synchronization Module
F.A.C.P.
ENO LINE Cs RE TO q oR Tp NEXT SIGNAL TO NOTIFICATION ALARM CIRCUIT
cuss WSW ONLY. TO NEXT SIGNAL ; ID,&T
TO NOTIFICATION ALARM CIRCUIT
REMOVE JUMPER
FOR INDEPENDENT
SYNCHRONIZED STROBE
AUDIBLE SIGNAL+ + END OF IwE AND HORN OPERATION NE° 01 'n "'a' '�' 01Rf
RESISTOR FOR
CIRCUIT , aassa LEAVEJUMPERINPLACE SYNCHRONIZATION
WTI wwwO ONLY. LEAVE
ELIMINATE NEED FOR MODULE
LEAVE JUMPER IN PLACE ON
HORN INPUT ON AVSM
® e SLAVE UN ITS UNLESS SEPARATE
AND OPERATE SIGNAL CO OVER HORN CRT
IN UNISON MODE z z3 IS REQUIRED.
SYNCHRONIZATION
MODULE Send Signal
So S0 0- HO H- S+ 5o 5- Ha H-
00ioo _ 19s9sel is sss of ^^77
VISIBLE SIGNAL ID + •• I I .0' ' # RESISTOR FOR
CIRCUIT 0. I a.rsse
4s' A r I Ar WIRING ONLY
I 1 1
1 1 1 1
REN Or L FOR " 11
CLASS
WIRING ONLY. f I
Note: See Technical Bulletin 015 for proper synchronization module for application.
Note: When synchronizing the GE3 12 VDC Series, the AVSM synchronization module MUST be used.
Architect & Engineering Specifications:
The audible and /or visible signal shall be Gentex GE3 Series or approved equal and shall be listed by Underwriters Laboratories Inc. per UL
1971 and /or UL 464. The notification appliance shall also be listed with the California State Fire Marshal (CSFM) and the Bureau of Standards and Appeals
(NYC).
The notification appliance (combination audible/visible) shall produce a peak sound output of 100dBA or greater at 12 or 24V as measured in an ane-
choic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of
a single pair of power wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the abil-
ity to be synchronized.
Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm
control panel.
The audible /visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2 Hz regardless of power input voltage.
The appliance shall have an operating current of 55mA or less at 24 VDC for the 15Cd strobe circuit and 106mA or less at 12 VDC for the 15Cd strobe circuit.
The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with termi-
nals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.
The unit shall have an input voltage range of 16 -33 volts with either direct current of full wave rectified power for 24 volt models or a voltage range of 8 -17,5
volts for 12 volt models.
The appliance shall be capable of testing supervision without disconnecting wires. Also the appliance shall be capable of mounting to a surface back
box. The unit shall also be able to verify voltage at the unit without removing unit.
24 units per carton
28 pounds per carton
Important Notice,
G E N T E X These materials have been prepared by Gentex Corporation ('Centex') for informational purposes only, are 551 - 0050 -02
necessarily summary• and are not purported to servo as legal advice and should not be used as such.
Gentex makes no representations and warranties, express or implied, that these materials are complete
CORPORATION and accurate, up -to -date, or in compliance with all relevant local, state and federal laws, regulations and
rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding
Interpretation of laws, regulations and rules and the application of such laws, regulations and rules to panic-
Fire Protection Products: vwvw. gentex. corn ular tact patterns. Each person's activities can differently affect the obligations that exist under applicable
laws, regulations or rules. Therefore. these materials should be used only for informational purposes and
10985 Chicago Drive Box 310 • Zeeland, Michigan 49464 should not be used as a substitute for seeking professional legal advice. Gentex will not be responsible for
616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax any action or failure to act in reliance upon the information contained in this material.
Gentex curpuration Iesrrves Uc riyln Is hake Lhanyes to L!e, Vruduct date silents at h Eir dserebw,. (' Printed un Recycled Paper
whe lock ILUI`'J
{ l e k a P. l 4;4s
S
0 ' % r `
{.� D if{ .I ll'l:N'1 11 ISl!'.• MI NI
• Helping People Take Action
SERIES MB MOTOR BELLS
Description
Wheelock's Series MB Motor Bells provide a better engineered motor
bell for fire and life safety alarm systems. The Wheelock Series MB,'
Bells include higher dBA, low current draw, built -in trimplate for
semi -flush mounting, low frequency aluminum shells, and low RFI
noise. The motor for Series MB Bells is a durable, high torque W
permanent magnet motor selected for its high performance and long
life.
These DC vibrating Series MB Motor Bells are offered in 6" and 10" SERIES MB
shell sizes in both 12 and 24 VDC models.
Series RSSP Sync /Non -Sync retrofit plates are used in conjunction
with the Series MB Motor Bell when combination appliances are „
required. The Series RSSP retrofit plates are available with either '
Multi - Candela or single candela strobes and easily mount to a 4" k ,.).»z
square or Wheelock SBL -2 backbox. All Series RSSP strobe �;
appliances meet or exceed the requirements of NFPA 72 (National Fire
Alarm Code), ANSI 117.1 (American National Standard for
Accessible and Usable Buildings and Facilities), ADA (Americans with ' ,• A
Disabilities Act) and UL Standard 1971 (Signaling Devices for the fi r ;
Hearing Impaired).
The Series RSSP retrofit plates may be synchronized when installed
with the Wheelock Series SM, DSM, Sync Modules or the PS- 12/24 -8 (`s
. ,,
- Power Supply with Wheelock's patented sync protocol. Wheelock's N»,
synchronized strobes offer an easy way to comply with ADA....:
requirements concerning photo- sensitive epilepsy. REMOTE PLATE with SBL -2
Features RSSP REMOTE PLATE
• Approvals include: UL Standard 464, Factory Mutual (FM), • Built -in trimplate makes semi -flush mounting
California State Fire Marshal (CSFM), New York (MEA) and simpler and less expensive.
Chicago (BFP). • Screw terminals permit fast in -out field wiring of
• Meets OSHA 29 Part 1910.165. #12 to 18 AWG wire.
• High sound output with low current draw. • Polarized for DC supervision of NAC circuits.
• Low frequency aluminum shells for better audibility • Operates on filtered or unfiltered DC.
through walls, doors and other structures. • For combined audible (bell) and visual signaling,
• 6" and 10" shell sizes in 12 or 24 VDC models. convenient retrofit plate assemblies are available
• Integral RFI suppression to minimize included noise on with Multi - Candela or Single candela strobes
the NAC circuit. (Refer to Fire Alarm Products Catalog for Series
• Mounting options for surface, semi - flush, outdoor, and RSSP Sync /Non -Sync Strobes specifications and
concealed conduit installation. technical information).
Ordering Information
Model Number Order Code Shell Size Input Voltage Input Current dBA @ 10 Ft. Mounting NOTES:
(VDC) Options 1. Typical dBA at 10 feet
is measured in an
MB G6 - 12 - R 3942 6" 12 0.060 anechoicchamber.
- 2. For bells all 12 VDC
MB G6 - 24 - R 3941 6" 24 0.030 models are UL rated for
92 D,E,J,K,N,R,S,Z 9,0 to 15.6 VDC and all 24
MB- G10 -12 -R 3944 10" 12 0.060 VDC models for 18.0 to
MB- G10 -24 -R 3943 10" 24 0.030 31.0 VDC.
-
Copyright 2002 Wheelock, Inc. All rights reserved.