Plans PaaD5 D6/cZ
//96 rd 5. 6/1, 7
Hydraulics Summary Sheet
AFP Systems, Inc. ..
Designer: R ilECE,VE
19435 SW 129th Ave. Tualatin Or 97062 Calc By: R y an Cole
Date: ISEP 2 9 2005
CITY OF IUD
Project Information
Information
VESTA
1 '950 SW GARDEN PLACE Demand...
TIGARD,OR Spr Req'd Pres: 52.00 PSI
Spr Req'd Flow: 258.10 GPM
Add'I Flows: 0.00 GPM
Hose at Srce: 150.00 GPM
Contract No: Total Flow: 408.10 GPM
Building:
Total Pres: 52.00 PSI
System ID: Static Elev: 0.00 Ft
Ref. Drawing No: 1 OF 1
Construction: STL. Supply...
Occupancy: NFPA 13 Water Flow Test
Static: 95.00 PSI
Authority: CLAKAMAS COUNTY Residual: 55.00 PSI
Qty Flowing: 1940.00 GPM
Elevation: 0.00 Ft
System Information System Type: PRE - ACTION Date:9 -23 -0S Time:11:00AM
By: AFP /TIGARD WATER DEPT.
Hydraulics Design Criteria Pump Data
Density: .10 GPM /SqFt Rated: 0.0 PSI@ 0.0 GPM
Remote Area: 1500 SqFt Boost Pres: (NA) PSI
Sprinkler Coverage: 130 SqFt Discharge Pres: (NA) PSI
Design Standard: NFPA 13 99 Discharge Flow: (NA) GPM
Hazard: LIGHT
•
Figure: Curve: Combined
Static: (NA) PSI
Residual: (NA) PSI
Sprinklers / Nozzles
Qty Flowing: (NA) GPM
Manufacturer: VIKING
Model: M
Size: 1/2 Available...
P) 92.76 PSI@ 408.10 GPM
K— Factor: 5.6 F) 52.00 PSI@ 2017.21 GPM
Temp. Rating: 155
Commodity Storage
Commodity: Strg Meth: Margin...
Class: Location: Pressure: 40.76 PSI
Area: Aisle Wid: Flow: 1609.10 GPM
Storage Ht: Solid Piled% Palletized%
Sigma Dynamics Corporation
Racks 7700 Summary Sheet
Rack Type: Encapsulation?
Horizontal Barriers:
Flue Spacing Longitudinal: Transverse:
r
F
SUBMITTAL SERIAL NO:2386HY1 09 -26 -2005 PAGE 4
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
10 11DQ 46.96 2.157 L 11.00 C =120 PT 8.11 ( 11)
Q 122.84 F =T F 8.50 PE 0.00
FM T 19.50 0.1117 PF 2.18
-5 10DQ 135.27 2.157 L 15.00 C =120 PT 10.29 ( 10)
Q 258.10 F =E F 3.50 PE 5.20
FM T 18.50 0.4412 PF 8.16
4 5 2.157 L 20.00 C =120 PT 23.65 ( 5)
Q 258.10 F =T,4E F 22.50 PE -5.20
FM T 42.50 0.4412 PF 18.75
3 4 3.260 L 28.00 C =120 PT 37.20 ( 4)
Q 258.10 F =T F 13.00 PE 0.00
FM T 41.00 0.0590 PF 2.42
2 3 4.260 L 175.00 C =120 PT 39.62 ( 3)
Q 258.10 F =T,4E F 43.20 PE 0.00
FM T 218.20 0.0160 PF 3.49
1 2 4.260 L 15.00 C =120 PT 43.11 ( 2)
Q 258.10 F= T,E,DCA F 22.80 PE 6.50
FR T 37.80 0.0160 PF 0.60
4" Ames Mod. 2000ss - Double Check Valve Assembly 1.57
0 1 6.340_ L 50.00 C =140 PT 51.79 ( 1)
Q 258.10 F =T,2E F 64.00 PE 0.00
UN T 114.00 0.0017 PF 0.19
PT 51.98 ( 0)
A
0
SUBMITTAL SERIAL NO:2386HY1 09 -26 -2005 PAGE 3
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
105 104 1.682 L 15.00 C =120 PT 7.29 (104)
Q 15.12 F =0 F 0.00 PE 0.00
BN T 15.00 0.0078 PF 0.12
12 105DQ 15.24 1.682 L 5.50 C =120 PT 7.41 (105)
Q 30.37 F =T F 6.40 PE 0.00
BN T 11.90 0.0283 PF 0.34
PT 7.75 ( 12)
107 106 1.682 L 15.00 C =120 PT 7.64 (106)
Q 15.48 F =0 F 0.00 PE 0.00
BN T 15.00 0.0081 PF 0.12
11 107DQ 15.60 1.682 L 5.50 C =120 PT 7.76 (107)
Q 31.08 F =T F 6.40 PE 0.00
BN T 11.90 0.0295 PF 0.35
PT 8.11 ( 11)
11 116 1.682 L 2.00 C =120 PT 8.04 (116)
Q 15.88 F =T F 6.40 PE 0.00
BN T 8.40 0.0085 PF 0.07
PT 8.11 ( 11)
16 17 2.157 L 10.00 C =120 PT 9.27 ( 17)
Q 33.22 F =0 F 0.00 PE 0.00
FM T 10.00 0.0099 PF 0.10
15 16DQ 33.40 2.157 L 7.00 C =120 PT 9.37 ( 16)
Q 66.63 F =0 F 0.00 PE 0.00
FM T 7.00 0.0360 PF 0.25
14 15DQ 33.85 2.157 L 7.00 C =120 PT 9.62 ( 15)
Q 100.48 F =0 F 0.00 PE 0.00
FM T 7.00 0.0770 PF 0.54
10 14DQ 34.79 2.157 L 1.00 C =120 PT 10.16 ( 14)
Q 135.27 F =0 F 0.00 PE 0.00
FM T 1.00 0.1335 PF 0.13
PT 10.29 ( 10)
12 13 2.157 L 7.00 C =120 PT 7.62 ( 13)
Q 45.51 F =0 F 0.00 PE 0.00
FM T 7.00 0.0178 PF 0.12
11 12DQ 30.37 2.157 L 8.00 C =120 PT 7.74 ( 12)
Q 75.88 F =0 F 0.00 PE 0.00
FM T 8.00 0.0458 PF 0.37
;a
'
SUBMITTAL SERIAL NO:2386HY1 09 -26 -2005 PAGE 2
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
102 101 1.682 L 15.00 C =120 PT 7.17 (101)
Q 15.00 F =0 F 0.00 PE 0.00
BN T 15.00 0.0077 PF 0.12
13 102DQ 15.12 1.682 L 5.50 C =120 PT 7.29 (102)
Q 30.12 F =T F 6.40 PE 0.00
BN T 11.90 0.0278 PF 0.33
PT 7.62 ( 13)
115 114 1.682 L 15.00 C =120 PT 8.73 (114)
Q 16.55 F =0 F 0.00 PE 0.00
BN T 15.00 0.0092 PF 0.14
17 115DQ 16.68 1.682 L 5.50 C =120 PT 8.87 (115)
Q 33.22 F =T F 6.40 PE 0.00
BN T 11.90 0.0334 PF 0.40
PT 9.27 ( 17)
113 112 1.682 L 15.00 C =120 PT 8.83 (112)
Q 16.64 F =0 F 0.00 PE 0.00
BN T 15.00 0.0093 PF 0.14
16 113DQ 16.77 1.682 L 5.50 C =120 PT 8.97 (113)
Q 33.40 F =T F 6.40 PE 0.00
BN T 11.90 0.0337 PF 0.40
PT 9.37 ( 16)
111 110 1.682 L 15.00 C =120 PT 9.06 (110)
Q 16.86 F =0 F 0.00 PE 0.00
BN T 15.00 0.0095 PF 0.14
15 111DQ 16.99 1.682 L 5.50 C =120 -PT 9.20 (111)
Q 33.85 F =T F 6.40 PE 0.00
BN T 11.90 0.0346 PF 0.41
PT 9.61 ( 15)
109 108 1.682 L 15.00 C =120 PT 9.57 (108)
Q 17.33 F =0 F 0.00 PE 0.00
BN T 15.00 0.0100 PF 0.15
14 109DQ 17.46 1.682 L 5.50 C =120 PT 9.72 (109)
Q 34.79 F =T F 6.40 PE 0.00
BN T 11.90 0.0364 PF 0.43
PT 10.15 ( 14)
13 103 1.682 L 2.00 C =120 PT 7.55 (103)
Q 15.39 F =T F 6.40 PE 0.00
BN T 8.40 0.0080 PF 0.07
PT 7.62 ( 13)
A
I
SUBMITTAL SERIAL NO:2386HY1 09 -26 -2005 PAGE 1
FLOW TEST RESULTS
Water Supply
STATIC 95.00 PSI
RESIDUAL 55.00 PSI @ 1940.00 GPM
CITY PRESSURE AVAILABLE AT 408.1 GPM 92.76 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K- FACTOR PRESSURE
101 15.00 15.00 5.60 7.17
102 15.12 15.00 5.60 7.29
103 15.39 15.00 5.60 7.55
104 15.12 15.00 5.60 7.29
105 15.24 15.00 5.60 7.41
106 15.48 15.00 5.60 7.64
107 15.60 15.00 5.60 7.76
108 17.33 15.00 5.60 9.57
109 17.46 15.00 5.60 9.72
110 16.86 15.00 5.60 9.06
111 16.99 15.00 5.60 9.21
112 16.64 15.00 5.60 8.83
113 16.77 15.00 5.60 8.96
114 16.55 15.00 5.60 8.73
115 16.68 15.00 5.60 8.87
116 15.88 15.00 5.60 8.04
TOTAL WATER REQUIRED FOR SYSTEM 258.10 GPM
OUTSIDE HOSE STREAMS AT 0 150.00 GPM
TOTAL WATER REQUIREMENT 408.10 GPM
PRESSURE REQUIRED AT 0 52.00 PSI
MAXIMUM PRESSURE UNBALANCE IN LOOPS 0.00 PSI
MAXIMUM VELOCITY FROM 4 TO 5 22.66 FPS
Sigma Dynamics Corporation
VESTA 7700 Supply / Demand Graph
125
120
115 Margin
Pressure 40.76 PSI
110 Flow 1609.10 GPM
105
100
95°
90
85
80
75
w 70
a
a , 65
g 60
a 50 i. °o
45
40
35 1
30
m
25
2 '
1
10
5
N 1.85
o 250 500 750 1000 1250 1500 1750 2000 2250 2500
Water Flow (GPM)
System Demand.. Water Supply..
Sprinkler Demand 52.00 PSI @ 258.10 GPM Static 95.00 PSI
Additional Flows 0.00 GPM Residual 55.00 PSI @ 1940.00 GPM
Hose at Source 150.00 GPM Elevation 0.00 PSI
Total Demand 52.00 PSI @ 408.10 GPM
. ft' June 17, 2005 Sprinkler 11 a , .
• NI KING _ ® SEP RI .. ff! ATIC AND
TECHNICAL. DATA �MicromaticHP STANDARD
P�LS
1. PRODUCT NAME
Viking Micromatic Model M and Micro- 4, ,
- maticHP® Model M Standard Response . _ ,
Sprinklers �; <a
•
,- 0 . 7 . . ,
• Available Styles: Upright, Pendent, and .,
Conventional
2. MANUFACTURER ' 'i
The Viking Corporation I
210 N. Industrial Park Road •.�>
Hastings, Michigan 49058, U.S.A.
Telephone: (269) 945 -9501 Upright Pendent Conventional
(877) 384 -5464 Sprinkler Temperature Nominal Sprinkler Temperature Max. Ambient Bulb
Fax: (269) 945 -9599 Classification Rating (Fusing Point) Ceiling Temperatures Color
e -mail: techsvcs @vikmgcorp.com Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
3. PRODUCT DESCRIPTION Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
Viking Micromatic® and MicromaticHP® Intermediate 212 °F (100 °C) 150 °F (65 °C) Green
Standard Response Sprinklers are small High 286 °F (141 °C) 225 °F (107 °C) Blue
thermosensitive spray sprinklers available Extra High 360 °F (182 °C) 300 °F (149 °C) Mauve
in several finishes, temperature ratings, Ultra High 500 °F (260 °C) 465 °F (240 °C) Black
and orifice sizes to meet design require- Sprinkler Finishes: Brass, Chrome- Enloy ®, White Polyester (White Poly finish for Sprinkler
ments. The small frame and 5 mm glass Base Part Nos. 10138, 10139, 10141, 10173, and 10220), Black Polyester (Black Poly finish
bulb provide a pleasing appearance Used for Sprinkler Base Part Nos. 10138, 10139, and 10173), and Black Teflon®
in conjunction with one of the various corro- Corrosion - Resistant Coatings White Polyester (White Poly finish for Sprinkler Base Part
sion- resistant coatings, the units provide Nos. 10138, 10139, 10141, 10173, and 10220 only), Black Polyester (Black Poly finish for
protection against many corrosive environ- Sprinkler Base Part Nos. 10138, 10139, and 10173), and Black Teflon® in all temperature rat -
ments. In addition, the Polyester finishes rags. Wax- Coated Brass and Wax over Polyester finish for sprinklers with the following
and Teflon coating can also be used in temperature ratings:
decorative applications where colors are 155 °F (68 °C) Lt. Brown Wax 200 °F (93 °C) Brown Wax 286 °F (141 °C) Dk. Brown Wax
desired. 175 °F (79 °C) Brown Wax 212 °F (100 °C) Brown Wax
During fire conditions, the heat - sensitive 1 Based on NFPA -13. Other limits may apply, depending on fire loading, sprinkler location, and
liquid in the glass bulb expands, causing other requirements of the Authonty Having Jurisdiction. Refer to specific installation standards.
er, releasing the pip cap The temperature rating is stamped on the deflector
the bulb t o shatter, cp 2
and sealing The corrosion - resistant coatings have passed the standard corrosion test required by the ap-
g s at P g assembly. Waterflp c a y g proving agencies indicated on pages 11 b -d. These tests cannot and do not represent all
through the sprinkler orifice strikes the possible corrosive environments. Prior to installation, verify through the end -user that the
sprinkler deflector, forming a uniform spray coatings are compatible with or suitable for the proposed environment. For automatic sprin-
pattern to extinguish or control the fire. klers, the coatings indicated are applied to the exposed extenor surfaces only. Note that the
Viking Standard Response Glass -Bulb Style spring is exposed on spnnklers with Poly finishes and Teflon coatings. For Teflon coated
Spnnklers may be ordered and/or used as 4 open sprinklers only, the waterway is coated.
open spnnklers (glass bulb and pip cap as- Sprinklers of Ultra -High temperature rating are intended for use inside ovens, dryers, or simi-
sembly removed) on deluge systems. lar enclosures with normal operating temperatures above 300 °F (149 °C). Where the ambi-
ent temperature around the Ultra -High temperature rated sprinkler is significantly reduced
4. TECHNICAL DATA 5 below 300 °F (149 °C), response time may be severely retarded.
Wax Over Polyester unavailable for Sprinkler Base P /Ns 09992, 09993, 09994, and 09995.
LISTINGS AND APPROVALS '
Refer to the charts on pages 11 b -d. SPRINKLER MATERIALS Pip Cap and Insert Assembly for all other
Spacing Requirements Max. spacing 15 Frame: Brass Castings UNS- C84400 Sprinkler Part Nos: Copper UNS- C11000
ft (4,6 m , min. spacing 6 ft. (1,8 m . and Stainless Steel UNS- S30400
( ) P 9 ( ) Deflector: Brass UNS- C51000 or Copper
Glass bulb fluid temperature rated to -65 °F UNS- C19500 for Sprinklers 10139, Pip Cap Attachment: Brass UNS- C36000
( -55 °C). 10142, 10170, 10173, 10223, and Ejector Spring (Part Nos. 12105 and
-
S rin U.S.A. Patent No. 4,167,974 12106). Stainless Steel
Min. Operating Pressure 7 ,3 kPa ) kler Copper UN Base Part Nos. 1 10 133 for 8, 10141, 141, Sprinklers with Teflon Coating
psi ( 48 kler 10138,
RATED WATER WORKING PRESSURE 10169, 10174, 10187, 10190, 10193, Belleville Spring Sealing Assembly: Ex-
Sprinklers 09992, 09993, 09994, and 10220, 10233, and 12106. Brass posed
Screw: Nickel plated
09995 are rated for use with water
UNS- C26000 for all other Part Nos. Pip Cap: Teflon Coated
working pressures ranging from the Bushing (for Sprinkler Base Part Nos. Sprinklers with Poly Finishes
minimum 7 psi (48,3 kPa) up to 250 09994, 09995, 10188, 10189, 10191, Belleville Spring Sealing Assembly: Ex-
psi (1 724 kPa) for high - pressure sys- 10192, 10218, 10219, 10221, and posed
tems. High - pressure (HP) sprinklers 10222): Brass UNS- C36000 AVAILABLE FINISHES
can be identified by locating "250" Bulb. Glass, nominal 5 mm diameter Brass, Chrome - Enloy® (patents pending),
stamped on the deflector. Belleville Spring Sealing Assembly: Nickel White Polyester (White Poly finish for
All other Part Nos. not mentioned above Alloy, coated on both sides with Teflon Sprinkler Base Part Nos. 10138, 10139,
are rated to a maximum 175 psi (1 207 Tape 10141, 10173, and 10220), Black Polyes-
kPa) wwp. Screw: Brass UNS- C36000 ter (Black Poly finish for Sprinkler Base
Factory tested hydrostatically to 500 psi (3 Pip Cap for Sprinklers 09992, 09993, Part Nos. 10138, 10139, and 10173), and
448 kPa). 09994, 09995, and 10221: Bronze Black Teflon® in all temperature ratings;
UNS- C31400 or UNS- C31600 Wax- Coated Brass or Wax over Polyes-
Note: Units of measure in parentheses may be approximations. Replaces page 11 a -d, dated April 15, 2005 (updated FM Approval for
Form No. F 100397 Sprinkler VK102). Refer to technical data page SR1 -2 for general
care, installation, and maintenance information.
•
t
/ .
Sprinkler 11 b June 17, 2005
NII(ING ® MICROMATIC AND
. " TECHNICAL DATA MicromaticHP ® STANDARD
RESPONSE SPRINKLERS
Approval Chart Temperature KEY
Micromatic Standard Response Pendent Sprinklers Finish
- Maximum 175 PSI WWP Al
Standard Orifice
Thread Max. Sprinkler Description Nominal Overall Listings and Approvals
Size Pressure K- Factor Length
NPT BSP PSIG Style Base Part SIN U.S. metric Inch mm cULus FM NYC VdS LPCB
Number
' / z " 15 mm 175 Pendent 10139 VK102 5 6 8,1 2 -3/16 56_ B2, D9, E 1 1 , F7 A5, C10, F5 B2, D9, E11 B5 B2, D9
- 15 mm 175 Pendent 10173 VK102 5 6 8,1 2 -3/16 56 B2, D9, E11, F7 A5, C10, F5 B2, D9, E11 B5 B2, D9
Large Orifice
' / z " 15 mm 175 Pendentl 10223 VK202 8.0 1 1 , 5 2 -3/8 60 B1, D8, E 1 1 , F7 B7, D10, F7 B1, 08, E11 - -
%" 20 mm 175 Pendent 10142 VK202 8 0 1 1 , 5 2 -5/16 59 B 1 , D8, E 1 1 , F7 B7, D10, F7 B1, D8, El1 - B4, D8
- 15 mm 175 Pendent 10187 VK202 8.0 1 1 , 5 2 -3/8 60 B 1 , D8, E 1 1 , F7 C10 - - -
- 20 mm 175 Pendent 10170 VK202 8 0 1 1 , 5 2 -3/8 60 B1, D8, E11 C10, A7 - - _ B7, D3
3 /4" 20 mm 175 Pendent 12105 VK202 8 0 11,5 2 -3/16 56 - - - A4 -
Small Orifice
%" 15 mm 175 Pendent 10221 VK003 2.8 4,0 2 -3/16 56 B1, 08, El1 B7, D10 - - -
/z" 15 mm 175 Pendent 10222 VK004 4 2 6,0 2 -1/4 58 B1, D8, E11 - - - -
- 10 mm 175 Pendent 10175 VK004 4.2 6,0 2 -1/4 58 - - - B4 67, D3
- 15 mm 175 Pendent 10188 °,12 VK004 42 6,0 2 -1/4 58 61, D8, El1 - - - -
- 15 mm 175 Pendent 10189 ° ,12 VK003 2 8 4,0 2 -3/16 56 B1, D8, El1 B7, D10 - - -
Installed with the Viking Micromatic Model E -1 or E -2 Recessed Escutcheon"
' /z" 15 mm 175 Pendent 10139 VK102 5 6 8,1 2 -3/16 56 D2 C5 D2 D5 D2
_ %" 15 mm 175 Pendent 10223 VK202 8.0 11,5 2 -3/8 60 D1 D7 D1 - -
' /z" 15 mm 175 Pendent 10221 VK003 2 8 4,0 2 -3/16 56 D1 C7 D1 - D1
'/z" 15 mm 175 Pendent 10222 VK004 4.2 6,0 2 -1/4 58 D1 - D1 - D1
/ ,," 20 mm 175 Pendent 10142 VK202 8 0 11,5 2 -5/16 59 D1 D7 D1 - D4
- 15 mm 175 Pendent 10173 VK102 5.6 8,1 2 -3/16 56 D1 C7 - - D1
- 20 mm 175 Pendent 10170 VK202 8 0 11,5 2 -3/8 60 D1 D7 - - D1
'4" 20 mm 175 Pendent 12105 VK202 8.0' 11,5 2 -3/16 56 - - - D4 -
Installed with the Vikinq_Microfast Model F -1 Adjustable Escutcheon
' /z" 15 mm 175 Pendent 10139 VK102 5.6 8,1 2 -3/16 56 D2 - D2 E5 D2
'/z" 15 mm 175 Pendent 10223 VK202 8.0 11,5 2 -3/8 60 D1 _ - D1 - -
%" 15 mm 175 Pendent 10221 VK003 2 8 4,0 2 -3/16 56 D1 - D1 - D1
' /z" 15 mm 175 Pendent 10222 VK004 4.2 6,0 2 -1/4 58 D1 - D1 - 01
'/." 20 mm 175 Pendent 10142 VK202 8.0 11,5 2 -5/16 59 D1 - D1 - D4
- 15 mm 175 Pendent 10173 VK102 5 6 8,1 2 -3/16 56 - - - - D1
- 20 mm 175 Pendent 10170 VK202 8.0 11,5 2 -3/8 60 - - - . - D1
' /." 20 mm 175 Pendent 12105 VK202 8.0 11,5 2 -3/16 56 - - - A4 -
Approved Temperature Ratings Approved Finishes
1 - Brass, Chrome- Enloy ® , White Polyester', Black Polyester and Black Teflon
A -155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 2 - Brass, Chrome-Enloe, White Poly Finish Black Poly Finish and Black Teflon
212 °F (100 °C), 286 °F (141 °C), and 360 °F 3 -White Polyester, Black Polyester, Black Teflon ® , Wax - Coated.Brass, and Wax over Polyester
(182 °C) 4 - Brass, Chrome- Enloy®, White Polyester, and Black Polyester
B -155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 5 - Brass, Chrome- Enloy ® , White Poly Finish, and Black Poly Finish
286 °F (141 °C), and 360 °F (182 °C) 6 - White Poly Finish, Black Poly Finish, and Wax- Coated Brass (corrosion resistant)
C -155 °F (68 °C), 175 °F (79 °C), 200 °F(93 °C), 7 - Brass and Chrome- Enloy
and 212 °F (100 °C) 8 - Wax- Coated Brass and Wax Over Polyester
D -155 °F (68 °C), 175 °F (79 °C), and 200 °F 9 - Wax- Coated Brass and Wax Over Poly Finish
(93 °C) 10 - Wax- Coated Brass (corrosion resistant)
E - 286 °F (141 °C)� 11 - High Temperature 200 °F (93 °C) Wax Coating (corrosion resistant); maximum ambient
F - 500 °F (260 °C) temperature allowed at ceiling = 150 °F (65 °C)
1 Base part number shown. For complete part number, refer to Viking's current pnce schedule.
2 This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
3 Accepted for use, City of New York Department of Buildings, MEA Number 89 -92 -E, Vol. XII.
' Listed by Underwnters Laboratories Inc. for use in the U.S. and Canada.
5 cULus Listed as corrosion- resistant.
6 Metric K- factor shown is for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metric K- factor shown by 10.0.
7 Spnnklers of Ultra -High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures
• above 300 °F (149 °C). Where the ambient temperature around the Ultra -High temperature rated sprinkler is significantly reduced below 300 °F
(149 °C), the response time of the Ultra -High temperature rated spnnkler may be severely retarded.
8 FM Approval of Viking Micromatic Standard Response Recessed Pendent Spnnklers installed with the Viking Micromatic Model E -1 or E -2 ,
Recessed Escutcheon is limited to wet systems and preaction systems qualifying as wet systems, for hazard occupancies up to and including
Ordinary Hazard, Group II
9 Listings and Approvals limited to Light- Hazard Occupancies with hydraulically calculated wet systems only.
10 The spnnkler orifice is bushed.
11 Refer to the "Sprinkler Accessories" section for technical data on approved escutcheons and other accessones. Escutcheons must be ordered
separately from sprinklers. Refer to Viking's current pnce schedule.
t2S pnnklers 10173, 10189, and 10188 are available on special order.
Spacing Requirements: Maximum spacing 15 ft. (4,6 m), minimum spacing 6 ft. (1,8 m).
•
June 17, 2005 Sprinkler 11 c -
®
MI CROMATIC ® AND
TECHNICAL DATA Micro maticHP ® STANDARD
' RESPONSE SPRINKLERS .
Approval Chart • 1 Temperature KEY
Finish
MicromaticHP Standard Response Pendent Sprinklers A
Maximum 250 PSI WWP
Standard Orifice
• Thread Size Max. Sprinkler Description Nominal K- Factor Overall Length Listings and Approvals
Pressure
NPT BSP PSIG Style Base Part Number SIN U.S. metric Inch mm cULus FM NYC VdS LPCB
' /Z" 15 mm 250 Pendent 09992 VK122 5.6 8,1 2 -1/4 58 Al — — — —
Small Orifice
'A" 15 mm 250 Pendent 09994 VK023 2.8 4,0 2 -1/4 58 Al — — — —
Installed with the Viking Micromatic Model E -1 or E -2 Recessed Escutcheon
''A" 15 mm 250 Pendent 09992 VK122 5.6 8,1 2 -1/4 58 B1 — — — —
1 /2 15 mm 250 Pendent 09994 VK023 2.8 4,0 2 -1/4 58 B1 — — — —
Installed with the Viking Microfast® Model F -1 Adjustable Escutcheon
A" 15 mm 250 Pendent 09992 VK122 5.6 8,1 2 -1/4 58 Al — — — —
h" 15 mm 250 Pendent 09994 VK023 2.8 4,0 2 -1/4 58 Al — — — —
Approved Temperature Ratings Approved Finishes
A - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C) 1 - Brass, Chrome- Enloy ® , White Polyester Black Polyester
B - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) and Black Teflon
Footnotes
I Base part number shown. For complete part number, refer to Viking's current price schedule.
2 This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
3 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
4 cULus Listed as corrosion- resistant.
5 Metric K- factor shown is for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metric K- factor shown by 10.0.
6 Listings and Approvals limited to Light -Hazard Occupancies with hydraulically calculated wet systems only.
7 The sprinkler orifice is bushed.
8 The Microfast Model F -1 Adjustable Escutcheon is considered a surface- mounted escutcheon because it does not allow the fusible element of
the sprinkler to be recessed behind the face of the wall or ceiling.
9 Refer to the "SprinklerAccessories "section for technical data on approved escutcheons and other accessories. Escutcheons must be ordered
separately from sprinklers. Refer to Viking's current pnce schedule.
Spacing Requirements: Maximum spacing 15 ft. (4,6 m), minimum spacing 6 ft. (1,8 m)
Sprinkler Base Part No. 10139 Ceiling Opening Size: 2- 5/16" (59 mm) Minimum,
2 -1/2" (64 mm) Maximum.
with a standard 1/8" (3,1 mm)
F 2 -1/8" 2 � �
surface- mounted escutcheon. (54 mm)
(54 mm) ,
4 L!l'JE il'l
I - -- — = '
� � 7
IL• !I Ill i -a /4" Ib � I ���
2 -1/4" I ( 44,5 mm) 2 " 1 -1/2" (38 mm 1— � l 1 -1/a" (28,6 mm) BEIM
(58 mm)
itbli? �� (51 mm) I l I Minimum Minimu (44,5 mm) lira I j ii + Maximum Maximum - --
• Sprinkler Base Part No. 10139 Sprinkler Base Part No. 10139
Spnnkler Base installed with a Microfast installed with a Micromatic
Part No. 10139 Model F -1 Adjustable Escutcheon. Model E - Recessed Escutcheon
ter* for sprinklers with temperature rat- is also to be used for wax coated spnn- NOTE: Recessed pendent sprinklers
• ings through 286 °F (141 °C). klers. with protective caps must use wrench
' Wax Over Polyester unavailable for Spnnkler B. Wrench for Polyester and Teflon 12144W/B.
Base Part Nos. 09992, 09993, 09994, and
o999s. coated and recessed Micromatic and '"A 'A" ratchet is required (not available from Vi-
. ACCESSORIES MicromaticHP Standard Response Refer to t "Spnnkler Accessories" sec -
Sprinkler Wrenches: Sprinklers: Part No. 07398W* (avail p
A. Standard wrench. Part No. 10896W/B able since 1990), or Part No. tion of the data book.
(available since 2000) or 05000CW /B 12144W/B'", available since 2003.
(no longer available). Standard wrench
r
Sprinkler 11 d June 17, 2005
NIKING ® MICROMATIC AND
TECHNICAL DATA MicromaticHP STANDARD
RESPONSE SPRINKLERS
Approval Chart Temperature KEY
Finish
Micromatic and MicromaticHP Standard Response Al
Upright and Conventional Sprinklers
Maximum 175 PSI WWP
Standard Orifice
Thread Size Max. Sprinkler Description Nominal Overall Listings and Approvals
Pressure K- Factor Lencth
NPT BSP PSIG Style Base Part SIN U.S. metric s a Inch mm cULus FM NYC VdS LPCB
Number
' /2 " _ 15 mm 175 Upright 10138 VK100 5.6 8,1 2 -3/16 56 B14, El1, F13, G9 A15, D12, G15 B14, El1, F13 - -
/2" _ 15 mm 175 Upright 10233 VK145 5 6 8,1 2 -3/16 56 - A8, D7, G8 - B6 B9, E3
- 15 mm 175 Upright 10174 VK145 5.6 8,1 2 -3/16 56 - A8, D7, G8 - - B9, E3
- 15 mm 175 Upright 10193 VK100 5.6 8,1 2 -3/16 56 B1, El0, F13, G9 A8, D7, G8 B1, E10, F13 - -
Large Orifice
'A" 15 mm 175 Upright 10220 VK200 8 0 11,5 2 -3/8 60 B2, El1, F13, G9 B8, E12, G8 B2, E11 - -
3 / " 20 mm 175 Upright 10141 VK200 8.0 11,5 2 -5/16 59 B2, Eli, F13, G9 B8, E12, G8 B2, E11, F13 B6 B5, El1
- 15 mm 175 Upright 10190 VK200 8 0 1 1 , 5 2 -3/8 60 B1, E10, F13, G9 B8, E12, G8 - - -
- 20 mm 175 Upnght 10169 VK200 8.0 11,5 2 -5/16 59 81, El0, F13 B8, E12, G8 - - 89, E3
Small Orifice
'/2" 15 mm 175 Upnght 10218 VK001 2.8 4,0 2 -3/16 56 B1, E10, F13 E9, E12 - - -
' /A" 15 mm 175 Upright 10219 VK002 4.2 6,0 2 -3/16 56 B1, E10, F13 - - - -
- 15 mm 175 Upright 10191 VK002 4.2 6,0 2 -3/16 56 B1, E10, F13 - - - -
- 15 mm 175 Upright 10192 VK001 2.8 4,0 2 -3/16 56 B1, E10, F13 E9, E12 - - -
- 10 mm 175 Upright 10176 VK002 4.2 6,0 2 -3/16 56 - - - 016 B9, E3
Conventional
' /s" 15 mm 175 Cony. 10227 VK118 5.6 8,1 2 -3/16 56 B1, E10, F13 - B1, E10, F13 B16 B5, E10
' A " 20 mm 175 Cony. 10228 VK120 8.0 1 1 , 5 2 -5/16 59 B1, E10, F13 - B1, E10, F13 - B5, E10
_ - 15 mm 175 Cony. 10172 VK118 5.6 8,1 2 -3/16 56 B1, E10, F13 - - - 85, E10
_ - 20 mm 175 Cony. 10168 VK120 8.0 11,5 2 -5/16 59 B1, E10, F.13 - - - B5, E10
3/4" 20 mm 175 Conv. 12106 VK120 8.0 11,5 2 -5/16 59 - - - B16 -
Maximum 250 PSI WWP
Standard Orifice
Y 115 mm1 250 'Upright! 09993 IVK124I 5.6 1 8,1 12 -1/4 158 Cl 1 - I - - -
Small Orificee
'h" 15 mm 250 Upnght 09995 VK021 2.8 4,0 1 2 -1/4 58 Cl - - - -
Approved Finishes
Approved Temperature Ratings 1 - Brass, Chrome -Enloe ® , White Polyester', Black Polyester and Black Teflon
2 - Brass, Chrome - Enloe White Poly Finishs, Black Polyesters, and Black Teflon
A -155 °F (68 °C), 175 °F (79 °C), 200 °F 3 -White Polyester, Black Polyester, Black Teflon Wax- Coated Brass, and Wax over Polyester
(93 °C), 212 °F (100 °C), 286 °F (141 °C), 4- White Poly Finish, Black Polyester, BlackTeflon� Wax- Coated Brass, and Wax over Polyester
B -155 F (68 ( C), 175 °F (79 °C), 200 °F 6 -Bass, Ch ome E y White P oly s Finish and and Black Polyester
(93 °C), 286 °F (141 °C), and 360 °F 7 - White Poly Finish and Wax- Coated Brass (corrosion resistant)
(182 °C) 8 - Brass, Chrome - Enloe and White Poly Finish
C -155 °F (68 °C), 175 °F (79 "C), 200 °F 9 - Brass and Chrome - Enloy
(93 °C), and 286 °F (141 °C) 10 - Wax - Coated Brass and Wax over Polyester
D -155 °F (68 °C), 175 °F (79 °C), 200 °F 11 - Wax - Coated Brass and Wax over Poly Finish
(93 °C), and 212 °F (100 °C) 12 - Wax- Coated Brass (corrosion resistant)
E - 155 °F (68 °C), 175 °F (79 °C), and 200 13 - 200 °F (93 °C) High-Temperature Wax Coating (corrosion resistant); maximum ambient tern -
°F (93 °C) perature allowed at ceiling = 150 °F (65 °C.)
F - 286 °F (141 °C) 14 - Brass, Chrome- Enloy ® , White Poly Finish', Black Poly Finish and Black Teflon
G - 500 °F (260 °C) 15 - Brass, Chrome- Enloy ® , White Poly Finish, and Black Poly Finish
16 - Brass, Chrome-Enloe, White Polyester, and Black Polyester
1 Base part number shown. For complete part number, refer to Viking's current pnce schedule.
2 This table shows the listings and approvals available at the time of punting. Other approvals may be in process.
3 Accepted for use, City of New York Department of Buildings, MEA Number 89 -92 -E, Vol. XII.
a Listed by Underwnters Laboratories Inc. for use in the U.S. and Canada.
s cULus Listed as corrosion- resistant.
6 Metric K- factor shown is for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metnc K- factorshown by 10.0.
7 Spnnklers of Ultra -High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures
above 300 °F (149 °C). Where the ambient temperature around the Ultra -High temperature rated sprinkler is significantly reduced below
300 °F (149 °C), the response time of the Ultra -High temperature rated spnnkler may be severely retarded.
6 Listings and Approvals limited to Light- Hazard Occupancies with hydraulically calculated wet systems only.
9 The spnnkler orifice is bushed.
10 Spnnklers 10168 and10172 are available on special order.
11 Accepted for use, City of New York Department of Buildings, MEA Number 89 -92 -E, Vol. III
Spacing Requirements: Maximum spacing 15 ft. (4,6 m), minimum spacing 6 ft. (1,8 m) for upright sprinklers. Conventional (old -style) sprinklers
must be spaced in accordance with the latest standards of NFPA, LPCB, and VdS, and any other applicable standards.
Replaces page 11 a -d, dated April 15, 2005 (updated FM Approval for Sprinkler VK102). Refer to Form No. F_100397
technical data page SR1 -2 for general care, installation, and maintenance information.