Correspondence April 6, 2007
RE:MODULAR CLASSROOM
Permit Number BUP 2007 -00044 Construction Type: VB
Tenant Name: Tigard Assembly Occupancy Type: E
Address: 11265 SW Gaarde St. Occupant Load: 86
Area: 1760 Sq. Ft. Stories: 1
Sprinklers: No Hazard: N/A
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC),
2004 edition; the Oregon Fire Code (OFC), 2004 edition and NFPA 72 Alarm Code. The
submitted plans are approved subject to the following.
Manual Devices
1. Manual Fire Alarm activation devices shall be mounted a minimum of 42 inches and a
maximum of 48 inches measured vertically from the floor to the activating handle or
lever of the device. Section 907.4.2 OFC.
Visual Devices (Section 1109.14 OSSC)
1 Visual signal appliances shall be provided in the building in each area
2. Visual alarms shall be located not less than 80 inches and not more than 96 inches above
the floor level. When a low ceiling exists, the visual alarm shall be mounted at least 6
inches below the ceiling.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road fronting
the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson,