Report } City of Tigard
13125 SW Hall Blvd. Tigard, OR 97223 503.639.4171
TIGARD r r
Residential Certificate of =I�ccupancy
Permit No.: f Address:
Owner /Contractor: -.6
2 r'
Date of Final Inspection: J � Inspector: t �' / ,
This structure has been found to be in substantial compliance with the provisions of the
State of Oregon Residential Specialty Code and is hereby approved for occupancy.
Re: Stone Chase — of 13
}- 1-e62 113` Avenue — Tigard, OR
/ 1 9 Permit #MST2005 -00419
Dear Sir or Madam:
This is to certify that in accordance with Section 1704.1.2 of the International Building Code, we have performed special
inspection of the following item(s) per our inspection reports only:
Installation of Adhesive Anchors
Structural Steel
All inspections and tests were performed and reported according to the requirements of Project Documents and, to the
best of our knowledge, the work was in conformance with the approved plans and specifications, approved change orders
and applicable workmanship provisions of the State Building Code and Standards, as well as the structural engineer's
design changes, approvals and verbal instructions.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced, except in
full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TES ING, NC.
Neil S. Shannon
Project Manager
NSS /Id
cc: Gerritz Biggi Custom Homes — Steve Gibson
City of Tigard Building Division
Alan Mascord Design Associates, Inc.
•
Main Ofee Salrm Office Bend Ogee
Carlson Testing, Inc. Y43A f{•1 /.a._]kr, 4060 Hudson St NE 63025 OR 977 Rd f]
Tigard, 4 S 11 9713 .Salem, OR 97301 Bend, OR 97700 2
Phone (503) 684 -3460 Phone (503)5,49-1252 Phone. (547) 330 -9155
Fax (5/13) 6.W -0954 Far /5271 589-1309 Ins 15411330-9167
Construction Materials Testing & Inspection
Special Inspection
FINAL SUMMARY LETTER
June 2, 2008
T0601622
City of Tigard
13125 SW Hall Blvd
Tigard, OR 97223 -8199
Attn: Building Department
Re: Stone Chase -Lot 13
/1 -)1 79 E.,e- frl
Permit #MST2005 -00419
Dear Sir or Madam:
This is to certify that in accordance with Section 1704.1.2 of the International Building Code, we have performed special
inspection of the following item(s) per our inspection reports only:
Installation of Adhesive Anchors
Structural Steel
All inspections and tests were performed and reported according to the requirements of Project Documents and, to the
best of our knowledge, the work was in conformance with the approved plans and specifications, approved change orders
and applicable workmanship provisions of the State Building Code and Standards, as well as the structural engineer's
design changes, approvals and verbal instructions.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be reproduced, except in
full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TES ING, NC.
Neil S. Shannon
Project Manager
NSS /Id
cc: Gerritz Biggi Custom Homes - Steve Gibson
City of Tigard Building Division
Alan Mascord Design Associates, Inc.
Main Office Salem Office Bend Office
1 � P.O. Box 23814 4060 Hudson Ave., NE P.O. Box 7918
e Tigard, Oregon 97281 Salem, OR 97301 Bend, OR 97708
Carlson T Inc. Phone (503) 684 -3460 P9 12 P0 5
11 FAX (503) 684 -0954 FAX (503) 589-1309 FAX (541) 330 -9163
May 29, 2008
T0601622.CTI
Permit No. MST2005 -00419
FIELD INSPECTION REPORT
DATES COVERED: May 28, 2008
PROJECT: Stone Chase — Lot 13
ADDRESS: 11279 SW Ellson Lane — Tigard, OR
INSPECTOR: N. Shannon, COP #655, WABO #SHA965609, OBOA #321
05- 28 -08: Structural Steel
As requested, CTI representative was on site for special inspection of structural steel to ORS and
design requirements. Previous inspections verified welding at all locations of moment frames in the
north wall except for the shear plate connection, detail 1 on page 16.
Engineer's previous review will allow a 50% inspection. Visual inspection of the east connection
reveals that standard machine bolts have been substituted for high strength A325 bolts and that
there is no indication that the vertical edge of the shear plate has been welded.
See Incompleted Items List (NCL) attached. The following non - complying item was observed:
0 NCL 5: Shear plate connections at north moment frames do not have A325 bolts and are not
welded (detail 1 on page 16).
** *CHECK ONE BOX ONLY*** YES NO
1. This is a preliminary inspection only. — OR — ❑
2. The work inspected conforms to acceptance criteria listed above. If "No," the portions of the
•
work that are non - conforming items are clearly stated above and will be added to the NCL.
Remaining portions of the work, which are not preliminary in nature, are to be considered as ❑
conforming.
Our reports pertain to the material tested /inspected only. Information contained herein is not to be
reproduced, except in full, without prior authorization from this office.
If there are any further questions regarding this matter, please do not hesitate to contact this office.
Respectfully submitted,
CARLSON TESTING, INC.
Neil S. Shannon
Project Manager
NS /sab
Attachment
cc Gerritz Biggi Custom Homes — Steve Gibson
City of Tigard Building Division
Carlson Testing, Inc.
Incompleted Items List (NCL)
May 39. 2005
1'0601622.
Project Name: STONE CHASE - LOT 13
Pro)ectAddress: 11279 SW ELLSON LANE TIGARD OR
Permit No: MST2005 -00419
P.O. No: Project Manager: NEIL S. SHANNON
Item # Insp. Date Item Description Compliance CTI Sign -Off Date
Corrected
1 BRD 04/21/2006 END PLATES ON COLUMNS WELDED WITH 3/16" PARTIAL APPROVED AS BUILT - PER NEIL S. SHANNON 11/27/2007
PENETRATION GROOVE WELD IN FIELD AT TOP OF PLATE LETTER FROM EOR DATED
AND FILLET WELDED IN SHOP AT INSIDE OF PLATE NEED 11/14/07.
•
CORRECTION. WELDING DETAIL ON PLANS FOR FILLET
WELD AT BOTH SIDES OF PLATE NOT CORRECT. UNABLE
TO VERIFY WELD CONFORMANCE WITH CONTRACT
DOCUMENTS.
2 BRD 04/21/2006 SINGLE BEVEL GROOVE PREPARATION AT BOTTOM FLANGE APPROVED AS BUILT - PER NEIL S. SHANNON 11/27/2007
OF BEAM REQUIRED OVERHEAD WELDING. PLAN DETAILED LETTER FROM EOR DATED
A CJP WELD IN FLAT POSITION (BEVEL WAS GROOVED 11/14/07.
UPSIDE DOWN). WELDING PERFORMED PER VERBAL
APPROVAL FROM E.O.R. /WRITTEN APPROVAL REQUIRED.
3 THIS ITEM WAS NOT APPLICABLE TO THIS PROJECT. 04/24/2006
4 THIS ITEM WAS NOT APPLICABLE TO THIS PROJECT. 04/24/2006
5 NSS 05/28/2008 SHEAR PLATE CONNECTIONS AT NORTH MOMENT FRAME DO
NOT HAVE A325 BOLTS & ARE NOT WELDED (DET. 1 ON
PG. 16).
ry :GERRITZ BIGGI CUSTOM HOMES - STEVE GIBSON
CITY OF TIGARD BUILDING DIVISION
ALAN MASCORD DESIGN ASSOCIATES INC
ENTERPRISE FABRICATORS CO INC
Page: 1
06/02/08 MON 16:37 FAX 503 670 9147 CARLSON TESTING 12003
.Main Office Salem Office Bend Office
.0, Box 23814 4060 Hudson Ave., NF P.O. Rox 7918
Carlson Testing, Inc. PFdne (0 (503) regon 97281 S, OR 9731 Bend, 6$4 -0954 03) 684-3460 P on (503) 589 -1252 Phone (5O) 30 9$55
FAX (503) 589 -1309 FAX (541) 330 -9153
June 2, 2008
Project #T0601622 •
Permit No. MST2005 -00419 FILE
Gerritz Biggi Custom Homes — Steve Gibson
9550 SW Beaverton - Hillsdale Highway
Beaver OR 97005 -3309
Re: Stone Chase — Lot •
11279 SW Elison Lane
Tigard, OR
To Whom It May Concern:
•
As requested I have received and reviewed Engineer of Record fax dated May 30, 2008 from
Richard Rowell of Rowell Engineering. Engineer of Record has reviewed CTI's field report of
May 28, 2008 and concluded that no additional weld is required. This information clears item #5
on the Incomplete Items List (NCL)_ See attached updated list.
If there are any further questions regarding this matter, please do not hesitate to contact this
office.
Respectfully submitted, �
•
CARLSON TESTING, INC.
•
Neil S. Shannon
Project Manager •
Id
cc: Gerritz Biggi Custom Homes — Steve Gibson
City of Tigard Building Division
Alan Mascord Design Associates; Inc.
•
•
•
•
Carlson Testing Inc.
Incompleted Items List (NCL)
eo
Jun 02, 2003
•
T0601 622. °°
Project Name: STONE CEASE LCT 13
Project Address: 11279 SW ELLSCN LANE TIGARD OR
Permit No: t'1ST2025 -0:419
P.O. No: Project Manager: NEIL S. SHANNON
Date
Item # Insp. Date item Description Compliance CTI Sign -Off Corrected at
I 0
?RD 04/21/2006 END PLATES ON COLUMNS WELDED WITH 3/1 PARTIAL APPROVED AS BUILT - PER NEIL S. SHANNON 11/27/2007 ca
PENETRATION GROOVE WELD >N FIELD AT TOP OF PLATE LETTER FROM FOR DATED
AND FILLET WELDED IN SHOP AT INSID ^E OF PLATE NEED 1:/ 14/07.
CCRR3CTIOPI. iiELDING DETAIL ON PLANS FOR FIL_,ET
WELD AT BOTH S =DES OF PLATE NOT CORRECT. UNABLE -I
TO VERIFY WELD CONFORMANCE WITH CONTRACT
DOCUMENTS.
2 BR E- 04/21/2C06 S :NGLE BEVEL GROOVE PREPARATION AT BOTTOM FLANGE AP= AS BUILT - PER NEIL S. SHANNON 11/27/2007
C)
OF BEAM REQUIRED OVERHEAD WELDING_ PLAN DETAILED LETTER FRO:v: FOR DATED
A CJP ICELD If. FL•r� �Oz�I` =CFi TSEPEL Ti7141'0 ci)
UPSIDE DOWN. EELD =NG PERFORMED PER VERBAL,
APPROVAL FROM E.O.R./WRITTEN APPRO:'AL REQUIRED. H
t=]
— — H
3 THIS ITEI.1 WAS POT APPLICABLE TO THIS PROJECT. 04/24/2006
C)
4 THIS ITEM WAS NOT APPLICABLE TO THIS PROJECT. 04/24/2.06
5 \SS 05/26/2004 SHEAR PLATE CONNECTIONS AT NORTH MOMENT FRAME DO - APPROVED AS BUILT PER NEIL S. SHANNON 06/02/2008
NOT HAVE A325 BOLTS & ARE NCT WELDED (DET_ _ ON FOR LETTER OF 05/30/2008
PG, 16).
Mori
I
CC: GERRITZ BIGGI CUSTCY HOMES - STEVE GIBSON
CITY OF TIGARD BUILDING DI:'ISION
ALAN NASCORN DESIGN ASSOCIATES INC
ENTERPRISE F ?BP.ICATGRS CO INC Pace: 1 •
06/02/08 MON 16:37 FAX 503 670 9147 CARLSON TESTING U005
;n!;m 1
''�'•..:'V l.' JiUII[ rKl!r C`(I �: Ui i;I,I Y re - 5:3'S,';',1 „ �• ;I,(
�11,.1�1, .I'J Zl, l
. 1 . . 1 J:ll'ii IVu. finll,, (43 F 7
k 16:17 Seis:;,ab(bl ROWELL FNGINEERIWG PpGE_ 82/132
10S70 SE Washington Street
hn Suite 210
COQ LL 2N IK CRI:N �' > D( ��PRI.1 �4N�o Portland, °P .97216
C!y!1. STr2UC'TllRnt_ ENGINEERS Tel, 503 234 - 8292
Fex 503. 254 -e'61
May 30, 2008
FILE COPY
PROJECT: Mascord Plan 2289E
Lot 13 Stone Chase
Tigard, Oregon
SUBJECT: Steel Moment Frame.
Per Carlson Testing's field report dated 5 - 28 - 08, there does not appear to a weld
connecting the shear plate to the horizontal member, and the High strength bolts,
were installed as machine bolts.
Discussion: The bolts are or y for temporary restraint, while the frame is being
erected, so this is not an important factor. However the vertical weld connecting the
. shear plate to the horizontal member Is important. The Horizontal member is
connected to the vertical frame in three ways. The top and bottom flanges are
connected to resist the moment. The web is fillet welded to the vertical member on
one side. The web is welded to the shear; plate, which is in turn welded to the
vertical member, Both of these web welds are to transfer the shear. The missing
weld means we are missing half of our sheer connection. In this case the shear
requirement is rather low, and the one fillet weld from the web to the vertical member
is enough to transfer the shear.
Conclusion: The frame does not need additional welding. or the bolts replaced.