Correspondence (9) �
June 7, 2004 /Oawu1i 5 r
CITY OF TIGARD
OREGON
Southwest Church of Christ
9725 SW Durham Road
Tigard, OR 97224
RE: ADDITION OF NEW AUDITORIUM
Project Information
Site Permit: BUP2004 -00164 Construction Type: V - 1HR
Tenant Name: SW Church of Christ Occupancy Type: A2.1
Address: 9725 SW Durham Road Occupant Load: 940
Area: 8,692 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following conditions.
1. Exit doors shall be provided with panic hardware. 1007.2.5 OSSC
2. Exit signs shall be illuminated at all times and shall be provided with a second source
of power that will provide 1 '/2 hours of illumination in case of primary power loss.
1003.2.8.5 OSSC
3. The means of egress shall be provided with illumination of not less than 1 foot candle
at the floor level anytime the building is occupied. The means of egress illumination
shall be provided with a second source of power in case of primary power loss.
1003.2.9.2 OSSC
4. Provide one 2 -A rated fire extinguisher in the new area. The extinguisher shall be
located so that no usable space has a distance greater than 75 feet to the extinguisher.
Standard 10 -1, Chapter 3 TVFR99 -01.
• Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop
Drawings, etc, will be charged a deferred submittal fee based on the valuation
of the portion of the work being deferred. The minimum fee shall be $200.00.
Special Inspection: Special inspection is required as identified on the "SPECIAL
INSPECTION MATRIX" on Sheet S1.0. The special inspection agency of record shall
furnish inspection reports to the Engineer of Record, Lewis & Van Vleet Consulting
Engineers, the General Contractor and the City of Tigard, Building Division, attention Hap
Watkins. All discrepancies shall be brought to the immediate attention of the general
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
contractor for correction. The special inspector shall submit a fmal signed report stating
whether the work requiring special inspection was, to the best of the inspector's knowledge,
in conformance with the approved plans and specifications and the applicable workmanship
• provisions of the code. 1701.3 OSSC
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processi ': the documents.
Respectful ,
rian Maio"
enior P, . Examiner
j