Correspondence FILE COPY April 26, 2004 CITY OF TIGARD John Westfal OREGON Dull Olson Weekes Architects • 319 SW Washington Street, #200 Portland, OR 97204 RE: MECHANICAL EQUIPMENT @ SCIENCE REMODEL Project Information Building Permit: MEC2004 -00078 Construction Type: VN Tenant Name: Tigard High School Occupancy Type: E - Address: 9000 SW Durham Road The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99- 01) 1999 edition. The submitted plans are approved subject to the following. 1. Fume Hoods shall be inter- connected with the make -up air system. 2. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) 3. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC 4. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 5. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. 304.10 OMSC 6. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 7 Appliances installed on roofs or elevated structures exceeding 16 feet in height shall be provided with a permanent means of access grade or floor level. 306.5 OMSC 8. Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 9. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC • 10. Smoke detectors shall be installed in return air systems with a design capacity greater than 2000 cfm. Upon activation, the smoke detector shall shut down the air distribution system. Smoke detectors shall be connected to a fire alarm system and shall activate an audible and visible alarm at a constantly attended location. 606.2, 606.4 & 606.4.1 OMSC 11. Suspended -type unit heaters/VAV's shall be supported by non - combustible elements that are designed and constructed to accommodate the weight and dynamic loads 920.2 OMSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and • •' essing the documents. Resp- Bri 1alo , Senior Plans Examiner • FILL uuri / /0 \ t� April 15, 2004 '�I� CITY OF TIGARD John Westfal Dull Olson Weekes Architects OREGON • 319 SW Washington Street, #200 Portland, OR 97204 RE: MECHANICAL EQUIPMENT @ SCIENCE REMODEL Project Information Building Permit: MEC2004 -00078 Construction Type: VN Tenant Name: Tigard High School Occupancy Type: E -1 Address: 9000 SW Durham Road The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99- 01) 1999 edition. The following item remains and needs clarification prior to the issuance of the permit. • 5 Clarify membrane penetration protection where Fire wrapped, exhaust duct from fume hood penetrates the ceiling membrane. Manufacturer's listing may have details for this application. RESPONSE PARTIALLY ACCEPTED The response submitted to this item is acceptable when supplemented with drawings. I have enclosed a copy of an International Evaluation Report. The supplemental drawings shall be in compliance with, and clarify the items identified in the International Evaluation Report. Detailing for the penetration at the floor /ceiling should be site specific and similar to Figure 3 of the report. The report requires 16 gauge duct, spec book says 20 gauge, page 15880 -1. FYI I am resistant to deferring this item. I don't want to cause the contractor to rebuild any construction if a shaft ended up being the only solution acceptable to the contractor. When submitting revised drawings or additional information, please attach a copy of the • 6 • enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Brian Blalock, Senior Plans Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 D U L L 0 L S O N W E E K E S ARCHITECTURE + INTERIORS + PLANNING .architects inc. COPY ECE VED DATE: April 1, 2004 APR 0 1 2004 TO: Brian Blaylock City of Tigard CITY OF TIGARD BUILDING DIVISION FROM: Keith Johnson • COPY: Jim Little Robinson Construction Craig Markus Cornerstone Construction Management Scott Miller MFIA Consulting Engineers PROJECT: MEC2004 -00078 Tigard HS Science Remodel RE: Mechanical Review Comments - Your Letter of March 25, 2004. Enclosed with this memo please find a reply letter from MFIA which addresses your review comments individually as requested. We will issue a change order request for installation of fire suppression in the fume hood exhaust ducts (Item #3) to the contractor. Attachments also include the following: • City of Tigard Letter of Transmittal. • Seismic calculations for rooftop units: RTU -1, RTU -04 -2, and RTU -04 -3 (12 pages total). • Technical information for duct wrap material (6 pages). If you have questions about this reply, please feel free to give me a call at 503 - 226 -6950. Thanks for your review of this portion of the project. Ol MEMORANDUM 319 SW WASHINGTON ST. #200 ( PORTLAND, OR 97204 t: 503 226 6950 J: 503 273 9192 I www.doua.cu'n .. t=do2Klpro;onts;02054 ,,.xr HS - 200e;1- Prcier r !cl\Norn Proc000lo k13 CoJe- Peorno;Riay,oc< 013104 A'echor, cal Rog ner Car rre ,ts aa:: FILE COPY ; m March 31, 2004 APR 01 2004 CITY OF TIGARD FI BUILDING DIVISION A MEMO TO: John Westfall INC. DOWA SUBJECT: Tigard HS Remodel- Phase 1 City of Tigard Plan Review Response 0 In regards to the plan review comments from the City of Tigard, we have the following N responses. S ✓ 1) Calculations for the attachment of rooftop units are attached. Details for the attachment are provided on detail 1 of sheet M6.1 of the construction documents. 2) The make -up air that will be interlocked with the fume hoods is provided by the L rooftop units through a control sequence (see detail 3 on sheet M5.1). The individual return air dampers provided per space are controlled to maintain a negative pressure T in the classrooms relative to the corridor. When the fume hoods are in operation, the return damper in the main duct will close allowing the air from the space to be exhausted through the fume hood. � �v N 3) A fire suppression system will be added in the fume hood exhaust ducts, per 510.7. Dpi° 4) The material to be used in the science and chemistry hoods include the following: G • Hydrogen Sulfide • Acetone • Isopropyl Alcohol E • Hydrochloric acid Of these materials Isopropyl Alcohol has the lowest Lower Flammability Limit (LFL) N of 2.0. If we are to stay below 25% of the LFL we need to provide at least 0.0002 CFM at each hood. Since each hood is sized for 750 CFM the requirements for G dilution are met with a significant safety factor. The above information is based on a vaporization rate of Isopropyl Alcohol of 789 onces /cu.ft. at room temperature with I exposed surface similar to laboratory conditions. Based on this we believe the N installation as designed exceeds code requirements. 5) Installation instructions for the fire - wrapped fume hood exhaust ducts, penetrating the E rated ceiling, are attached. E R MFIA, INC. S Robert Russell g \dowa architects \7104a1_tigard hs 2004\ docs\ 7104a1- m- march2604- phasel- cot- p(an- review.doc TIDE COPY March 25, 2004 CI FTG.2 u • John Westfal Dull Olson Weekes Architects OREGON 319 SW Washington Street, #200 Portland, OR 97204 RE: MECHANICAL EQUIPMENT @ SCIENCE REMODEL Project Information Building Permit: MEC2004 -00078 Construction Type: VN Tenant Name: Tigard High School Occupancy Type: E -1 Address: 9000 SW Durham Road The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99- 01) 1999 edition. The following information is required prior to the issuance of the permit. 1. Provide calculations and details for the attachment of the rooftop mechanical units. Permanent equipment 400 lbs and over, shall have their attachments designed in accordance with formulas in section 1632 of the Oregon Structural Specialty Code. 2. Clarify the Make -up air that will be interlocked to the exhaust fans for the fume hoods. Section 510.5.5 OMSC. 3. The ducts serving the fume hood shall be provided with an automatic fire suppression system unless the fumes and vapors qualify for exception of section 510.7, OMSC. Clarify fumes and vapors. 4. Provide clarification regarding the dilution of the contaminants as required by section 510.5.4 OMSC. 5. Clarify membrane penetration protection where Fire wrapped, exhaust duct from fume hood penetrates the ceiling membrane. Manufacturer's listing may have details for this application. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing tdocuments. Respectful), j <7 an Blalock, Senior Plans Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 A l Letter of Transmittal Building Division .da City of Tigard DATE RECEIVED: TO: ne-I A13 6(..44,--(LOGV— RECEIVED DEPT: BUILDING DIVISION APR 01 2004 FROM: 151A-NISOIL) CITY OF TIGARD BUILDING DIVISION COMPANY: OUL- DUDO1 AnCa. PHONE NO.: C - By:14 (DC5 RE: N,E.C, Zoo4 - ODD 72, (Case number, site address, etc.) To P1-40 0-5 rti 'L4 (c tib`tor), (Project name or subdivision name and lot number) ATTACHED ARE THE FOLLOWING ITEMS: Additional set(s) of plans. Revisions: Cross section(s) and details. Wall bracing and/or lateral analysis. Floor/roof framing. Basement and retaining walls. Beam calculations. I Engineer's calculations. - VIOC, G�r%. Other (explain): ,t$1 7( bix MtP E* OUGT i.01.41° Trtz.44- 1"- PO REMARKS: II j'§e"Otilp Routed to Permit Technician „' 154:fe:', - fe 15u6, Dt ?"1:' Ihitials .,Reptint,Permits(per Plan Notified Applicant:. Date': i Building\Forms\LetterTransmittal doc 1/6/04