Correspondence April 28, 2004 CITY OF TIG Y OREGON Southwest Church of Christ 9725 SW Durham Road Tigard, OR 97224 RE: SITE WORK FOR NEW AUDITORIUM Project Information Site Permit: SIT2004 -00013 Construction Type: V - 1HR Tenant Name: SW Church of Christ Occupancy Type: A2.1 Address: 9725 SW Durham Road Occupant Load: 940 Area: 8,692 Sq Ft Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. EROSION • Erosion control measures shall be in place prior to excavation or grading. EXCAVATION • After site grading and prior to excavation for footings, a representative from Carlson Geotechnical shall observe the existing site subgrades to identify areas of excessive yielding. If the representative recommends structural fill, a special inspection agency shall be employed by the developer to provide reports to the City of Tigard Building Division, verifying compliance with the Soils Report. FIRE • All thrust blocking and piping shall be inspected prior to backfill. • The private fire service main shall be at least 30 inches below grade. • The private fire service main shall be flushed thoroughly before connection to the system riser in order to remove foreign materials that might have entered the main during the course the installation. The flow rate shall not be less than the water demand rate of the system. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 ACCESSIBILITY • Accessible walkways and routes shall not exceed a running slope of 1 unit vertical in 20 units horizontal (5% slope). Cross slopes shall not exceed 1 unit vertical in 50 units horizontal (2% slope). • Accessible parking spaces and access aisles shall be located on a surface with a slope not to exceed 1 unit vertical in 50 units horizontal in all directions. 1104.4.3 OSSC • Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC which may not include all of the requirements of the ADA. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and proces ' g the documents. Respectfull ian Bs' ock, SeniJ ' lans Examiner