Correspondence April 28, 2004 CITY OF TIG
Y
OREGON
Southwest Church of Christ
9725 SW Durham Road
Tigard, OR 97224
RE: SITE WORK FOR NEW AUDITORIUM
Project Information
Site Permit: SIT2004 -00013 Construction Type: V - 1HR
Tenant Name: SW Church of Christ Occupancy Type: A2.1
Address: 9725 SW Durham Road Occupant Load: 940
Area: 8,692 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following.
EROSION
• Erosion control measures shall be in place prior to excavation or grading.
EXCAVATION
• After site grading and prior to excavation for footings, a representative from Carlson
Geotechnical shall observe the existing site subgrades to identify areas of excessive
yielding. If the representative recommends structural fill, a special inspection
agency shall be employed by the developer to provide reports to the City of
Tigard Building Division, verifying compliance with the Soils Report.
FIRE
• All thrust blocking and piping shall be inspected prior to backfill.
• The private fire service main shall be at least 30 inches below grade.
• The private fire service main shall be flushed thoroughly before connection to the
system riser in order to remove foreign materials that might have entered the main
during the course the installation. The flow rate shall not be less than the water
demand rate of the system.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
ACCESSIBILITY
• Accessible walkways and routes shall not exceed a running slope of 1 unit vertical in
20 units horizontal (5% slope). Cross slopes shall not exceed 1 unit vertical in 50
units horizontal (2% slope).
• Accessible parking spaces and access aisles shall be located on a surface with a slope
not to exceed 1 unit vertical in 50 units horizontal in all directions. 1104.4.3 OSSC
•
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and proces ' g the documents.
Respectfull
ian Bs' ock,
SeniJ ' lans Examiner