Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Correspondence
i :. � May 2, 2005 L „,„146= ` CITY OF TI OREGON HVAC INC. Sherrie Robunson 5188 SE Intl Way Milwaukie, OR 97222 RE: HVAC MODIFICATIONS — VERIZON RSU Project Information Building Permit: MEC2005 -00191 Occupancy Type: S 2 Tenant Name: Verizon RSU Construction Type: V -B Address: / © 49090 Cascade Ave Occupant Load: NA Area: NA Stories: 1 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition. The submitted plans are approved subject to the following. 1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) 2. The building or structure shall not be weakened by the installation of mechanical systems. Where floors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with the Building Code. 302 OMSC 3. The cutting, notching and boring of framing members shall comply with OMSC Sections 302.3.1 through 302.5.3. 4. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 5. Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC 6. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC • 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 7. Smoke detectors shall be installed in return air systems with a design capacity greater than 2000 cfm. Upon activation, the smoke detector shall shut down the air distribution system. Smoke detectors shall be connected to a fire alarm system and shall activate an audible and visible alarm at a constantly attended location. 606.2, 606.4 & 606.4.1 OMSC 10. Mercury Thermostats. The State of Oregon prohibits the installation of thermostats that contain mercury in commercial and residential buildings. "In accordance with ORS 455.355, the disposal of thermostats that contain mercury shall be in accordance ' with programs established by thermostat manufacturers, their representative or distributor, or by delivery to sites that will ensure that the mercury does not become part of the solid waste stream or wastewater." Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. , When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectful! Val Henze!, Senior Plans Examiner